Old trane vav boxes post:16.02.2024 at 00:00

Old trane vav boxes

 
old trane vav boxes old trane vav boxes

The organization is establishing this application for a double OS. nbsp; this application can be very easily run in Ms Windows. Furthermore, you could also use that device on your Apple pc. it will not just remove all your Images and movies in addition to go, Appear at all the room youve stored.

Rather, it losslessly gaze them as well as backs up the original to your pc.

Old trane vav boxes/

Thread: Old Trane VAV retrofit quandry

So we are in the process of changing out all the controls in the Govt. buildings of a particular town. Old trane vav boxes tisha vav buiding we get to, happens to be the Tax building, has these old Trane VAV boxes that have the damper actuator inside in the box.it basically turns a threaded rod to move a round damper over the inlet hole and it backs away from the hole to allow air into the box. I cracked open the VAV box to see how it worked and it appears to have end switches at both ends that stop the shaft from turning at the appropriate place. There are 3 wires that leave the control board on the outside of the VAV box that go into the box to the accuator. The are labeled hot/open/close and I have verified its just 24v AC power open/power close. The end switches must be inline with its respected wire, either breaking the open wire or the close wire.

Heres where the problem comes in.all the materials for the entire job have been bought and whoever looked at this building missed these VAV boxes. We planned on using Siemens ATEC's and we may still do that. The boxes are only HW reheat. The ATEC has 2 spare DO's we could use to stroke damper. We would have to do everything with programming. Back in the day there was only one TEC(long board) that would hold programming but now when I look at applecation 6633 on WCIS the last sub point is PPCL state (Empty/Loaded).so this leads me to believe ATEC can now hold programming. Has anybody actaully old trane vav boxes PPCL into ATEC's? We could load all the programming into our panels but if the network goes down none of the VAV's would work right. Hopefully there are some Siemens guy out there that can provide some input.

Trane VAV Equipment Specifications

and Maintenance

VariTrane
Single-Duct and Fan-Powered Units

All VariTrane VAV models with pneumatic, electronic, DDC controls, and diffusers.
VCCF04 - 24
VCEF04 - 24
VCWF04 - 24

SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and airconditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment
by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in old trane vav boxes literature and
on the tags, stickers, and labels that are attached to the equipment.

June 2013

VAV-SVX08D-EN

Warnings, Cautions and Notices


Warnings, Cautions honeywell comfort point cp-vav Notices. Note that warnings,
cautions and notices appear at appropriate intervals
throughout this manual. Old trane vav boxes are provide to alert
installing contractors to potential hazards that could result
in death or personal injury. Cautions are designed to alert
personnel to hazardous situations that could result in
personal injury, while notices indicate a situation that
could result in equipment or property-damage-only
accidents.
Your personal safety and the vava usb c hub 8-in-1 adapter bestbuy operation of this
machine depend upon the strict observance of these
precautions.
Read this manual thoroughly before operating or servicing
this unit.

ATTENTION: Warnings, Cautions and Notices appear at

appropriate sections throughout this literature. Read


these carefully:
Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous
CAUTIONs situation which, if not avoided, could
result in minor or moderate injury. It
could also be used to alert against
unsafe practices.
a situation that could result in
NOTICE: Indicates
equipment or property-damage only

WARNING

must also be adhered to for responsible management of


refrigerants. Know the applicable laws and follow them.

WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.

WARNING
Personal Protective Equipment (PPE)
Required!
Installing/servicing this unit could result in exposure to
electrical, mechanical and chemical hazards.

Before installing/servicing this unit, technicians


MUST put on all Personal Protective Equipment (PPE)
recommended for the work being undertaken.
ALWAYS refer to appropriate MSDS sheets and OSHA
guidelines for proper PPE.

When working with or around hazardous chemicals,


ALWAYS refer to the appropriate MSDS sheets and
OSHA guidelines for information on allowable
personal exposure levels, proper respiratory
protection and handling recommendations.

If there is a risk of arc or flash, technicians MUST put


on all Personal Protective Equipment (PPE) in
accordance with NFPA 70E or other country-specific
requirements for arc flash protection, PRIOR to
servicing the unit.

Important
Environmental Concerns!
Scientific research has shown that certain man-made
chemicals can affect the earths naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of old trane vav boxes identified
chemicals that may affect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these
compounds have the same potential impact to the
environment.Trane advocates the responsible handling of
all refrigerants-including industry replacements for CFCs
such as HCFCs and HFCs.

Responsible Refrigerant Practices!


Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified.The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the old trane vav boxes that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
2013Trane All rights reserved

Failure to follow recommendations could result in death


or serious injury.

WARNING
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the
insulation in this product during installation,
maintenance or repair will expose you to airborne
particles of glass wool fibers and ceramic fibers known
to the state of California to cause cancer through
inhalation. Glass wool fibers could result in respiratory,
skin or eye irritation.

VAV-SVX08D-EN

Warnings, Cautions and Notices

Introduction

Trademarks

This manual describes the installation of VariTrane VAV


units with recommended wiring, piping, and mounting of
single-duct, dual-duct, fan-powered, low-height terminal
units, and diffusers.

Trane, VariTrane and theTrane vava usb c hub 8-in-1 adapter bestbuy are trademarks or


registered trademarks ofTrane in the United States and
other countries.Trane is a business of Ingersoll Rand. All
trademarks referenced in this document are the
trademarks of their respective owners.

See also the following reference documents:

BAS-SVX40A-EN Wireless Comm IOM

BAS-SVX55A-EN Wireless Comm Network Design


Best Practices Guide

LonTalk is a registered trademarks of Echelon Corporation.

Receiving and Handling


VariTrane units are shipped completely assembled with
the exceptions of optional attenuators for fan-powered
units and accessories.
Upon receiving old trane vav boxes equipment, complete the following:

Locate the nameplate and refer to the model and sales


order number and check that the correct units have
been delivered.

Inspect the control enclosures and air valve casing for


dents or punctures.

Verify that all options have been included, such as


filters, controls, heating coils, water valves, etc. Also
check that the unit voltages agree with the building
parameters.

Manually rotate fan (if applicable) to assure that there


are no obstructions within the housing.

Claims for in-transit damage must be filed


immediately with the delivery carrier.

For hot water re-heat units, check the coil fins and make
sure that coils are not damaged.

Locate and verify that the correct zone sensors are with
the order.These will be marked old trane vav boxes an orange
Accessories Enclosed label. Store in a secure
location until needed. Accessories lost at the job site
are NOT covered byTranes warranty.

If a discrepancy occurs between what was ordered and


what is received, contact you localTrane
representative immediately.

Read appropriate section in this old trane vav boxes for installation


procedures prior to starting equipment.

Upon receiving the equipment, please inspect each unit


and components for external or internal damage. Refer to
the bill of lading to insure all equipment old trane vav boxes accessories
have been received. Contact your localTrane sales
representative and notify the trucking company
immediately of any short ship or damaged equipment.

Revision Summary
VAV-SVX08D-EN. Added BottomAccess with Cam Lock
configuration and stand alone control information for
UCM 4.2, VV550 LonTalk, UC400, UC210 and WCI.

VAV-SVX08D-EN

Table of Contents
Warnings, Cautions and Notices. . 2
Introduction. 3

Model Number Descriptions. .


Single-Duct Units. .
Dual-Duct Units. . .
Fan-Powered Units. . .

5
5
7
8

Unit Information. 10
Single-Duct Units. . old trane vav boxes. 10
Dual-Duct Units. 10
Fan-Powered and Fan-Powered
Low-Height Units. . 11

Unit Installation. 12
Unit Setup. 25
(SCR) Motor Speed Control Adjustment
Procedure. 26
Electrically Commutated Motor (ECM). . 26

Wiring Diagrams. . old trane vav boxes. 40
Heaters with Contactors. . old trane vav boxes. 40
Maintenance. . 48
Installation of Diffusers. . 50
General. . 50
T-Bar Ceiling. . 50
Concealed Spline Ceiling. 50
Drywall/Plaster Ceiling. . 51

VAV-SVX08D-EN

Model Number Descriptions


Single-Duct Units
Digit 1, 2 Unit Type
VC =

VariTrane Single Duct

Digit 3Reheat
C =
E =
W =

Cooling Only
Electric Heat
Hot Water Heat

Digit 4Development Sequence


F

DD27=

Sixth

DD28=
DD29=
DD30=

Digit 5, 6Primary Air Valve


04
05
06
08
10
12
14
16
24

=
=
=
=
=
=
=
=
=

4" inlet (225 cfm)


5" inlet (350 cfm)
6" inlet (500 cfm)
8" inlet (900 cfm)
10" inlet (1400 cfm)
12" inlet (2000 cfm)
14" inlet (3000 cfm)
16" inlet (4000 cfm)
24" x 16" inlet (8000 cfm)

Digit 7, 8, 9Not Used


000 =

DD32=
DD33=
DD41=
DD42=

N/A

Digit 10, 11Design Sequence


** =

DD31=

Factory Assigned

Digit 12, 13, 14, 15Controls


DD00 Trane Actuator Only and
Enclosure
DD01= UCM4 Cooling Only Control
DD02= UCM4 N.C. On/Off Hot Water
DD03= UCM4 Prop. Hot Water
DD04= UCM4 Staged On/Off E-Heat
DD05= UCM4 Pulse Width MOD E-Heat
DD07= UCM4 N.O. On/Off Hot Water
DD11= VV550 DDC Controller - Cooling
Only
DD12= VV550 DDC Ctrl to operate N.C.
On/Off water valve
DD13= VV550 DDC Ctrl to operate Prop
water valve
DD14= VV550 DDC Ctrl - On/Off Electric
Heat
DD15= VV550 DDC Ctrl w/Pulse Width
Modulation
DD16= VV550 DDC Controller Ventilation Flow
DD17= VV550 DDC Ctrl to operate N.O.
On/Off Water Valve
DD19= VV550 Old trane vav boxes Controller with Flow
Tracking
DD20= VV550 DDC Vent Flow cntrl to
operate N.C. water valve
DD21= VV550 DDC - Vent Flow w/ On/Off
Elec Heat
DD22= VV550 DDC Vent Flow vava usb c hub 8-in-1 adapter bestbuy to
operate prop water valve
DD23= VV550 DDC- Basic plus- Local
(Electric heat- PWM) Remote
(Staged EH)
DD24= VV550 DDC-Basic plus- Local
(Water heat- Modulating)
Remote (Water- N.C. 2 position)
DD25= VV550 DDC-Basic plus- Local
(Water heat- Modulating)
Remote (Water- N.O. 2 position)
DD26= VV550 DDC-Basic plus- Local
VAV-SVX08D-EN

DD43=
DD44=
DD45=
DD46=
DD47=
DD49=
DD50=
DD51=
DD52=
DD53=
DD54=
DD55=
DD56=
DD57=
DD58=
DD59=
DD60=
DD61=

(Water heat- N.O. 2-position)


Remote (Water- Modulating)
VV550 DDC-Basic plus- Local
(Water heat- N.C. 2-position)
Remote (Water- Modulating)
VV550 DDC-Basic plus- Local
(Water heat- N.O. 2-position)
Remote (Water- N.O. 2-position)
VV550 DDC-Basic plus- Local
(Water heat- N.C. 2-position)
Remote (Water- NC 2-position)
VV550 DDC-Basic plus- Local
(Water heat- N.O. 2-position)
Remote (Water- N.C. 2-position)
VV550 DDC-Basic plus- Local
(Water old trane vav boxes N.C. 2-position)
Remote (Water- N.O. 2-position)
VV550 DDC-Basic plus- Local
(Electric heat- Staged) Remote
(Staged EH)
VV550 DDC Vent Flow cntrl to
operate N.O. On/Off water valve
UC400 DDC-Basic (No water or
electric heat)
UC400 DDC-Basic (Water heatN.C.- 2 position)
UC400 DDC-Basic (Water heatModulating)
UC400 DDC-Basic (Electric heatstaged)
UC400 DDC-Basic (Electric heatPWM)
UC400 DDC Ventilation flowcooling only
UC400 DDC-Basic (Water heatN.O.- 2 position)
UC400 DDC-FlowTracking
(Cooling only)
UC400 DDC-Ventilation Flow
(Water shmuel beis perek vav N. C.- 2 position)
UC400 DDC-Ventilation Flow
(Electric heat- staged)
UC400 DDC-Ventilation Flow
(Water heat- Modulating)
UC400 DDC-Basic plus- Local
(Electric heat- PWM) Remote
(Staged EH)
UC400 DDC-Basic plus- Local
(Water heat- Modulating)
Remote (Water- N.C. 2 position)
UC400 DDC-Basic plus- Local
(Water heat- Modulating)
Remote (Water- N.O. 2 position)
UC400 DDC-Basic plus- Local
(Water heat- N.O. 2-position)
Remote (Water- Modulating)
UC400 DDC-Basic plus- Local
(Water heat- N.C. 2-position)
Remote (Water- Modulating)
UC400 DDC-Basic plus- Local
(Water heat- N.O. 2-position)
Remote (Water- N.O. 2-position)
UC400 DDC-Basic plus- Local
(Water heat- N.C. 2-position)
Remote (Water- N.C. 2-position)
UC400 DDC-Basic plus- Local
(Water heat- N.O. 2-position)
Remote (Water- N.C. 2-position)
UC400 DDC-Basic plus- Local
(Water heat- N.C. 2-position)

Remote (Water- N.O. 2-position)


DD62= UC400 DDC-Basic plus- Local
(Electric heat- Staged) Remote
(Staged EH)
DD63= UC400 DDC-Ventilation Flow
(Water heat- N.O. 2-position)
DD65= UC400 Basic
(Electric HeatModulating SCR)
DD66= UC400 Basic plus-Local
(Electric heat-Modulating SCR)
Remote (Staged EH)
DD67= UC400 Ventilation Flow
(Electric heat-Modulating SCR)
DD71= UC210 DDC-Basic (No water or
electric heat)
DD72= UC210 DDC-Basic (Water heatN.C.- 2 position)
DD73= UC210 DDC-Basic (Water heatModulating)
DD74= UC210 DDC-Basic (Electric heatstaged)
DD75= UC210 DDC-Basic (Electric heatPWM)
DD76= UC210 DDC Ventilation flowcooling only
DD77= UC210 DDC-Basic (Water heatN.O.- 2 position)
DD79= UC210 DDC-FlowTracking
(Cooling only)
DD80= UC210 DDC-Ventilation Flow
(Water heat- N. C.- 2 position)
DD81= UC210 DDC-Ventilation Flow
(Electric heat- staged)
DD82= UC210 DDC-Ventilation Flow
(Water heat- Modulating)
DD83= UC210 DDC-Basic plus- Local
(Electric heat- PWM) Remote
(Staged EH)
DD84= UC210 DDC-Basic plus- Local
(Water heat- Modulating)
Remote (Water- Old trane vav boxes. 2 position)
DD85= UC210 DDC-Basic plus- Local
(Water heat- Modulating)
Remote (Water- N.O. 2 position)
DD86= UC210 DDC-Basic plus- Local
(Water heat- N.O. 2-position)
Remote (Water- Modulating)
DD87= UC210 DDC-Basic plus- Local
(Water heat- N.C. 2-position)
Remote (Water- Modulating)
DD88= UC210 DDC-Basic plus- Local
(Water heat- N.O. 2-position)
Remote (Water- N.O. 2-position)
DD89= UC210 DDC-Basic plus- Local
(Water heat- N.C. 2-position)
Remote (Water- N.C. 2-position)
DD90= UC210 DDC-Basic plus- Local
(Water heat- N.O. 2-position)
Remote (Water- N.C. 2-position)
DD91= UC210 DDC-Basic plus- Local
(Water heat- N.C. 2-position)
Remote (Water- N.O. 2-position)
DD92= UC210 DDC-Basic plus- Local
(Electric heat- Staged) Remote
(Staged EH)
DD93= UC210 Ventilation Flow
(Water heat- N.O. 2-position)
DD95= UC210 Basic
(Electric HeatModulating SCR)
DD96= UC210 Basic plus-Local
5

Model Number Descriptions


(Electric heat-Modulating SCR)
Remote (Staged EH)
DD97= UC210 Ventilation Flow
(Electric heat-Modulating SCR)
ENCL= Shaft Only in Enclosure
ENON= Shaft Out Side for Electric Units
FM00= Other Actuator and Control
FM01= Trane Supplied Actuator, Other
Ctrl
PC00= N.C. Actuator and Linkage Only
PC04= N.C. with DA Stat, old trane vav boxes Series
PC05= N.C. with RA STAT, 3000 Series
PCSS= Normally Closed Special
PN00= N.O. Actuator and Linkage Only
PN04= N.O. 3000 Series, DA STAT
PN05= N.O. 3000 Series, RA STAT
PN11= Auto Dual Min.
PN32= N.O. PNEU Constant Vol.
PN34= N.O. 3000 Series Constant
Vol.,RA STAT
PNON= Shaft Out Side for Pneumatic
Units
PNSS= Normally Open Special
N.C .= Old trane vav boxes. = Normally-opened
DA Stat = Direct-acting pneumatic t-stat
(by others)
RA Stat old trane vav boxes Reverse-acting pneumatic
t-stat (by others)
PN = Pneumatic
FM = Factory installation old trane vav boxes customersupplied controller
PVR = Pneumatic Volume Regulator

Digit 16Insulation
A
B
D
F
G

=
=
=
=
=

1/2" Matte-faced
1" Matte-faced
1" Foil-faced
1" Double-wall
3/8" Closed-cell

Digit 17 & 18Not Vwo certificaten halen vavo =

N/A

Digit 19Outlet Plenum


(Connection is Slip & Drive)
0 =
A =
B =
C =
D =
E =
F =
H =
J =
Note:

None
1 Outlet RH
1 Outlet END
1 Outlet LH
2 Outlets, 1 RH, 1 END
2 Outlets, 1 LH, 1 END
2 Outlets, 1 RH, 1 LH
3 Outlets, 1 LH, 1 RH, 1 END
4 Outlets, 1 LH, 1 RH, old trane vav boxes END
See unit drawings for outlet sizes/
damper information.

Digit 20Not Used


0

N/A

Digit 21Water Coil

Digit 27 - 29Electric Heat kW

0
1
2
3
4
A
B
C
D

000 =
010 =
015 =
460 =
Note:

=
=
=
=
=
=
=
=
=

None
1-Row
2-Row
3-Row
4-Row
1-Row Premium
2-Row Premium
3-Row Premium
4-Row Premium

Digit 22Electrical Connections


L

Left (Airflow hitting you in the


face)
R = Right (Airflow hitting you in the
face)
0 = Opposite side connection coil
and control
Note: VCCF,VCWF can be flipped in field
for opposite-hand connection

Digit 23Transformer
0
1
2
3
4
5
6
7
8

=
=
=
=
=
=
=
=
=

None
120/24 volt (50 VA)
208/24 volt (50 VA)
240/24 volt (50 VA)
277/24 volt (50 VA)
480/24 volt (50 VA)
347/24 Volt (50 VA)
380/24 Volt (50 VA)
575/24 Volt (50 VA)

Note: For VCEF old trane vav boxes with transformers


the VA depends on the staging,
control, and contactor type
(ranges are 50 VA to 75 VA, for 1
and 3 phase)

Digit 24Disconnect Switch


0 = None
W = With
Note: VCCF, VCWF Toggle Disconnect;
VCEF Door Interlocking Power
Disconnect

Digit 25Power Fuse


0 =
W =

None
With

Digit 26Electric Heat Voltage


0
A
B
C
D
E
F
G
H
J
K

=
=
=
=
=
=
=
=
=
=
=

None
208/60/1
208/60/3
240/60/1
277/60/1
480/60/1
480/60/3
347/60/1
575/60/3
380/50/3
120/60/1

None
1.0 kW
1.5 kW
46.0 kW
0.5 to 8.0 kW kW increments
8.0 to 18.0 kW old trane vav boxes kW increments
18.0 to 46.0 kW 2 kW increments

Digit 30Electric Heat Stages


0
1
2
3

=
=
=
=

None
1 Stage
2 Stages Equal
3 Stages Equal

Digit 31Electrical Heat


Contactors
0
1
2
3
4
5
6

=
=
=
=
=
=
=

None
24-volt magnetic
24-volt mercury
PE with magnetic
PE with mercury
SCR heat UC400
SCR heat FMTD/ENCL/DD00

Digit 32 & 33Not Used


00 =

N/A

Digit 34Actuator
0
A
B
C

=
=
=
=

Standard
Spring Return (Normally Open)
Spring Return (Normally Closed)
Belimo Actuator

Digit 35Sensor Options


0
1

=
=

Standard (Wired)
Factory Mounted Wireless
Receiver (Sensor Accessory)
Wireless Comm Interface
Modular FM

Digit 36Pre-Wired Factory


Solutions
0 =
W =

None
Factory Mounted DTS

Digit 37Bottom Access with


Cam Locks
0
1
2
3

=
=
=
=

None
Access Left SideTerminal Unit
Access Right SideTerminal Unit
Access Left SideTerminal Unit
with Water Connection on Right
Access Right SideTerminal Unit
with Water Coil Connection on
Left

VAV-SVX08D-EN

Model Number Descriptions

Dual-Duct Units
supplied controller
PVR = Pneumatic Volume Regulator

Digit 31Not Used

VDD = VariTrane dual-duct

Digit 1, 2, 3Unit Type


Digit 4Development Sequence

Digit 16Insulation

Digit 32Not Used

A
B
D
F
G

Sixth

Digit 5, 6Primary Air Valve


05
06
08
10
12
14
16

=
=
=
=
=
=
=

5" inlet (350 cfm)


6" inlet (500 cfm)
6" inlet (900 cfm)
10" inlet (1400 cfm)
12" inlet (2000 cfm)
14" inlet (3000 cfm)
16" inlet (4000 cfm)

Digit 7, 8Secondary Air Valve


05
06
08
10
12
14
16

=
=
=
=
=
=
=

5" inlet (350 cfm)


6" inlet (500 cfm)
8" inlet (900 cfm)
10" inlet (1400 cfm)
12" inlet (2000 cfm)
14" inlet (3000 cfm)
16" inlet (4000 cfm)

Digit 9Not Used


0

N/A

Digit 10, 11Design Sequence


** =

Factory Assigned

=
=
=
=
=

VAV-SVX08D-EN

=
=

N/A
N/A

Digit 33Special Options


0
X

=
=

None
Varies - Factory Assigned

Digit 17Not Used

Digit 34Actuator

N/A

Belimo Actuator

Digit 18Not Used

Digit 35Wireless Sensor

0
1

N/A

Digit 19Outlet Plenum


(Connection is slip & drive)
0 =
A =
B =
C =
D =
E =
F =
G =
H =
J =
Note:

Digit 12, 13, 14, 15Controls


DD00= Trane Actuator Only
DD01= UCM4 Cooling Only Control
DD08= UCM4 Dual Duct
Constant Volume
DD11= VV550 DDC Controller Cooling Only
DD18= VV550 DDC Controller w
Constant Volume
DD41= UC400 DDC-Basic (No water or
electric heat)
DD48= UC400 DDC-Basic (Constant
Volume)
DDSS= Vava usb c hub 8-in-1 adapter bestbuy Special
ENON= Shaft Out Side for Electric
Units
FM00= Other Actuator and Control
FM01= Trane Supplied Actuator, Other
Ctrl
PC03= NC Heating Valve, N.O. Cooling
Valve
PCSS= Normally Closed Vava usb c hub 8-in-1 adapter bestbuy N.O. Heat/Cool Actuators &
Linkage Only
PN09= N.O. Heating, N.O. Cooling,
w/PVRs
PN10= N.O. Heating, N.O. Cooling,
w/PVRs (CV DISCH)
PNON= Shaft Out Side for Pneumatic
Units
PNSS= Normally Open Special
Notes:
N.C. = Normally-closed
N.O. = Normally-opened
DA Stat = Direct-acting pneumatic t-stat
(by others)
RA Stat = Reverse-acting pneumatic tstat (by others)
PN = Pneumatic
FM = Factory installation of customer-

1/2" Matte-faced
1" Matte-faced
1" Foil-faced
1" Double-wall
3/8" Closed-cell

none
1 outletRH
1 outletEND
1 outletLH
2 outlets1 RH, 1 END
2 outlets1 LH, 1 END
2 outlets1 RH, 1 LH
2 outlets - END
3 outlets1 LH, 1 RH, 1 END
4 outlets1 LH, 1 RH, 2 END
See unit drawings for outlet sizes/
damper information.

=
=

Sensor/Receiver Standard
Wireless Sensor/Receiver
Mounted
Note: All sensors selected in
accessories

Digit 36Duct Temp Sensor


0 =
W =

None
With DuctTemp Sensor

Digit 20Not Used


0

N/A

Digit 21Not Used


0

N/A

Digit 22Not Used


0

N/A

Digit 23Transformer
0
1
2
3
4
5
6
7

=
=
=
=
=
=
=
=

None
120/24 volt (50 VA)
208/24 volt (50 VA)
240/24 volt (50 VA)
277/24 volt (50VA)
480/24 volt (50 VA)
347/24 volt (50 VA)
575/24 volt (50 VA)

Digit 24Disconnect Switch


0 =
W =

None
WithToggle

Digit 25Power Fuse


0 =
W =

None
With

Digit 26Not Used


0

N/A

Digit 27Not Used


0

N/A

Digit 28Not Used


0

N/A

Digit 29Not Used


0

N/A

Digit 30Not Used


0

N/A
7

Model Number Descriptions

Fan-Powered Units
Digit 1, 2Unit Type
VP =
VS =
LP =
LS =

VariTrane Fan-Powered Parallel


VariTrane Fan-Powered Series
VariTrane Fan-Powered
Low-Height Parallel
VariTrane Fan-Powered
Low-Height Series

Digit 3Reheat
C =
E =
W =

Cooling Only
Electric Heat
Hot Water Heat

Digit 4Development Sequence


F

Sixth

Digit 5, 6Primary Air Valve


05 =
06 =
08 =
10 =
12 =
14 =
16 old trane vav boxes =
Note:

5" inlet (350 max cfm)


6" inlet (500 max cfm)
8" inlet (900 max cfm)
10" inlet (1400 vav kpop tour cfm)
12" inlet (2000 max cfm)
14" inlet (3000 max cfm)
16" inlet (4000 max cfm)
8" x 14" inlet (1800 max CFM)
10, 12, 14, 16 Not Available on
Low-Height

Digit 7, 8Secondary Air Valve


00 =

N/A

Digit 9Fan
P
Q
R
S
T
U
V
W
X

=
=
=
=
=
=
=
=
=

02SQ fan (500 nominal cfm)


03SQ fan (1100 nominal cfm)
04SQ fan (1350 nominal cfm)
05SQ fan (1550 nominal cfm)
06SQ fan (1850 nominal cfm)
07SQ fan (2000 nominal cfm)
08SQ Fan (500 nominal cfm)
09SQ Fan (900 nominal cfm)
10SQ Fan (1800 nominal cfm)

Digit 10, 11Design Sequence


** =

Factory assigned

Digit 12, 13, 14, 15Controls


DD01=
DD02=
DD03=
DD04=
DD05=
DD07=
DD11=
DD12=
DD13=
DD14=
DD15=
DD17=
DD23=
DD28=

Cooling Only Control


N.C. On/Off Hot Water
Prop. Hot Water
Staged On/Off E-Heat
Pulse Width Mod of E-Heat
N.O. On/Off Hot Water
VV550 DDC Controller - Cooling
Only
VV550 DDC Ctrl w/N.C. On/Off
HW Valve
VV550 DDC Ctrl w/Prop. HW
Valve
VV550 Old trane vav boxes Ctrl - On/Off
Electric Heat
VV550 DDC Ctrl w/Pulse Width
Modulation
VV550 DDC Ctrl w/N.O. On/Off
HW Valve
VV550 DDC- Basic plus- Local
(Electric heat- PWM) Remote
(Staged EH)
VV550 DDC-Basic plus- Local
(Water heat- N.O. 2-position)
Remote (Water- N.O. 2-position)

DD29= VV550 DDC-Basic plus- Local


(Water heat- N.C. 2-position)
Remote (Water- N.C. 2-position)
DD30= VV550 DDC-Basic plus- Local
(Water heat- N.O. 2-position)
Remote (Water- N.C. 2-position)
DD31= VV550 DDC-Basic plus- Local
(Water heat- N.C. 2-position)
Remote (Water- N.O. 2-position)
DD32= VV550 DDC-Basic plus- Local
(Electric heat- Staged) Remote
(Staged EH)
DD41= UC400 DDC-Basic (No water or
electric heat)
DD42= UC400 DDC-Basic (Water heatNormally Closed- 2 position)
DD43= UC400 DDC-Basic (Water heatModulating)
DD44= UC400 DDC-Basic (Electric heatstaged)
DD45= UC400 DDC-Basic (Electric heatPWM)
DD47= UC400 DDC-Basic (Water heatNormally Opened- 2 position)
DD53= UC400 DDC-Basic plus- Local
(Electric heat- PWM) Remote
(Staged EH)
DD58= UC400 DDC-Basic plus- Local
(Water heat- N.O. 2-position)
Remote (Water- N.O. 2-position)
DD59= UC400 DDC-Basic plus- Local
(Water heat- N.C. 2-position)
Remote (Water- N.C. 2-position)
DD60= UC400 Old trane vav boxes plus- Local
(Water heat- N.O. 2-position)
Remote (Water- N.C. 2-position)
DD61= UC400 DDC-Basic plus- Local
(Water heat- N.C. 2-position)
Remote (Water- N.O. 2-position)
DD62= UC400 DDC-Basic plus- Local
(Electric heat- Staged) Remote
(Staged EH)
DD65= Basic (Electric Heat- Modulating
SCR)
DD66= Basic plus old trane vav boxes Local (Electric heat
Modulating SCR) Remote
(Staged EH)
DD71= UC210 DDC-Basic
(Cooling only)
DD72= UC210 DDC-Basic
(Water heat-nc 2pos)
DD73= UC210 DDC-Basic
(Water heat-Modulating)
DD74= UC210 DDC-Basic
(Electric heat-staged)
DD75= UC210 DDC-Basic
(Electric heat-pwm)
DD77= UC210 DDC-Basic
(Water heat-NO 2pos)
DD83= UC210 DDC-Basic+ Local
(Electric heat-pwm)
Remote (Staged)
DD84= UC210 DDC-Basic+ Local
(Water heat Modulating)
Remote (Water-NC 2pos)
DD85= UC210 DDC-Basic+ Local
(Water heat Modulating)
Remote (Water-NO 2pos)

DD86= UC210 DDC-Basic+ Local


(Water heat NO 2pos)
Remote (Water-Modulating)
DD87= UC210 DDC-Basic+ Local
(Water heat NC 2pos)
Remote (Water-Modulating)
DD88= UC210 DDC-Basic+ Local
(Water heat NO 2pos)
Remote (Water-NO 2pos)
DD89= UC210 DDC-Basic+ Local
(Water heat NC 2pos)
Remote (Water-NC 2pos)
DD90= UC210 DDC-Basic+ Local
(Water heat NO 2pos)
Remote (Water-NC 2pos)
DD91= UC210 DDC-Basic+ Local
(Water heat NC 2pos)
Remote (Water-NO 2pos)
DD92= UC210 DDC-Basic+ Local
(Electric heat-staged)
Remote (Staged)
DD95= UC210 DDC-Ctrl w/Modulating
SCR
DD96= UC210 DDC-SpaceTemp Ctrl w/
Local SCR & Remote Stge Elec
Heat
DD00= Trane Actuator Only
ENCL= Shaft Only in Enclosure
ENON= Shaft Out Side for Electric Units
FM00= Other Actuator and Control
FM01= Trane supplied actuator,
other control
PN00= N.O. Actuator and Linkage Only
PN05= N.O. 3000 Series, RA Stat
PN51= Pneumatic normally open
w/3011,DPS fan
PN52= Pneumatic normally open
w/3011, DPM fan
PNON= Shaft Out Side for Pneumatic
Units
Notes:
N.C. = Normally-closed
N.O. = Normally-opened
DA Stat = Direct-acting pneumatic t-stat
(by others)
RA Stat = Reverse-acting pneumatic
t-stat (by others)
PN = Pneumatic
FM = Factory installation of customersupplied controller
PVR = Pneumatic Volume Regulator

Digit 16Insulation
A
B
D
F
G

=
=
=
=
=

1/2 Matte-faced
1" Matte-faced
1" Foil-faced
1" Double-wall
3/8 Closed-cell

Digit 17Motor Type


D
E

=
=

PSC Motor
High-efficiency motor (ECM)

Digit 18Motor Voltage


1
2
3
4
5

=
=
=
=
=

115/60/1
277/60/1
347/60/1
208/60/1
230/50/1

Digit 19Outlet Connection


8

VAV-SVX08D-EN

Model Number Descriptions


1
2

=
=

Flanged
Slip & Drive

Digit 20Attenuator
0 =
W =

No Attenuator
With Attenuator

Digit 21Water Coil


0
1
2
3
4
5
6
A
B
C

=
=
=
=
=
=
=
=
=
=

None
1-RowPlenum inlet installed RH
2-RowPlenum inlet installed RH
1-RowDischarge installed, LH
1-RowDischarge installed, RH
2-RowDischarge installed, LH
2-RowDischarge installed, RH1
1-RowPremium water coil inlet
2-RowPremium water coil inlet
1-RowPremium hot coil
on discharge, LH
D = 1-RowPremium hot coil
on discharge, RH
E = 2-RowPremium hot coil
on discharge, LH
F = 2-RowPremium hot coil
on discharge, RH
Note: 1- and 2-row not available with
Low-Height

Digit 22Electrical Connections


L

Left (Airflow hitting you in the


face)
R = Right (Airflow hitting you in the
face)
W = Narrow Corridor LH, Hi-Volt Inlet
Facing
X = Narrow Corridor RH, Hi-Volt Inlet
Facing
Note: (W & X) Fan Powered Series Only

Digit 23Transformer
0

N/A (provided as standard)

Digit 24Disconnect Switch


0 = None
W = With
Electric Reheat w/ door interlocking
power disconnect, Cooling Only and
Water Old trane vav boxes w/ toggle disconnect

Digit 26Electric Heat Voltage


0 =
A =
B =
C =
D =
E =
F =
G =
H =
J =
K =
Note:

Digit 36Pre-Wired Factory


Solutions
0 =
W =

None
Factory Mounted DTS

Digit 27, 28, 29Electric Heat


kW
000 = None
050 = 0.5 kW
010 = 1.0 kW
015 = 1.5 kW
260 = 26.0 kW
Note: Electric Heat Voltage 0.5 to 8.0 kW kW increments
8.0 to 18.0 kW 1 kW increments
18.0 to 46.0 kW2 kW increments

Digit 30Electric Heat Stages


0 =
1 =
2 =
3 =
Note:

None
1 Stage
2 Stages Equal
3 Stages Equal
3 not available with Low Height

Digit 31Contactors
0 =
1 =
2 =
3 =
4 =
5 =
6 =
Note:

Digit 25Power Fuse


0 =
W =

None
208/60/1
208/60/3
240/60/1
277/60/1
480/60/1
480/60/3
347/60/1
575/60/3
380/50/3
120/60/1
K not available with Low Height

None
With

None
24-volt magnetic
24-volt mercury
PE with magnetic
PE with mercury
SCR heat UC400
SCR heat FMTD/ENCL/DD00
SCR cannot be selected with the
following configuration:
KW old trane vav boxes 10, 208 volt vava cake kokas phase, Low
Height

KW > 22, 480 volt 3 phase, Low


Height

Voltage = 575 volt

Digit 32Airflow Switch


0 =
W =

None
With

Digit 33Not Used


0

N/A

Digit 34Actuator
0
A

=
=

Standard
Belimo actuator

Digit 35Wireless Sensors


0
1

None
Factory Mounted Wireless
Receiver (Sensor Assembly)
2 = Wireless Comm Interface
Modular Old trane vav boxes All sensors selected in
accessories

VAV-SVX08D-EN

=
=

Unit Information
Single-Duct Units

Figure 3.

Typical single duct unit VCEF

The basic unit consists of a sheet metal casing with an air


valve, which is used to modulate the air being delivered
into the occupied zone.The unit is designed to modulate
either cooling or heating air between the temperatures of
40F and 140F. Air enters the air valve through the round
or rectangular inlet and exits into the sheet metal casing to
be distributed to the zone either through integral round
outlets in the casing or through rectangular duct attached
to the discharge of the unit.
The basic unit can also be ordered with factory-mounted
electric or hot water heating coils attached to the
discharge. See Figure 2, p. 10.
These re-heat units are used primarily to reheat air-to-zone
temperature enviro-tec vav box k factor the load in the occupied space is low.

Dual-Duct Units

Primary air is modulated through theVariTrane air valve by


rotating the damper blade. All air valves have a round/
rectangular inlet for easy fit-up with incoming duct work.

Dual-duct units provide two air valves: one as heating


primary air and the other as cooling primary air. Both
discharge into the common outlet, which old trane vav boxes to the zone
being controlled. See Figure 4, p. 10.

Typical Single-Duct Units


Figure 1.

Typical single old trane vav boxes unit VCCF

Units are provided with a slip and drive rectangular duct


connection or can be ordered with integral outlet plenum.
Sequencing of hot and cold air valve is dependent on job
requirements. One typical control is valves working in
conjunction to respond to zone temperature.
When the cooling valve becomes fully closed or reaches a
specified minimum, the heating valve will begin to
modulate or vice versa.The old trane vav boxes result is that air flowing
to the zone varies from maximum down to a minimum and
back up to maximum as load varies and controls would
cause one air valve to close and the other to open.

Figure 2.

Typical single duct unit VCWF

Another typical application is when the unit provides a


constant volume to the zone. When the zone sensor is tied
directly to the heating valve, it will modulate the heating
valve according to the zone temperature.
When the heating valve is fully closed or there is a call for
cooling in the zone, the cooling valve will be at constant
supply. As the space becomes too cool, the heating valve
will modulate open, decreasing the cooling valve flow.The
typical result is that the air flowing into the zone stays at a
constant flow whether the unit is heating or cooling.
Figure 4.

10

Typical dual-duct unit: VDDF

VAV-SVX08D-EN

Unit Information

Fan-Powered and Fan-Powered LowHeight Units

Figure 8.

Low height parallel: LPWF (top) & low height


parallel: LPEF (bottom)

VariTrane fan-powered and low-height fan-powered units


can be either parallel or series, with or without re-heat.
(SeeFigure 5, p. 11 thru Figure 8, p. 11.)

Typical Fan-Powered Units


Figure 5.

Parallel fan-powered terminal unit (top) &


series fan-powered terminal units (bottom)

The fan on a series unit runs continuously whenever the


main air handler unit is in operation.There are various
options for starting the fan.The fan can be started three
ways: 1) remotely, 2) by a duct pressure switch, or 3) by a
combination of both.The particular fan control method
may vary from unit to unit, depending upon job needs.

Figure 6.

Low height series: LSCF (top) & low height


series: LSWF (bottom)

Typically, heater is off while air valve modulates primary


air and responds to zone temperature. If zone temperature
decreases to the point where a decrease in primary air will
not maintain the desired temperature, the re-heat will be
activated to increase the temperature of the discharge air.
On a parallel unit, the VariTrane air valve delivers primary
cooling air to the unit outlet. When the space temperature
decreases beyond air valve control, the fan is turned on as
the first stage of heat.The fan delivers plenum air from
above the occupied space to the unit outlet, which is mixed
with primary air and delivered to the occupied space.
Note: Either the fan, the air valve, or both can deliver
airflow into the occupied space. In order to prevent
primary airflow from exiting through the fan when
the fan is not running on a parallel unit, a back draft
damper is provided. When the fan is not running,
the efficiency of this system is the same as a
standard single-duct VAV unit.

Figure 7.

Low height series: LSEF (top) & low height


parallel: LPCF (bottom)

Typically, the control systems applied to parallel units


cause the air valve to close to zero or a minimum flow
before the fan is activated. After the fan is activated, the
optional heat will be activated upon further reduction in
zone temperature.Therefore, minimal primary air is mixed
with the heated old trane vav boxes fan-powered unit fan sizes 02SQ05SQ and
08SQ10SQ were performance tested at .12 in. w.g. and
sizes 06SQ and 07SQ were tested at .15 in. w.g. Units are
not designed to operate unducted and below these tested
static pressures.
Note: Fan-powered units are available with rectangular
discharge connection only.The optional heater is
mounted on the discharge of the unit. Hot water
coils are connected to either the plenum inlet or on
the discharge on parallel units, and to the discharge
of series units.

VAV-SVX08D-EN

11

Unit Installation
WARNING
Proper Structural Support Required!

Figure 10.

Dual-duct hanger bracket locations


C

Ceiling structure must be strong enough to support the


weight of the unit. If unsure, check with a structural
engineer. Refer toTable 1, p. 22 thruTable 6, p. 24 for unit
weights. Failure to ensure proper structural ceiling
support could result in unit failing from its location
which could result in death or serious injury.

AIR
VALVE

AIR
VALVE

COOLING

HEATING

Due to their weight, the VAV terminal units should be


suspended from the uppermost ceiling, independent of
the false ceiling grid. Suspension devices are to be
supplied by the installer. Units must be installed level and
upright. Failure to level the unit properly may prevent
proper operation of the controls and/or terminal unit.
Units are not designed to be installed vertically.
Consequently, this will also void the Old trane vav boxes ratings and any
warranty on the unit.

Single-Duct
Figure 9.

Single-duct hanging recommendations


.

TOP VIEW

5" thru 10"

23.154" (588 mm)

25.25" (641 mm)

1.376" (35 mm)

12" thru 16"

25.154" (639 mm)

37.25" (946 mm)

1.376" (35 mm)

Inlet Size

Fan-Powered (Standard and Low-Height)


Fan-powered units should be supported by either hanger
straps or by using a threaded old trane vav boxes in conjunction with the
hanger old trane vav boxes that are provided on the unit. Care should
be exercised to insure that the hanging straps do not block
the side access panel. See Figure 11, p. 15 thru Figure 18,
p. 21.

Duct Connections
All VariTrane units should be provided with a minimum of
1.5-duct diameters of straight duct prior to the inlet of the
unit. It is recommended that at least 48 inches of straight
duct be provided from the discharge of the units prior to
any take-offs or transitions.
Depending upon the size and weight of the single-duct
unit, it may be capable of being supported by the ductwork
that is connected to it. No hanger brackets are provided on
these units since the unit should be supported by means
of enviro-tec vav box k factor hanger strap.The hanger strap should be secured
directly to the unit casing as shown in Figure 9, p. 12.
For cooling only single-duct units or single-duct units with
hot water coil, the unit may be rotated 180 for opposite
side connections.
For units with electric heat, the unit must be ordered from
the factory designating either right- or left-hand
connections

Dual-Duct
Dual-duct units should be supported by either hanger
straps or by using old trane vav boxes threaded rod in conjunction with the
hanger brackets that are provided on the unit. See
Figure 10, p. 12.

12

Important: This is a requirement for electric heat fanpowered units used in old trane vav boxes with
100% downward discharge.
Note: In order to maintain the UL rating for VariTrane
electric coils, there must be four feet of straight
unlined ductwork downstream of the reheat coil
prior to any diffuser takeoffs.
1. After all connections are made, check that the entire
ductwork system is airtight. In some high-pressure
systems, duct sealer may be necessary.
2. Provide insulation around the entire inlet collar (all the
way to the unit casing).
Note: Use caution not to damage the flow tubes when
making ductwork connections or insulating.
3. Cut slits in the insulation for the flow tubes and
secure with duct tape.

VAV-SVX08D-EN

Unit Installation
4. If the unit is to be installed in a location with high
humidity, external insulation around the heating coil
should be installed as required.

Fan-powered VAV units have a plenum inlet enviro-tec vav box k factor must


be clear of obstructions. Allow at least 36 of clearance
in front of the side access and plenum opening.

Water Coil Connections

Low-height fan-powered terminals require the same


plenum clearance requirement that applies to the
standard fan-powered units. However the access to the
internal components is located on the bottom of the
unit.

Note: The following coils have 3/8 OD water coil piping


connections.
Single Vava night light blue light 1-row coils (inlet sizes 05, 05, 06, 08
or 10 only)
Low Height Parallel Inlet 1-row
Low Height Parallel Discharge 1-row
All others require a 7/8 OD yod hey vav hey shield pendant coil piping connections.
Note:
1. If necessary, you can change the coil connection from
left-handed to right-handed (and vice-versa) by
disconnecting the coil from the unit and rotating the
coil vava headquarters a steering wheel 180.
Note: Exception - Coil connection cannot be changed
on parallel fan powered unit with hot water coil
on plenum inlet.
2. On single row coils, the water inlet should always be on
the bottom and the outlet on the top. On multi-row
coils, always plumb in the counter flow orientation:
Left-hand units water inlet on the bottom and
outlet on the top.
Right-hand units water inlet on the top and
outlet on the bottom.
3. Care should be taken to properly support the water coil
piping connections while connecting the adjoining
pipe.

It is also recommended that 6 of clearance be provided to


the top and bottom of old trane vav boxes the units.
Note: The minimum clearance for controls and heater
controls should be 36 for all models except units
with 575-volt electric heaters, which require 48 of
clearance. NEC and/or local codes override all
clearance requirements.

Actuator Mounting
Important: When installing or replacing the actuator
tighten the actuator set old trane vav boxes per the
manufacturers instructions. Failure to
follow the manufacturers specifications
may result in unit malfunction.
Trane offers a factory-mounted actuator with a 90-second
drive time.The enviro-tec vav box k factor drives 1 degree per second. A
field-installed actuator may be used if desired.The
actuator shaft has a -inch diameter and is designed to
travel clockwise to close the damper and counterclockwise to open the damper.There is an indicator on the
end of the actuator shaft that can be used to determine the
position of the damper.

Stand Alone UCM 4.2

Single-duct and dual-duct units provided with hot


water reheat have an access panel located vav diffuser cost the side
of the water coil. All other single-duct and dual-duct
units are provided without access, as all functioning
components are external to the unit.

Fan-powered terminals are provided with a sliding side


access.

When there is no communication to the UCM control and


the unit is in the stand alone mode the control action is
determined by the auxiliary temperature sensor located
onTB3-5 andTB3-6 terminals on the UCM board. In order
for the auxiliary sensor old trane vav boxes determine the control action
(heat, cool) it must be located in the supply duct.The
auxiliary temperature is then compared to the zone
temperature. If the supply air temperature is 10 degrees
above the zone temperature, then the old trane vav boxes action will be
heat. Old trane vav boxes the supply air temperature is less than or equal to
the zone temperature, then the control action will be cool.
If the supply air temperature is between the zone
temperature and the zone temperature + 10F (5.5C)(zone
temperature < supply air temperature < zone temperature
+ 10F) (5.5C), the control action remains the same and the
UCM controls to the minimum flow set point. If an
auxiliary sensor is not installed the UCM will retain the last
control action in effect.

Low-height terminal units have a removable bottom


panel.

Stand Alone VV550 LonTalk Control

4. It is recommended that piping to the parole a vava inouva coil should


be done after field-mounted controls, external
insulation, and ductwork connections have been
completed.
Important:

Do not connect water valve or pipe


extensions to the water coil connections
unless supported.

Unit Accessibility

Clearances
For proper service, it is recommended that at least 36 of
side clearance be provided to service and access singleduct and dual-duct terminals units.
VAV-SVX08D-EN

When there is no enviro-tec vav box k factor to theVV550 control and


the unit is in the stand alone mode the control action is
determined by the auxiliary temperature sensor located
onTB3-5 andTB3-6 terminals on the VV550 board.The
control must also be configured through the InputsTab
of Analog Input 4 as Primary Supply Air Sensor. In order
13

Unit Installation
for the auxiliary sensor to determine the control action
(heat, cool) it must be located in the supply inlet of the
duct.The auxiliary temperature is then compared to the
zone temperature. If the supply air temperature is 10
degrees above the zone temperature, then the control
action will be heat. If the supply air temperature is less
than or equal to the zone temperature, then the control
action will be cool. If the supply air temperature is between
the zone temperature and the zone temperature + 10F
(5.5C)(zone temperature < supply air temperature < zone
temperature + 10F) (5.5C), the control action remains the
same and the UCM controls to the minimum flow set
point. If an auxiliary sensor is not installed the UCM will
retain the last control action in effect.

Stand Alone UC400


When old trane vav boxes is no communication to the UC400 control and
the unit is in the stand alone mode the control action is
determined by the auxiliary temperature sensor located
on AI5 terminals on the UC400 control.This input may
have to be changed from AI4 (Discharge Air Input) as wired
from the factory. In order for the auxiliary sensor to
determine the control action (heat, cool) it must be located
in the supply inlet of the duct.The auxiliary temperature is
then compared to the zone temperature. If the supply air
temperature is 10 degrees above the zone temperature,
then the control action will be heat. If the supply air
temperature is less than or equal to the zone temperature,
then the control action will be cool. If the supply air
temperature is between the zone temperature and the
zone temperature + 10F (5.5C)(zone temperature <
supply air temperature < zone temperature + 10F) (5.5C),
the control action remains the same and the UCM controls
to the minimum flow set point. If an old trane vav boxes sensor is old trane vav boxes the UCM will retain the last control action in
effect.

14

VAV-SVX08D-EN

Unit Installation

Figure 11.

Parallel hanger bracket locations sizes


C
Water
Coil
Airflow
Plenum Inlet

TOP VIEW
Parallel Cooling & Hot Water

B
Flow Ring
Tubing

Primary
Airflow
F

Optional Attenuator
Field Installed
E

Air
Valve

Airflow
Discharge Outlet
A
B
D
E
C
F
FAN SIZE
26.75" old trane vav boxes mm) 26.75" (679 mm) 41.154" (1041 mm) 3.25" (83 mm) 20.00" (508 mm) 38.95" (989 mm)
02SQ
03SQ, 04SQ, 05SQ 29.75" (756 mm) 26.75" (679 mm) 41.154" (1041 mm) 3.25" (83 mm) 20.00" (508 mm) 38.95" (989 mm)
36.75" (933 mm) 26.75" (679 mm) 41.154" (1041 mm) 3.25" (83 mm) 20.00" (508 mm) 38.95" (989 mm)
06SQ, 07SQ
C

Airflow
Plenum Inlet

Flow Ring
Tubing

Optional Attenuator
Field Installed

Primary
Airflow
F

Air
Valve

TOP VIEW
Parallel Electric Heat

Terminal Box

Heater
Airflow
Discharge Outlet
43.546
(1106 mm)

VAV-SVX08D-EN

15

Unit Old trane vav boxes 12. Series hanger bracket locations
A

Flow Ring
Tubing

B
C

Air
Valve

Optional Attenuator
Field Installed
Airflow
Plenum Inlet

TOP VIEW
Series Cooling & Hot Water

D
2.

1.

Fan Inlet w/o


Attenuator

1.

All attenuators are the same length and width.

2.

Sizes 01 and 02 units are smaller than attenuators.

Water
Coil
1.625"
(41 mm)

FAN SIZE

F
(Elec. Heat Only)

J
(Elec. Heat Only)

G
(Elec. Heat Only)

02SQ

18.75" (476 mm)

26.75" (679 mm)

3.25" (83 mm)

41.154" (1041 mm)

35.154 (740 mm)

20.132" (511 mm) 53.750" (1365 mm)

19.00" (483 mm)

03SQ, 04SQ

20.75" (527 mm)

26.75" (679 mm)

3.25" (83 mm)

41.154" (1041 mm)

41.154" (1041 mm)

23.875 vava usb c hub 8-in-1 adapter bestbuy mm)

59.750 (1517 mm)

19.00" (483 mm)

27.25" (692 mm)

26.75" (679 mm)

3.25" (83 mm)

41.154" (1041 mm)

41.154" (1041 mm)

29.875" (759 mm) 59.750" (1517 mm)

19.00" (483 mm)

27.25" (692 mm)

26.75" (679 mm)

3.25" (83 mm)

41.154" (1041 mm)

41.154" (1041 mm)

29.875" (759 mm) 58.250" (1479 mm)

17.50" (445 mm)

05SQ
06SQ, 07SQ

Flow Ring
Tubing

B
C

Air
Valve

Optional Attenuator
Field Installed
Airflow
Plenum Inlet

TOP VIEW
Series Electric Heat

G Fan Inlet old trane vav boxes Installation

Figure 13. Low-height parallel 08SQ/09SQ w/hot water or electric heat


31.65"
(804 mm)

13.00"
(330 mm)

Airflow
Plenum Inlet

23.90"
(607 mm)

Primary
Airflow

19.86"
(504 mm)

Optional Attenuator
Field Installed

24.30"
(617 mm)

3.35"
(85 mm)

Airflow
Discharge Outlet

23.10"
(587 mm)

13.80"
(350 mm)

TOP VIEW

4.00"
(102 mm)

31.65"
(804 old trane vav boxes mm)

23.90"
(607 mm)

Airflow
Plenum Inlet

Primary
Airflow

19.86"
(504 mm)

Optional Attenuator
Field Installed

Terminal Box

24.30"
(617 mm)

Heater

3.35"
(85 mm)

TOP VIEW

Airflow
Discharge Outlet

3.00"
(76 mm)

VAV-SVX08D-EN

23.10"
(587 mm)

13.80"
(350 mm)

4.00"
(102 mm)

17

Unit Installation

Figure 14. Low-height parallel 10SQ

1.625"
(41 mm)

Flow Ring
Tubing

38.95"
(989 mm)

Primary
Airflow
Plenum
Inlet

Air
Valve

5.625"
(143 mm)

38.75"
(984 mm)

Terminal Box

Optional Heater

5.625"
(143 mm)

Airflow
Discharge Outlet
41.137"
(1045 mm)

TOP VIEW

18

VAV-SVX08D-EN

Unit Installation

Figure 15. Low-height series 08SQ/09SQ w/hot water or electric heat

31.65"
(804 mm)

4.00"
(102 mm)

10.13"
(257 mm)

12.85"
(326 mm)

Airflow
Plenum Inlet

Primary
Airflow
19.86"
(504 mm)

Optional Attenuator
Field Installed
Air
Valve

3.35"
(85 mm)

34.30"
(871 mm)

31.65"
(804 mm)

3.35"
(85 mm)
Water
Coil

TOP VIEW

4.00"
(102 mm)

10.13"
(257 mm)

12.85"
(326 mm)

Airflow
Plenum Inlet

Primary
Airflow
Optional Attenuator
Field Installed
Air
Valve

Airflow

19.86"
(504 mm)

3.35"
(85 mm)

20.00"
(508 mm)
27.00"
(686 mm)

34.30"
(871 mm)

3.35"
(85 mm)
Optional
Electric Heater

TOP VIEW

Airflow
20.00"
(508 mm)
27.00"
(686 mm)

VAV-SVX08D-EN

19

Unit Installation

Figure 16. Low-height series 10SQ w/hot water or electric heat


19.45"
(494 mm)
31.65"
(804 mm)

19.45"
(494 mm)

10.12"
(257 mm)

31.65"
(804 mm)
Optional Attenuator
Field Installed

Optional Attenuator
Field Installed
Primary
Airflow

19.86"
(504 mm)

Airflow
Plenum Inlet

Airflow
Plenum Inlet

3.35"
(85 mm)

19.86"
(504 mm)

30.30"
(770 mm)

3.35"
(85 mm)
TOP VIEW

Airflow
Discharge Outlet

3.50"
(89 mm)

42.00"
(1067 mm)

3.50"
(89 mm)

19.45"
(494 mm)
31.65"
(804 mm)

10.12"
(257 mm)

19.45"
(494 mm)
31.65"
(804 mm)
Optional Attenuator
Field Installed

Optional Attenuator
Field Installed
Primary
Airflow

19.86"
(504 mm)

Airflow
Plenum Inlet

Airflow
Plenum Inlet

3.35"
(85 mm)

19.86"
(504 mm)

Terminal Box

30.30"
(770 mm)

Plenum Area

3.35"
(85 mm)
TOP VIEW

Optional
Heater

1.92"
(49 mm)
3.50"
(89 mm)

20

Airflow
Discharge Outlet

42.00"
(1067 mm)

3.50"
(89 mm)

VAV-SVX08D-EN

Unit Installation

Figure 17.

Attenuator installation - parallel units

1. Attach attenuator as shown with provided mounting brackets.


Mounting Bracket

Optional Attenuator
Field Installed

Note: Bottom bracket not shown. Bottom bracket to be installed in same orientation on bottom of unit.

Figure 18. Attenuator installation old trane vav boxes series units

1. Attach attenuator as shown with provided mounting brackets.


Mounting Bracket

Optional Attenuator
Field Installed

Note: Bottom bracket not shown. Bottom bracket to be installed in same orientation on bottom of unit.

VAV-SVX08D-EN

21

Unit Installation

Figure 19. Attenuator installation - low-height parallel units


1. Attach attenuator to unit as shown with provided mounting brackets.

MOUNTING BRACKET

OPTIONAL ATTENUATOR
FIELD INSTALLED

Notes: Bottom bracket not shown. Bottom bracket to be installed in same orientation on bottom of unit.

Figure 20. Attenuator installation - low-height series units


1. Attach attenuator to unit as shown with provided mounting brackets.

MOUNTING BRACKET

MOUNTING BRACKET

OPTIONAL ATTENUATOR
FIELD INSTALLED

OPTIONAL ATTENUATOR
FIELD INSTALLED

OPTIONAL ATTENUATOR
FIELD INSTALLED
MOUNTING BRACKET

Note: Bottom bracket not shown. Bottom bracket to be installed in same orientation on curio vavo of unit.

Table 1.

Single-duct units

VCEF w/
VCWF
VCWF
VCWF
VCWF
VCCF w/
Dual
VCWF
VCWF
VCWF
VCWF 1-Row w/ 2-Row w/ 3-Row w/ 4-Row w/
Unit VCCF Dual Wall VCEF
Wall
1-Row
2-Row
3-Row
4-Row Dual Wall Dual Wall Dual Wall Dual Wall
Size (lbs/kg) (lbs/kg) (lbs/kg) (lbs/kg) (lbs/kg) (lbs/kg) (lbs/kg) (lbs/kg) (lbs/kg) (lbs/kg) (lbs/kg) (lbs/kg)
4
5
6
8

16/7
16/7
16/7
16/7

19/9
19/9
19/9
20/9

38/17
38/17
38/17
38/17

48/22
48/22
48/22
49/22

21/10
21/10
21/10
21/10

22/10
22/10
22/10
24/11

23/11
23/11
22/10
24/11

24/11
24/11
24/11
26/12

24/11
24/11
24/11
25/11

25/11
25/11
25/11
28/13

26/12
26/12
25/11
28/13

27/12
27/12
27/12
30/14

10
12
14
16
24

22/10
27/12
32/15
35/16
52/24

27/12
34/15
41/19
46/21
63/29

46/21
52/24
60/27
69/31
84/38

60/27
68/31
80/36
91/41
106/48

29/13
37/17
44/20
49/22
70/32

32/15
40/18
48/22
54/24
77/35

32/15
41/19
51/23
56/25
76/35

36/16
45/20
55/25
61/28
82/37

34/15
43/20
53/24
60/27
81/37

37/17
47/21
57/26
65/29
88/40

37/17
48/22
60/27
67/30
87/40

41/19
52/24
64/29
72/33
93/42

22

VAV-SVX08D-EN

Unit Installation

Table 2.

Table 3.
Unit
Size

Dual-duct units
Unit Size

VDDF (lbs/kg)

VDDF w/Dual Wall (lbs/kg)

0505
0506
0606
0508

54/24
54/24
54/24
55/25

68/31
68/31
68/31
68/31

0608
0510
0808
0610

55/25
56/25
56/25
56/25

69/31
69/31
70/32
70/32

0810
1010
0612
0812

57/26
61/28
57/26
58/26

70/32
74/34
70/32
71/32

1012
1212
0814
1014

59/27
60/27
78/35
79/36

72/33
84/38
102/46
103/47

1214
1414
0816
1016

80/36
81/37
79/36
80/36

104/47
105/48
103/47
104/47

1216
1416
1616

81/37
82/37
83/38

105/48
105/48
106/48

Parallel fan-powered units


VPWF 1-Row VPWF 2-Row
VPxF
VPCF
VPCF w/Dual
VPEF VPEF w/Dual VPWF 1-Row VPWF 2-Row w/Dual Wall w/Dual Wall Attenuator
(lbs/kg) Wall (lbs/kg) (lbs/kg) Wall (lbs/kg) (lbs/kg)
(lbs/kg)
(lbs/kg)
(lbs/kg)
(lbs/kg)

0502SQ
0602SQ
0603SQ
0802SQ

81/37
80/36
83/38
81/37

115/52
114/52
117/53
115/52

110/550
109/49
112/51
110/50

144/65
143/65
146/66
144/65

92/42
91/41
105/48
92/42

95/43
94/43
108/49
95/43

126/57
125/57
139/63
126/57

129/59
128/58
142/64
129/59

46/21
46/21
48/22
46/21

0803SQ
0804SQ
1002SQ
1003SQ

83/38
84/38
82/37
84/38

117/53
118/54
116/53
118/54

112/51
113/51
111/50
113/51

146/66
147/67
145/66
147/67

105/48
106/48
93/42
106/48

108/49
109/49
96/44
109/49

139/63
140/64
127/58
140/64

142/64
143/65
130/59
143/65

48/22
48/22
46/21
48/22

1004SQ
1005SQ
1006SQ
1007SQ

85/39
98/44
114/52
122/55

119/54
132/60
148/67
156/71

114/52
128/58
144/65
152/69

148/67
162/73
178/81
186/84

107/49
120/54
127/58
135/61

110/50
123/56
130/59
138/63

141/64
154/70
161/73
169/77

144/65
157/71
164/74
172/78

48/22
48/22
54/24
54/24

1203SQ
1204SQ
1205SQ
1206SQ

85/39
86/39
99/45
115/52

119/54
120/54
133/60
149/68

114/52
115/52
129/59
145/66

148/67
149/68
163/74
179/81

107/49
108/49
121/55
128/58

110/50
111/50
124/56
131/59

141/64
142/64
155/70
162/73

144/65
145/66
158/72
165/75

48/22
48/22
48/22
54/24

1207SQ
1404SQ
1405SQ
1406SQ

123/56
87/39
100/45
116/53

157/71
121/55
134/61
150/68

153/69
116/53
130/59
146/66

187/85
150/68
164/74
180/82

136/62
109/49
122/55
129/59

139/63
112/51
125/57
132/60

170/77
143/65
156/71
163/74

173/78
146/66
159/72
166/75

54/24
48/22
48/22
54/24

1407SQ
1606SQ
1607SQ

124/56
117/53
125/57

158/72
151/68
159/72

154/70
147/67
155/70

188/85
181/82
189/86

137/62
130/59
138/63

140/64
133/60
141/64

171/78
164/74
172/78

174/79
167/76
175/79

54/24
54/24
54/24

VAV-SVX08D-EN

23

Unit Installation

Table 4.

Series fan-powered

VSCF
Unit Size (lbs/kg)

VSCF w/
Dual Wall
(lbs/kg)

VSEF
(lbs/kg)

VSEF w/
Dual Wall
(lbs/kg)

VSWF
1-Row
(lbs/kg)

VSWF
2-Row
(lbs/kg)

VSWF
1-Row
w/Dual Wall
(lbs/kg)

VSWF
2-Row
w/Dual Wall
(lbs/kg)

VSxF
Attenuator
(lbs/kg)

0402SQ
0502SQ
0602SQ
0603SQ
0604SQ

78/35
78/35
77/35
76/34
87/39

93/42
93/42
92/42
100/45
111/50

104/47
104/47
103/47
105/48
116/53

119/54
119/54
118/54
129/59
140/64

85/39
85/39
84/38
88/40
99/45

87/39
87/39
86/39
92/42
103/47

100/45
100/45
99/45
112/51
123/56

102/46
102/46
101/46
116/53
127/58

46/21
46/21
46/21
48/22
48/22

0802SQ
0803SQ
0804SQ
1002SQ
1003SQ

79/36
77/35
88/40
81/37
80/36

94/43
101/46
112/51
96/44
104/47

105/48
106/48
117/53
107/49
109/49

120/54
130/59
141/64
122/55
133/60

86/39
89/40
100/45
88/40
92/42

88/40
93/42
104/47
90/41
96/44

101/46
113/51
124/56
103/47
116/53

103/47
117/53
128/58
105/48
120/54

46/21
48/22
48/22
46/21
48/22

1004SQ
1005SQ
1006SQ
1007SQ
1203SQ

91/41
92/42
104/47
117/53
82/37

115/52
116/53
133/60
146/66
106/48

120/54
121/55
135/61
148/67
111/50

144/65
145/66
164/74
177/80
135/61

103/47
104/47
119/54
132/60
94/43

107/49
108/49
124/56
137/62
98/44

127/58
128/58
148/67
161/73
118/54

131/59
132/60
153/69
166/75
122/55

48/22
48/22
54/24
54/24
48/22

1204SQ
1205SQ
1206SQ
1207SQ
1404SQ

92/42
94/43
105/48
118/54
93/42

116/53
118/54
134/61
147/67
117/53

121/55
123/56
136/62
149/68
122/55

145/66
147/67
165/75
178/81
146/66

104/47
106/48
120/54
133/60
105/48

108/49
110/50
125/57
138/63
109/49

128/58
130/59
149/68
162/73
129/59

132/60
134/61
154/70
167/76
133/60

48/22
48/22
54/24
54/24
48/22

1405SQ
1406SQ
1407SQ
1606SQ
1607SQ

96/44
106/48
119/54
107/49
120/54

120/54
135/61
148/67
136/62
149/68

125/57
137/62
150/68
138/63
151/68

149/68
166/75
179/81
167/76
180/82

108/49
121/55
134/61
122/55
135/61

112/51
126/57
139/63
127/58
140/64

132/60
150/68
163/74
151/68
164/74

136/62
155/70
168/76
156/71
169/77

48/22
54/24
54/24
54/24
54/24

LPEF
(lbs/kg)

LPEF w/
Dual Wall
(lbs/kg)

LPWF
1-Row
(lbs/kg)

LPWF
2-Row
(lbs/kg)

LPWF 1-Row
w/Dual Wall
(lbs/kg)

Table 5.

Low-height parallel units

Unit Size

LPCF w/
LPCF
Dual Wall
(lbs/kg) (lbs/kg)

LPWF 2-Row
LPxF
w/DualWall Attenuator
(lbs/kg)
(lbs/kg)

0508SQ
0608SQ
0609SQ
0808SQ

69/31
68/31
73/33
69/31

89/40
88/40
93/42
89/40

84/38
83/38
88/40
84/38

104/47
103/47
108/49
104/47

78/35
77/35
82/37
78/35

81/37
80/36
85/39
81/37

98/44
97/44
102/46
98/44

101/46
100/45
105/48
101/46

10/5
10/5
10/5
10/5

0809SQ
0810SQ
14RT09SQ
14RT10SQ

74/34
90/41
83/38
97/44

94/43
110/50
103/47
117/53

89/40
105/48
98/44
112/51

109/49
125/57
118/54
132/60

83/38
99/45
92/42
106/48

86/39
102/46
95/43
109/49

103/47
119/54
112/51
126/57

106/48
122/55
115/52
129/59

10/5
10/5
10/5
10/5

Table 6.

Low-height series units

Unit Size

LSCF
(lbs/kg)

LSCF w/
Dual Wall
(lbs/kg)

0508SQ
0608SQ
0609SQ
0808SQ

71/32
70/32
80/36
71/32

86/39
85/39
95/43
86/39

86/39
85/39
95/43
86/39

101/45
100/45
110/50
101/46

80/36
79/36
89/40
80/36

0809SQ
0810SQ
14RT09SQ
14RT10SQ

81/37
95/43
90/41
105/48

96/44
120/54
105/48
130/59

96/44
120/54
105/48
130/59

111/50
145/66
120/54
155/70

90/41
111/50
99/45
121/55

24

LSEF w/
LSWF
LSWF
LSEF
Dual Wall 1-Row
2-Row
(lbs/kg) (lbs/kg) (lbs/kg) (lbs/kg)

LSWF 1-Row
w/Dual Wall
(lbs/kg)

LSWF 2-Row
w/Dual Wall
(lbs/kg)

LSxF
Attenuator
(lbs/kg)

82/37
81/37
91/41
82/37

95/43
94/43
104/47
95/43

97/44
96/44
106/48
97/44

10/5
10/5
10/5
10/5

92/42
115/52
101/46
125/57

105/48
136/62
114/52
146/66

107/49
140/64
116/53
150/68

10/5
20/9
10/5
20/9

VAV-SVX08D-EN

Unit Setup
Figure 21. Flow sensor P vs. airflow delivery

Flow Sensor Differential Pressure (inches water)

10

6
4

8"

10"

8" x 12"
12" 14"

16"

16" x 24"

0.1

0.01
10

100

1,000

10,000

Airflow (CFM)

Fan Motor Amperage


Table 7.

Maximum ECM fan motor amperage (FLA)


Fan Size

HP VAC

115 VAC

277 VAV

Parallel/Series 03SQ

1/3

4.5

2.4

Parallel/Series 04SQ

1/2

6.5

3.5

Parallel/Series 05SQ

10.1

5.4

Parallel/Series 06SQ

9.5

5.1

Low-height Parallel/
Series 08SQ

1/2

2.0

1.1

Low-height Parallel/
Series 09SQ

1/2

6.7

3.6

Low-height Series 10SQ

2 x 1/2

7.5

4.0

VAV-SVX08D-EN

25

Unit Setup

Electrically Commutated Motor (ECM)


Table 8.

Maximum PSC fan motor amperage (FLA)

Fan Size

HP VAC

115
VAC

277
VAV

347
VAC

208

Parallel/Series 02SQ

1/8

1.6

Parallel/Series old trane vav boxes 04SQ

1/3

5.5

2.0

1.8

Parallel/Series 05SQ

1/2

6.7

2.4

2.2

Parallel/Series 06SQ

1/2

3.8

3.3

4.6

Parallel/Series 07SQ

4.7

3.8

6.6

Low-height Parallel/
Series 08SQ

1/3

5.5

2.5

1.8

Low-height Parallel/
Series 09SQ

1/3

5.5

2.5

1.8

Series Low-height
10SQ

2 x 1/8

11.0

5.0

3.5

Parallel Low-Height
10SQ

2 x 1/8

9.4

3.5

3.0

(SCR) Motor Speed Control Adjustment


Procedure.
In order to make units more convenient and efficient to
balance, an SCR (silicone control rectifier) is provided as
standard on all fan-powered units.
The SCR is located on the side of the fan control vav facgts the speed of the motor, the external knob must be
rotated either clockwise or counterclockwise depending
on the desired enviro-tec vav box k factor adjustment.
There is an internal potentiometer (Figure 22, p. 26)
setting on the SCR controller that can be accessed by
removing the control box cover.This internal
potentiometer is set at the factory to the enviro-tec vav box k factor motor
voltage.

Figure 23. ECM control board

Trane offers an energy efficient ECM motor as a motor


option. Balancing of an ECM motor is accomplished
through electronic control adjustments on the ECM
control board (see Figure 23, p. 26). Potentiometer
settings for a multitude of CFM settings are given in
Table 9, p. 27 thru Table 21, p. 39. Other potentiometer
settings can be determined either by interpolating from
these tables or by using the following equation:
CFMsetting = CFMmin + {(Potentiometer Setting) x
[(CFMmax - CFMmin)/100]}
There is an LED on vava 4k projectors ECM control board, which will blink
one time for every 100 CFM of motor setting. For example,
the LED on a unit set for 790 CFM will blink 7 times.The
LED on a unit set for 800 CFM will blink 8 times.
Note: This feature only verifies vava boom.orly the CFM is set
properly.This feature does old trane vav boxes indicate at what
speed the motor is actually running.
The ECM must be load tested. In other words, the fan
must be connected to properly test the ECM.

It may be necessary to adjust this in old trane vav boxes field depending on


the buildings power factor.
Figure 22. SCR (L) & internal potentiometer (R)

120 v

Max

208 v
277 v

347 v
DO NOT SET THIS
POTENTIOMETER
BELOW THE VOLTAGE
OF THE FAN MOTOR.

Note: Do not set this potentiometer below the voltage of


the fan motor.

26

VAV-SVX08D-EN

Unit Setup
Table 9.
Table 9.

VPxF 03SQ ECM CFM

Motor Min CFM: 160


Motor Max CFM: 1085

Motor Min CFM: 160


Motor Max CFM: 1085
CFM

L/sec

% Setting

160
170
179
188
198

76
80
84
89
93

1
2
3
4
5

207
216
226
235
244

98
102
107
111
115

6
7
8
9
10

254
263
272
282
291

120
124
129
133
137

11
12
13
14
15

300
310
319
328
338

142
146
151
155
159

16
17
18
19
20

347
356
366
375
385

164
168
173
177
181

21
22
23
24
25

394
403
413
422
431

186
190
195
199
204

26
27
28
29
30

441
450
459
469
478

208
212
217
221
226

31
32
33
34
35

487
497
506
515
525

230
234
239
243
248

36
37
38
39
40

534
543
553
562
571

252
256
261
265
270

41
42
43
44
45

581
590
599
609
618

274
278
283
287
292

46
47
48
49
50

627
637
646
655
665

296
300
305
309
314

51
52
53
54
55

VAV-SVX08D-EN

VPxF 03SQ ECM CFM (continued)

CFM

L/sec

% Setting

674
683
693
702
711

318
323
327
331
336

56
57
58
59
60

721
730
739
749
758

340
345
349
353
358

61
62
63
64
65

767
777
786
795
805

362
367
371
375
380

66
67
68
69
70

814
823
833
842
852

384
389
393
397
402

71
72
73
74
75

861
870
880
889
898

406
411
415
419
424

76
77
78
79
80

908
917
926
936
945

428
433
437
442
446

81
82
83
84
85

954
964
973
982
992

450
455
459
464
468

86
87
88
89
90

1001
1010
1020
1029
1038

472
477
481
486
490

91
92
93
94
95

1048
1057
1066
1076
1085

494
499
503
508
512

96
97
98
99
100

27

Unit Setup
Table 10. VPxF 04SQ ECM CFM (continued)
Table 10. VPxF 04SQ ECM CFM

Motor Min CFM: 220


Motor Max CFM: 1510

Motor Min CFM: 220


Motor Max CFM: 1510

28

CFM

L/sec

% Setting

220
233
246
259
272

104
110
116
122
128

1
2
3
4
5

285
298
311
324
337

135
141
147
153
159

6
7
8
9
10

350
363
376
389
402

165
171
178
184
190

11
12
13
14
15

415
429
442
455
468

196
202
208
215
221

16
17
18
19
20

481
494
507
520
533

227
233
239
245
251

21
22
23
24
25

546
559
572
585
598

258
264
270
276
282

26
27
28
29
30

611
624
637
650
663

288
294
301
307
313

31
32
33
34
35

676
689
702
715
728

319
325
331
338
344

36
37
38
39
40

741
754
767
780
793

350
356
362
368
374

41
42
43
44
45

806
819
832
845
859

381
387
393
399
405

46
47
48
49
50

872
885
898
911
924

411
417
424
430
436

51
52
53
54
55

CFM

L/sec

% Setting

937
950
963
976
989

442
448
454
461
467

56
57
58
59
60

1002
1015
1028
1041
1054

473
479
485
491
497

61
62
63
64
65

1067
1080
1093
1106
1119

504
510
516
522
528

66
67
68
69
70

1132
1145
1158
1171
1184

534
540
547
553
559

71
72
73
74
75

1197
1210
1223
1236
1249

565
571
577
584
590

76
77
78
79
80

1262
1275
1288
1302
1315

596
602
608
614
620

81
82
83
84
85

1328
1341
1354
1367
1380

627
633
639
645
651

86
87
88
89
90

1393
1406
1419
1432
1445

657
663
670
676
682

91
92
93
94
95

1458
1471
1484
1497
1510

688
694
700
706
713

96
97
98
99
100

VAV-SVX08D-EN

Unit Setup
Table 11.
Table 11.

VPxF 05SQ ECM CFM

Motor Min CFM: 280


Motor Max CFM: 1850

Motor Min CFM: 280


Motor Max CFM: 1850
CFM

L/sec

% Setting

280
296
312
327
343

132
140
147
155
162

1
2
3
4
5

359
375
391
407
423

170
177
184
192
199

6
7
8
9
10

438
454
470
486
502

207
214
222
229
237

11
12
13
14
15

518
534
549
565
581

244
252
259
267
274

16
17
18
19
20

597
613
629
645
661

282
289
297
304
312

21
22
23
24
25

676
692
708
724
740

319
327
334
342
349

26
27
28
29
30

756
772
787
803
819

357
364
372
379
387

31
32
33
34
35

835
851
867
883
898

394
402
409
417
424

36
37
38
39
40

914
930
946
962
978

431
439
446
454
461

41
42
43
44
45

994
1009
1025
1041
1057

469
476
484
491
499

46
47
48
49
50

1073
1089
1105
1120
1136

506
514
521
529
536

51
52
53
54
55

VAV-SVX08D-EN

VPxF 05SQ ECM CFM (continued)

CFM

L/sec

% Setting

1152
1168
1184
1200
1216

544
551
559
566
574

56
57
58
59
60

1231
1247
1263
1279
1295

581
589
596
604
611

61
62
63
64
65

1311
1327
1342
1358
1374

619
626
634
641
649

66
67
68
69
70

1390
1406
1422
1438
1454

656
664
671
678
686

71
72
73
74
75

1469
1485
1501
1517
1533

693
701
708
716
723

76
77
78
79
80

1549
1565
1580
1596
1612

731
738
746
753
761

81
82
83
84
85

1628
1644
1660
1676
1691

768
776
783
791
798

86
87
88
89
90

1707
1723
1739
1755
1771

806
813
821
828
836

91
92
93
94
95

1787
1802
1818
1834
1850

843
851
858
866
873

96
97
98
99
100

29

Unit Setup
Table 12. VPxF 06SQ ECM CFM (continued)
Table 12. VPxF 06SQ ECM CFM

Motor Min CFM: 530


Motor Max CFM: 2100

Motor Min CFM: 530


Motor Max CFM: 2100

30

CFM

L/sec

% Setting

530
546
562
577
593

250
258
265
273
280

1
2
3
4
5

609
625
641
657
673

287
295
302
310
317

6
7
8
9
10

688
704
720
736
752

325
332
340
347
355

11
12
13
14
15

768
784
799
815
831

362
370
377
385
392

16
17
18
19
20

847
863
879
895
911

400
407
415
422
430

21
22
23
24
25

926
942
958
974
990

437
445
452
460
467

26
27
28
29
30

1006
1022
1037
1053
1069

475
482
490
497
505

31
32
33
34
35

1085
1101
1117
1133
1148

512
520
527
535
542

36
37
38
39
40

1164
1180
1196
1212
1228

549
557
564
572
579

41
42
43
44
45

1244
1259
1275
1291
1307

587
594
602
609
617

46
47
48
49
50

1323
1339
1355
1370
1386

624
632
639
647
654

51
52
53
54
55

CFM

L/sec

% Old trane vav boxes Setup
Table 13. VSxF 03SQ ECM CFM (continued)
Table 13. VSxF 03SQ ECM CFM

Motor Min CFM: 200


Motor Max CFM: 1100

Motor Min CFM: 200


Motor Max CFM: 1100
CFM

L/sec

% Setting

200
209
218
227
236

94
99
103
107
112

1
2
3
4
5

246
255
264
273
282

116
120
124
129
133

6
7
8
9
10

291
300
309
318
327

137
142
146
150
154

11
12
13
14
15

336
346
355
364
373

159
163
167
172
176

16
17
18
19
20

382
391
400
409
418

180
185
189
193
197

21
22
23
24
25

427
436
446
455
464

202
206
210
215
219

26
27
28
29
30

473
482
491
500
509

223
227
232
236
240

31
32
33
34
35

518
527
536
546
555

245
249
253
257
262

36
37
38
39
40

564
573
582
591
600

266
270
275
279
283

41
42
43
44
45

609
618
627
636
646

287
292
296
300
305

46
47
48
49
50

655
664
673
682
691

309
313
318
322
326

51
52
53
54
55

VAV-SVX08D-EN

CFM

L/sec

% Setting

700
709
718
727
736

330
335
339
343
348

56
57
58
59
60

745
755
764
773
782

352
356
360
365
369

61
62
63
64
65

791
800
809
818
827

373
378
382
386
390

66
67
68
69
70

836
845
855
864
873

395
399
403
408
412

71
72
73
74
75

882
891
900
909
918

416
420
425
429
433

76
77
78
79
80

927
936
945
955
964

438
442
446
451
455

81
82
83
84
85

973
982
991
1000
1009

459
463
468
472
476

86
87
88
89
90

1018
1027
1036
1045
1055

481
485
489
493
498

91
92
93
94
95

1064
1073
1082
1091
1100

502
506
511
515
519

96
97
98
99
100

31

Unit Setup
Table 14. VSxF 04SQ ECM CFM (continued)
Table 14. VSxF 04SQ ECM CFM

Motor Min CFM: 275


Motor Max CFM: 1500

Motor Min CFM: 275


Motor Max CFM: 1500

32

CFM

L/sec

% Setting

275
288
300
312
325

130
136
142
147
153

1
2
3
4
5

337
350
362
374
387

159
165
171
177
183

6
7
8
9
10

399
411
424
436
449

188
194
200
206
212

11
12
13
14
15

461
473
486
498
510

218
223
229
235
241

16
17
18
19
20

523
535
548
560
572

247
253
258
264
270

21
22
23
24
25

585
597
609
622
634

276
282
288
293
299

26
27
28
29
30

646
659
671
684
696

305
311
317
323
328

31
32
33
34
35

708
721
733
745
758

334
340
346
352
358

36
37
38
39
40

770
783
795
807
820

363
369
375
381
387

41
42
43
44
45

832
844
857
869
882

393
399
404
410
416

46
47
48
49
50

894
906
919
931
943

422
428
434
439
445

51
52
53
54
55

CFM

L/sec

% Setting

956
968
980
993
1005

451
457
463
469
474

56
57
58
59
60

1018
1030
1042
1055
1067

480
486
492
498
504

61
62
63
64
65

1079
1092
1104
1117
1129

509
515
521
527
533

66
67
68
69
70

1141
1154
1166
1178
1191

539
544
550
556
562

71
72
73
74
75

1203
1215
1228
1240
1253

568
574
579
585
591

76
77
78
79
80

1265
1277
1290
1302
1314

597
603
609
615
620

81
82
83
84
85

1327
1339
1352
1364
1376

626
632
638
644
650

86
87
88
89
90

1389
1401
1413
1426
1438

655
661
667
673
679

91
92
93
94
95

1451
1463
1475
1488
1500

685
690
696
702
708

96
97
98
99
100

VAV-SVX08D-EN

Unit Setup
Table 15. VSxF 05SQ ECM CFM (continued)
Table 15. VSxF 05SQ ECM CFM

Motor Min CFM: 350


Motor Max CFM: 2050

Motor Min CFM: 350


Motor Max CFM: 2050
CFM

L/sec

% Setting

350
367
385
402
419

165
173
181
190
198

1
2
3
4
5

436
453
470
488
505

206
214
222
230
238

6
7
8
9
10

522
539
556
573
591

246
254
263
271
279

11
12
13
14
15

608
625
642
659
676

287
295
303
311
319

16
17
18
19
20

694
711
728
745
762

327
335
344
352
360

21
22
23
24
25

779
797
814
831
848

368
376
384
392
400

26
27
28
29
30

865
882
900
917
934

408
416
425
433
441

31
32
33
34
35

951
968
985
1003
1020

449
457
465
473
481

36
37
38
39
40

1037
1054
1071
1088
1106

489
498
506
514
522

41
42
43
44
45

1123
1140
1157
1174
1192

530
538
546
554
562

46
47
48
49
50

1209
1226
1243
1260
1277

570
579
587
595
603

51
52
53
54
55

VAV-SVX08D-EN

CFM

L/sec

% Setting

1295
1312
1329
1346
1363

611
619
627
635
643

56
57
58
59
60

1380
1398
1415
1432
1449

651
660
668
676
684

61
62
63
64
65

1466
1483
1501
1518
1535

692
700
708
716
724

66
67
68
69
70

1552
1569
1586
1604
1621

732
741
749
757
765

71
72
73
74
75

1638
1655
1672
1689
1707

773
781
789
797
805

76
77
78
79
80

1724
1741
1758
1775
1792

814
822
830
838
846

81
82
83
84
85

1810
1827
1844
1861
1878

854
862
870
878
886

86
87
88
89
90

1895
1913
1930
1947
1964

895
903
911
919
927

91
92
93
94
95

1981
1998
2016
2033
2050

935
943
951
959
967

96
97
98
99
100

33

Unit Setup
Table 16. VSxF 06SQ ECM CFM (continued)
Table 16. VSxF 06SQ ECM CFM

Motor Min CFM: old trane vav boxes Max CFM: 2500

Motor Min CFM: 700


Motor Max CFM: 2500

34

CFM

L/sec

% Setting

700
718
737
755
773

330
339
348
356
365

1
2
3
4
5

791
809
827
846
864

373
382
391
399
408

6
7
8
9
10

882
900
918
937
955

416
425
433
442
451

11
12
13
14
15

973
991
1009
1027
1046

459
468
476
485
493

16
17
18
19
20

1064
1082
1100
1118
1137

502
511
519
528
536

21
22
23
24
25

1155
1173
1191
1209
1227

545
554
562
571
579

26
27
28
29
30

1246
1264
1282
1300
1318

588
596
605
614
622

31
32
33
34
35

1336
1355
1373
1391
1409

631
639
648
656
665

36
37
38
39
40

1427
1446
1464
1482
1500

674
682
691
699
708

41
42
43
44
45

1518
1536
1555
1573
1591

717
725
734
742
751

46
47
48
49
50

1609
1627
1646
1664
1682

759
768
777
785
794

51
52
53
54
55

CFM

L/sec

% Setting

1700
1718
1736
1755
1773

802
811
820
828
837

56
57
58
59
60

1791
1809
1827
1846
1864

845
854
862
871
880

61
62
63
64
65

1882
1900
1918
1936
1955

888
897
905
914
922

66
67
68
69
70

1973
1991
2009
2027
2046

931
940
948
957
965

71
72
73
74
75

2064
2082
2100
2118
2136

974
983
991
1000
1008

76
77
78
79
80

2155
2173
2191
2209
2227

1017
1025
1034
1043
1051

81
82
83
84
85

2245
2264
2282
2300
2318

1060
1068
1077
1085
1094

86
87
88
89
90

2336
2355
2373
2391
2409

1103
1111
1120
1128
1137

91
92
93
94
95

2427
2445
2464
2482
2500

1146
1154
1163
1171
1180

96
97
98
99
100

VAV-SVX08D-EN

Unit Setup
Table 17.
Table 17.

LPxF 08SQ ECM CFM

Motor Min CFM: 100


Motor Max CFM: 460

Motor Min CFM: 100


Motor Max CFM: 460
CFM

L/sec

% Setting

100
103
107
111
114

47
49
50
52
54

1
2
3
4
5

118
121
125
129
132

56
57
59
61
62

6
7
8
9
10

136
140
143
147
151

64
66
68
69
71

11
12
13
14
15

154
158
162
165
169

73
75
76
78
80

16
17
18
19
20

172
176
180
183
187

81
83
85
87
88

21
22
23
24
25

191
194
198
202
205

90
92
93
95
97

26
27
28
29
30

209
212
216
220
223

99
100
102
104
105

31
32
33
34
35

227
231
234
238
242

107
109
111
112
114

36
37
38
39
40

245
249
253
256
260

116
117
119
121
123

41
42
43
44
45

263
267
271
274
278

124
126
128
129
131

46
47
48
49
50

282
285
289
293
296

133
135
136
138
140

51
52
53
54
55

VAV-SVX08D-EN

LPxF 08SQ ECM CFM (continued)

CFM

L/sec

% Setting

300
303
307
311
314

142
143
145
147
148

56
57
58
59
60

318
322
325
329
333

150
152
154
155
157

61
62
63
64
65

336
340
344
347
351

159
160
162
164
166

66
67
68
69
70

354
358
362
365
369

167
169
171
172
174

71
72
73
74
75

373
376
380
384
387

176
178
179
181
183

76
77
78
79
80

391
394
398
402
405

184
186
188
190
191

81
82
83
84
85

409
413
416
420
424

193
195
196
198
200

86
87
88
89
90

427
431
435
438
442

202
203
205
207
209

91
92
93
94
95

445
449
453
456
460

210
212
214
215
217

96
97
98
99
100

35

Unit Setup
Table 18.
Table 18.

LPxF 09SQ ECM CFM

Motor Min CFM: 250


Motor Max CFM: 1025

Motor Vava usb c hub 8-in-1 adapter bestbuy CFM: 250


Motor Max CFM: 1025

36

LPxF 09SQ ECM CFM (continued)

CFM

L/sec

% Setting

250
258
265
273
281

118
122
125
129
133

1
2
3
4
5

289
297
305
312
320

136
140
144
147
151

6
7
8
9
10

328
336
344
352
359

155
159
162
166
170

11
12
13
14
15

367
375
383
391
399

173
177
181
184
188

16
17
18
19
20

406
414
422
430
438

192
196
199
203
207

21
22
23
24
25

446
453
461
469
477

210
214
218
221
225

26
27
28
29
30

485
493
500
508
516

229
232
236
240
244

31
32
33
34
35

524
532
540
547
555

247
251
255
258
262

36
37
38
39
40

563
571
579
587
594

266
269
273
277
281

41
42
43
44
45

602
610
618
626
634

284
288
292
295
299

46
47
48
49
50

641
649
657
665
673

303
306
310
314
317

51
52
53
54
55

CFM

L/sec

% Setting

680
688
696
704
712

321
325
329
332
336

56
57
58
59
60

720
727
735
743
751

340
343
347
351
354

61
62
63
64
65

759
767
774
782
790

358
362
365
369
373

66
67
68
69
70

798
806
814
821
829

377
380
384
388
391

71
72
73
74
75

837
845
853
861
868

395
399
402
406
410

76
77
78
79
80

876
884
892
900
908

414
417
421
425
428

81
82
83
84
85

915
923
931
939
947

432
436
439
443
447

86
87
88
89
90

955
962
970
978
986

450
454
458
462
465

91
92
93
94
95

994
1002
1009
1017
1025

469
473
476
480
484

96
97
98
99
100

VAV-SVX08D-EN

Unit Setup
Table 19.
Table 19.

LSxF 08SQ ECM CFM

Motor Min CFM: 100


Motor Max CFM: 460

Motor Min CFM: 100


Motor Max CFM: 460
CFM

L/sec

% Setting

100
103
107
111
114

47
49
50
52
54

1
2
3
4
5

118
121
125
129
132

56
57
59
61
62

6
7
8
9
10

136
140
143
147
151

64
66
68
69
71

11
12
13
14
15

154
158
162
165
169

73
75
76
78
80

16
17
18
19
20

172
176
180
183
187

81
83
85
87
88

21
22
23
24
25

191
194
198
202
205

90
92
93
95
97

26
27
28
29
30

209
212
216
220
223

99
100
102
104
105

31
32
33
34
35

227
231
234
238
242

107
109
111
112
114

36
37
38
39
40

245
249
253
256
260

116
117
119
121
123

41
42
43
44
45

263
267
271
274
278

124
126
128
129
131

46
47
48
49
50

282
285
289
293
296

133
135
136
138
140

51
52
53
54
55

VAV-SVX08D-EN

LSxF 08SQ ECM CFM (continued)

CFM

L/sec

% Setting

300
303
307
311
314

142
143
145
147
148

56
57
58
59
60

318
322
325
329
333

150
152
154
155
157

61
62
63
64
65

336
340
344
347
351

159
160
162
164
166

66
67
68
69
70

354
358
362
365
369

167
169
171
172
174

71
72
73
74
75

373
376
380
384
387

176
178
179
181
183

76
77
78
79
80

391
394
398
402
405

184
186
188
190
191

81
82
83
84
85

409
413
416
420
424

193
195
196
198
200

86
87
88
89
90

427
431
435
438
442

202
203
205
207
209

91
92
93
94
95

445
449
453
456
460

210
212
214
215
217

96
97
98
99
100

37

Unit Setup
Table 20.
Table 20.

LSxF 09SQ ECM CFM

Motor Min CFM: 240


Motor Max CFM: 950

Motor Min CFM: 240


Motor Max CFM: 950

38

LSxF 09SQ ECM Vavo portuguese (continued)

CFM

L/sec

% Setting

240
247
255
262
269

113
117
120
123
127

1
2
3
4
5

276
283
290
298
305

130
134
137
140
144

6
7
8
9
10

312
319
326
333
341

147
151
154
157
161

11
12
13
14
15

348
355
362
369
376

164
167
171
174
178

16
17
18
19
20

384
391
398
405
412

181
184
188
191
195

21
22
23
24
25

419
427
434
441
448

198
201
205
208
211

26
27
28
29
30

455
462
470
477
484

215
218
222
225
228

31
32
33
34
35

491
498
505
513
520

232
235
239
242
245

36
37
38
39
40

527
534
541
548
556

249
252
255
259
262

41
42
43
44
45

563
570
577
584
592

266
269
272
276
279

46
47
48
49
50

599
606
613
620
627

283
286
289
293
296

51
52
53
54
55

CFM

L/sec

% Setting

635
642
649
656
663

299
303
306
310
313

56
57
58
59
60

670
678
685
692
699

316
320
323
327
330

61
62
63
64
65

706
713
721
728
735

333
337
340
343
347

66
67
68
69
70

742
749
756
764
771

350
354
357
360
364

71
72
73
74
75

778
785
792
799
807

367
371
374
377
381

76
77
78
79
80

814
821
828
835
842

384
387
391
394
398

81
82
83
84
85

850
857
864
871
878

401
404
408
411
415

86
87
88
89
90

885
893
900
907
914

418
421
425
428
431

91
92
93
94
95

921
928
936
943
950

435
438
442
445
448

96
97
98
99
100

VAV-SVX08D-EN

Unit Setup
Table 21.
Table 21.

LSxF 10SQ ECM CFM

Motor Min CFM: 400


Motor Max CFM: 1800

Motor Min CFM: 400


Motor Max CFM: 1800
CFM

L/sec

% Setting

400
414
428
443
457

189
196
202
209
216

1
2
3
4
5

471
485
499
513
527

222
229
236
242
249

6
7
8
9
10

542
556
570
584
598

256
262
269
276
282

11
12
13
14
15

612
626
641
655
669

289
296
302
309
316

16
17
18
19
20

683
697
711
725
740

322
329
336
342
349

21
22
23
24
25

754
768
782
796
810

356
362
369
376
382

26
27
28
29
30

824
838
853
867
881

389
396
402
409
416

31
32
33
34
35

895
909
923
937
952

422
429
436
442
449

36
37
38
39
40

966
980
994
1008
1022

456
462
469
476
482

41
42
43
44
45

1036
1051
1065
1079
1093

489
496
502
509
516

46
47
48
49
50

1107
1121
1135
1150
1164

523
529
536
543
549

51
52
53
54
55

VAV-SVX08D-EN

LSxF 10SQ ECM CFM (continued)

CFM

L/sec

% Setting

1178
1192
1206
1220
1234

556
563
569
576
583

56
57
58
59
60

1249
1263
1277
1291
1305

589
596
603
609
616

61
62
63
64
65

1319
1333
1348
1362
1376

623
629
636
643
649

66
67
68
69
70

1390
1404
1418
1432
1447

656
663
669
676
683

71
72
73
74
75

1461
1475
1489
1503
1517

689
696
703
709
716

76
77
78
79
80

1531
1545
1560
1574
1588

723
729
736
743
749

81
82
83
84
85

1602
1616
1630
1644
1659

756
763
769
776
783

86
87
88
89
90

1673
1687
1701
1715
1729

789
796
803
809
816

91
92
93
94
95

1743
1758
1772
1786
1800

823
829
836
843
850

96
97
98
99
100

39

Wiring Diagrams
Note: See programming guides listed below for detailed wiring information on the following:
UCM 4.2: VAV-SVX01*-EN

UC400: VAV-SVX07*-EN

VV550: VAV-SVP01*-EN

Heaters with Contactors


Figure 24. Single-duct units (electronic or DDC/UCM)

40

VAV-SVX08D-EN

Wiring Diagrams

Figure 25. Single-duct units (pneumatic controls)

VAV-SVX08D-EN

41

Wiring Diagrams

Figure 26. Fan-powered units (electronic or DDC/UCM)

42

VAV-SVX08D-EN

Wiring Diagrams

Figure 27. Fan-powered units (pneumatic controls)

VAV-SVX08D-EN

43

Wiring Diagrams

Figure 28. Fan-powered control boxes


Fan-powered Control Box
with Pneumatic Controls
Duct Pressure Switch Option

GREEN
GROUND
SCREW

L1

GREEN
GROUND
SCREW

5.

TRANSFORMER

BL
BR
R

BK

BK

24V

24V

TO VAV
CONTROLLER

DISCONNECT
SWITCH

L1

5.

TRANSFORMER

6.

LINE VOLTAGE
OR FROM HEATER TERMINAL

LINE VOLTAGE
OR FROM HEATER TERMINAL

Fan-powered Control Box


with Electronic or DDC Controls

NO

DISCONNECT
SWITCH

BK

BK

2.

2.
NC
BK

BK

BK
MOTOR
RELAY

BK

BR

MOTOR
RELAY

24V

BK
FUSE

4.

24V

4.

R
W

MOTOR
SPEED
CONTROL

MOTOR
SPEED
CONTROL

BK

BK

TERMINAL
BLOCK
W-COM

TERMINAL
BLOCK
W-COM

BK

BR

FUSE
1

FAN CONTROL BOX

FAN CONTROL BOX


W BK

W BK
BR

BR
MOTOR
FAN

BR
MOTOR
FAN

CAPACITOR

3.

3.

WARNING

LINE VOLTAGE
OR FROM HEATER TERMINAL

Fan-powered Control Box


with Pneumatic Controls

HAZARDOUS VOLTAGE!
DISCONNECT, LOCK OUT AND TAG
ALL ELECTRIC POWER INCLUDING
REMOTE DISCONNECTS BEFORE
SERVICING.

GREEN
GROUND
SCREW

DUCT PRESSURE MAIN CONTROL

6.

BR

CAPACITOR

BK

DUCT PRESSURE
SWITCH

BK

L1

5.

DISCHARGE MOTOR START/RUN


CAPACITORS BEFORE SERVICING.
FAILURE TO DISCONNECT POWER
BEFORE SERVICING CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.

BK NO
C

CAUTION

P.E. SWITCH-1

BK

2.

NC
BK

BK

BK

NC

USE COPPER CONDUCTORS ONLY!


UNIT TERMINALS ARE NOT DESIGNED
TO ACCEPT OTHER TYPES OF
CONDUCTORS.

DISCONNECT
SWITCH

NO

P.E. SWITCH-2

BK
BK
NO

6.

FAILURE TO DO SO MAY CAUSE


DAMAGE TO THE EQUIPMENT.

BK

FUSE

4.

C
NC
P.E. SWITCH
W

NOTES:

DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED


EXTERNAL TO CONTROL BOX.

3.

CAPACITOR IS INSTALLED ON FAN HOUSING.

4.

FUSE IS OPTIONAL.

6.

DETERMINED Vava dashcam mount MOTOR VOLTAGE ON ORDER.


VOLTAGE FOUND ON UNIT NAMEPLATE.
FOR SERIES FAN POWERED TERMINAL UNITS ONLY.

TERMINAL
BLOCK

MOTOR
SPEED
CONTROL

BK

2.

5.

44

FACTORY INSTALLED
BY OTHERS
OPTIONAL OR ALTERNATE CIRCUITRY
W-COM

1.

FAN CONTROL BOX


W BK
BR
CAPACITOR

BR
MOTOR
FAN

3.

VAV-SVX08D-EN

Wiring Diagrams

Figure 29. Fan-powered units with ECM


Fan-powered Control Box w/ ECM with Vav media or DDC Controls
(Depending on the size of the unit, the ECM board may or may not be located
in the fan control box.)

Fan-powered Control Box w/ ECM with Pneumatic Controls


Duct Pressure Switch Option

LINE Enviro-tec vav box k factor VOLTAGE

FAN
MOTOR

FAN
MOTOR

OR FROM HEATER TERMINAL

OR FROM HEATER TERMINAL

4.

BK

GR

RED

TERMINAL
BLOCK
DISCONNECT
SWITCH

2.
DISCONNECT
SWITCH
W

3.

MOTOR
RELAY

3.

BL

BK

5.
POWER
FACTOR
CORRECTION
CHOKE

NO BL

BL
C
TO VAV

NEUT.

24V

RED

RED

NC

SWITCH
BK

TRANSFORMER

ECM
BOARD

BL

G
R

DUCT
PRESSURE

W
BK

24V

CONTROLLER

BL

24V

BK

24V

G
R

ECM
BOARD

W
BK

FUSE

FUSE

TERMINAL
BLOCK

RED

2.
3.

GREEN
GROUND
SCREW

BK

24V

NEUT.

BK

BK

BK

GR
GREEN
GROUND
SCREW

TRANSFORMER
POWER FACTOR
CORRECTION CHOKE

FAN CONTROL BOX

FAN CONTROL BOX

WARNING
HAZARDOUS VOLTAGE!
DISCONNECT, LOCK OUT AND TAG
ALL ELECTRIC POWER INCLUDING
REMOTE DISCONNECTS BEFORE
SERVICING.
DISCHARGE MOTOR START/RUN
CAPACITORS BEFORE SERVICING.

Fan-powered Control Box with Pneumatic Controls

FAILURE TO DISCONNECT Vava usb c hub 8-in-1 adapter bestbuy SERVICING CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.

LINE VOLTAGE
OR FROM HEATER TERMINAL

FAN
MOTOR

4.

CAUTION

GR

USE COPPER CONDUCTORS ONLY!

BK

GREEN
GROUND
SCREW

BK

UNIT TERMINALS ARE NOT DESIGNED


TO ACCEPT OTHER TYPES OF
CONDUCTORS.

TERMINAL
BLOCK

FAILURE TO DO SO MAY CAUSE


DAMAGE TO THE Old trane vav boxes PRESSURE MAIN CONTROL

BK

W
FUSE

BL
Y

5.

POWER FACTOR
CORRECTION CHOKE

NO

BK NO

NC

NEUT.
RED

24V
RED

P.E. SWITCH-2
TRANSFORMER

NOTES:
1.

BL

NO

FACTORY INSTALLED
BY OTHERS
OPTIONAL OR ALTERNATE CIRCUITRY

ECM
BOARD

G
R

BK

BK

W
BK

P.E. SWITCH-1

BK

24V

C
NC

NC
P.E. SWITCH

2.

DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED


EXTERNAL TO CONTROL BOX.

3.

FUSE IS OPTIONAL.

4.

DETERMINED BY MOTOR VOLTAGE ON ORDER.


VOLTAGE FOUND ON UNIT NAMEPLATE.

5.

FOR SERIES FAN POWERED TERMINAL UNITS ONLY.

VAV-SVX08D-EN

FAN CONTROL BOX

45

Wiring Diagrams

Figure 30. Fan-powered low-height units


Fan-Powered Low-Height Control Box old trane vav boxes Electronic or DDC Controls
CAPACITOR

5.
LINE VOLTAGE
OR FROM HEATER TERMINAL

Fan-Powered Low-Height Vava usb c hub 8-in-1 adapter bestbuy Box with Pneumatic Controls

MOTOR
BR

CAPACITOR

Duct Pressure Switch Option


BR
CAPACITOR

}
L1

FAN
MOTOR 2
(SIZE 10 ONLY)

3.

FAN
3.

BR
W

BK

BK

5.
LINE VOLTAGE
OR FROM HEATER TERMINAL

3.

CAPACITOR

BR

L1

N
BR

MOTOR
SPEED

GREEN

CONTROL

BK

2.

BK

GROUND

DISCONNECT
W

BR

BR

2.

SCREW

BK

FAN
MOTOR 2
(SIZE 10 ONLY)

MOTOR

GREEN
GROUND

3.

FAN

BR

MOTOR

SCREW

SWITCH
W

2.

SPEED

BK

CONTROL

TERMINAL
W

BLOCK
2.
4.

BK

BR

FUSE

BK

TERMINAL
BLOCK

DISCONNECT
SWITCH

BR

W
W

BK
W or BR

24V

BK

BK

MOTOR

BL
BR

RELAY

R
TRANSFORMER

BR

4.

BK
BK

FUSE

TO VAV
6.

CONTROLLER

BK

BK

NO

BL

BL
BL
1

24V

1 24V 3

TRANSFORMER

NC
R

24V

DUCT
MOTOR

PRESSURE
FAN CONTROL BOX

RELAY

SWITCH
FAN CONTROL BOX

WARNING
HAZARDOUS VOLTAGE!
DISCONNECT, LOCK OUT AND TAG
ALL ELECTRIC POWER INCLUDING
REMOTE DISCONNECTS BEFORE
SERVICING.
DISCHARGE MOTOR START/RUN
CAPACITORS BEFORE SERVICING.

Fan-Powered Low-Height Control Box with Pneumatic Controls

FAILURE TO DISCONNECT POWER


BEFORE SERVICING CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.

FAN
MOTOR

CAUTION

3.

5.
LINE VOLTAGE
OR FROM HEATER TERMINAL

UNIT TERMINALS ARE NOT DESIGNED


TO ACCEPT OTHER TYPES OF
CONDUCTORS.

L1

BK

CAPACITOR

BR

FAN
MOTOR 2
(SIZE 10 ONLY)

BR

BR

USE COPPER CONDUCTORS ONLY!

3.

W
BK

CAPACITOR

FAILURE TO DO SO MAY CAUSE


DAMAGE TO THE EQUIPMENT.

GREEN
GROUND
SCREW

MOTOR
SPEED
CONTROL

2.

DUCT PRESSURE MAIN CONTROL

6.

BK

TERMINAL
BLOCK

2.

NO

BK NO
C
NC

NC

P.E. SWITCH-1

BK

P.E. SWITCH-2

DISCONNECT

BK

BK

SWITCH

BR

4.
FUSE

BK

BK

NOTES:
1.

FACTORY INSTALLED
BY OTHERS
OPTIONAL OR ALTERNATE CIRCUITRY

2.

DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED


EXTERNAL TO CONTROL BOX.

3.

CAPACITOR IS INSTALLED ON FAN HOUSING.

4.

FUSE IS OPTIONAL.

5.

DETERMINED BY MOTOR VOLTAGE ON ORDER.


VOLTAGE FOUND ON UNIT NAMEPLATE.

6.

FOR SERIES FAN POWERED TERMINAL UNITS ONLY.

NO
BK

C
NC
P.E. SWITCH

FAN CONTROL BOX

46

VAV-SVX08D-EN

Wiring Diagrams

Figure 31. Fan-powered low-height units with ECM


Fan-Powered Low-Height Control Box w/ ECM with Electronic or DDC Controls

Fan-Powered Low-Height Control Box w/ ECM with Pneumatic Controls

(Depending on the size of the unit, the ECM board may or may not be located
in the fan control box.)

FAN
MOTOR 2
(SIZE 10 ONLY)

FAN
MOTOR

FAN
MOTOR 2
(SIZE 10 ONLY)

GR

NEUT.

TERMINAL
BLOCK

RED

GREEN
GROUND
SCREW

RED
2.
DISCONNECT
SWITCH
W

3.

BK
TERMINAL
BLOCK

DISCONNECT
SWITCH
2.

24V

BK

BK

BK

W
BK

FUSE

BL

BK

G
R

ECM
BOARD

5.
NO BL

MOTOR
RELAY

24V

24V

RED

RED

Y
BK

NEUT.

BL

BL

NC
DUCT
PRESSURE

TO VAV
CONTROLLER

SWITCH
BK

ECM
BOARD

BL

G
R

24V

W
BK

W
BK

FUSE

24V

FAN
MOTOR

BK

GR
GREEN
GROUND
SCREW

3.

4.

LINE VOLTAGE
OR FROM HEATER TERMINAL

LINE Vava usb c hub 8-in-1 adapter bestbuy FROM HEATER TERMINAL

BK

Duct Pressure Switch Option

TRANSFORMER

TRANSFORMER

FAN CONTROL BOX

FAN CONTROL BOX

WARNING
HAZARDOUS VOLTAGE!
DISCONNECT, LOCK OUT AND TAG
ALL ELECTRIC POWER INCLUDING
REMOTE DISCONNECTS BEFORE
SERVICING.
DISCHARGE MOTOR START/RUN
CAPACITORS BEFORE SERVICING.
FAILURE TO DISCONNECT POWER
BEFORE SERVICING CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.

CAUTION

Fan-Powered Low-Height Control Box w/ ECM with Pneumatic Controls

USE COPPER CONDUCTORS ONLY!


UNIT TERMINALS ARE NOT DESIGNED
TO ACCEPT OTHER TYPES OF
CONDUCTORS.

4.
LINE VOLTAGE
OR FROM HEATER TERMINAL

FAN
MOTOR

FAN
MOTOR 2
(SIZE 10 ONLY)

FAILURE TO DO SO MAY CAUSE


DAMAGE TO THE EQUIPMENT.

DUCT PRESSURE MAIN CONTROL

W
BK

BK

BK

GR
GREEN
GROUND
SCREW
TERMINAL
BLOCK

5.

DISCONNECT
SWITCH
2.
3.

NO

BK NO
C

BK

NC

BL
BL

FUSE

NC
NEUT.

BK

BK

2.

RED

RED

BL

DISCONNECT SWITCH, FUSE, & SCR ARE LOCATED


EXTERNAL TO CONTROL BOX.

NO

ECM
BOARD

G
R

FACTORY INSTALLED
BY OTHERS
OPTIONAL OR ALTERNATE CIRCUITRY

W
BK

TRANSFORMER

NOTES:
1.

24V

P.E. SWITCH-2
24V

P.E. SWITCH-1

C
NC
P.E. SWITCH

3.

FUSE IS OPTIONAL.

4.

DETERMINED BY MOTOR VOLTAGE ON ORDER.


VOLTAGE FOUND ON UNIT NAMEPLATE.

5.

FOR SERIES FAN POWERED TERMINAL UNITS ONLY.

FAN CONTROL BOX

VAV-SVX08D-EN

47

Maintenance
Periodic maintenance of theVariTrane product is minimal,
but necessary for efficient operation. Routine
maintenance consists of inspecting/replacing the air filters
of the fan-powered terminals.

Figure 32. Standard motor removal

Motors
Both the PSC (permanent split capacitor) and the ECM
(Electrically Commutated Motor) require no lubrication
during its normal life of operation.

Fan Wheel
Periodically, the fan wheel should be inspected for dirt or
debris and cleaned as necessary.

Filter
The filter on fan-powered terminals will need to be
inspected/replaced routinely depending on the
environmental conditions of the plenum.

Filter Change Out

To remove the filter, turn each of the filter retaining


clips 90 (CW or CCW)

Remove the filter and replace with new filter of the


same frame size.

Return the filter clips to their retainng position by


turning them 90 (CW or CCW) back to their original
position.

Water Coil

Standard height fan-powered series and parallel fan


motors are replaceable through the filter opening and the
standard sliding side access panel.To access the fan
motor, the fan housing must be detached by removing the
mounting bolts that hold the housing to the fan board.
Removing the entire housing allows the fan motor, fan
housing, and fan wheel to be re-aligned on a workbench or
floor and prevent any possible fan wheel rubbing that may
occur. Removing the housing will provide access to the
motor shaft set screw that holds the fan wheel to the motor
shaft.

Water coils should be inspected and the fins should be


cleaned periodically.
Water coils have been provided with an access panel as
standard to assist with inspection and cleaning.

Fan Motor Replacement

WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives
or other energy storing components provided by Trane
or others, refer to the appropriate old trane vav boxes for allowable waiting periods for discharge of
capacitors. Verify with an appropriate voltmeter that all
capacitors have discharged. Failure to disconnect power
and discharge capacitors before servicing could result
in death or serious injury.
For additional information regarding the safe discharge
of capacitors, see PROD-SVB06A-EN.

48

VAV-SVX08D-EN

Maintenance

The low-height fan assembly was designed with an inlet


ring that assists with removal of the fan motor.To access
the fan motor assembly, the bottom panel must be
removed.The inlet ring is held in place by six bolts and
three motor mount bolts. Remove these bolts and the
motor and fan wheel will come out of the fan housing.

Figure 34. Typical heat sink fin orientation

Figure 33. Low-height motor removal

Bottom View

Every Master or Master/Slave relay combination is


mounted on a heat sink to prevent the relays from
overheating during normal operation.The SCR assembly
must always be mounted with the heat sink fins oriented
vertically (See Figure 34, p. 49), with a minimum clearance
of " on all sides of the heat sink for cooling. Where
additional cooling slots are provided in the heater, theVAV
unit must be mounted with a minimum of 1" clearance in
front of the slots.

SCR Assembly

When the 0-10VDC control voltage is present at the Master


relay in both old trane vav boxes and three phase applications, an "ON"
indicating LED light on the Master relay will blink
continually (approximately 0.5 seconds on, 1.0 seconds
off). If the load side voltage is also present at the relay(s),
the Master relay LED and the Slave relay LED blink rate will
increase as the control signal increases. When the control
signal reaches a maximum of 10VDC, all LEDs will be lit
continuously, indicating that the relays are full-open and
continuously conducting. If the control signal is present in
three phase applications while the load side voltage is not,
only the Master relay LED will light and the blink rate will
be johnson controls vav tss solid state relays are used to switch a single old trane vav boxes on and off. An intelligent (Master) relay is used for enviro-tec vav box k factor phase applications. For three phase applications, a
Master-Slave configuration is used to switch two legs of
three phase power to the heater stage.The Master Relay
controls one leg independently, and provides old trane vav boxes control
signal to the Slave Relay, which controls the second leg.

If the SCR assembly does old trane vav boxes appear to be functioning


properly, verify that all required voltages are present and
all that all wiring is properly connected. If all these
conditions are verified, and the SCR LED(s) does not light
and/or the SCR relay(s) does not conduct, the entire Old trane vav boxes sink assembly should be changed out. Individual
Master or Slave relays should not be replaced.

VAV-SVX08D-EN

49

Installation of Diffusers
General

Concealed Spline Ceiling

All units must be installed upright and level as indicated by


the arrow on the side of the units. Return air slots should
be placed perpendicular and offset to the slot diffusers to
avoid short-circuiting of air distribution patterns.

Follow these procedures to finish installation of control


and vava usb c hub 8-in-1 adapter bestbuy diffusers and concealed spline for suspension
ceilings before completing the ceiling construction
(Figure 36, p. 50).

Place the unit in its approximate final position and check


that it is upright and level. For single-slot units, engage
the back of the diffuser over the t-bar with an edge and
both ends resting on the t-bar. For double-slot units,
slide the unit over the t-bar. For center-notch units, place
diffuser over the t-bar, straddling it across a t-bar and
resting on the units ends.

Place the units in their approximate final positions. If using


the trim angle diffuser, its slots must be even with the
spline level. If applying the trim accessory, the bottom of
the diffuser must be level old trane vav boxes the finished ceiling.

If the unit has a fire damper, make sure that the damper is
still fully open. Diffuser discharge must always be flush
with the ceiling tiles old trane vav boxes assure the proper airflow (Coanda
effect).
Diffusers require specific installation information when
mounting to a desired ceiling type. Select the ceiling type
that closely matches the job site application and use the
following procedures.

If installing the trim accessory, insert the trim into the


ceiling opening from below and engage the diffuser slot to
the trim t-bar structure. With bottom flange of trim
accessory against the ceiling, and using the pre-drilled
holes in the flange as a guide, drill holes in the flange of the
diffuser. Join the diffuser and trim accessory with selftaping sheet metal.
Figure 36. Diffuser with trim accessory installation in
concealed spline ceiling

T-Bar Ceiling
Finish installation of the diffuser in t-bar ceiling. (See
Figure 35, p. 50.) Follow these procedures before the
ceiling construction is completed.
1. Position the diffuser at each end resting directly on the
structural t-bar for support and the t-bar fitting into the
channel provided at the unit discharge air throw.
2. A ceiling tile support flange is provided on each side of
the discharge slot of the unit.Trim ceiling tile
approximately 1 inches each to allow for width of
discharge slot. For revealed edge ceilings, tile must be
cut in a Z pattern.
3. Old trane vav boxes ceiling tiles in usual manner with cut edges
resting on the flanges of the air slot.
Figure 35. Diffuser installation in t-bar ceiling

50

VAV-SVX08D-EN

Installation of Diffusers

Drywall/Plaster Ceiling
Finish installation of diffusers old trane vav boxes plaster ceiling. Follow
these procedures before completing the ceiling
construction (Figure 37, p. 51).

NOTICE:
Equipment Damage!
Do not install trim frame into ceiling using screws.
When diffuser is placed on the trim frames, it will pull
out.
1. Suspend the units above the intended ceiling level and
their approximate horizontal positions and finish
running flexible ductwork.
2. After drywall and/or plaster is installed, cut openings to
receive the diffuser air outlets. Also, allow for access
openings to complete installation and service of the
unit.
3. Slide the trim accessory up and into the ceiling
opening. Using the rim accessory as a template, drill
four guide holes in the lip of the diffuser slot. Lower
unit onto trim frame and attach with sheet metal
screws.
Note: The bottom of the throat section must be parallel to
the ceilings for proper air distribution.
Figure 37.

Diffuser with trim accessory installation in


plaster ceiling

Diffuser Flange

Trim Accessory

Plaster trim frame attaches with 24


tension clips on the side of the diffuser.

VAV-SVX08D-EN

51

Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in
creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced
controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.

2013Trane All rights reserved


VAV-SVX08D-EN 27 Jun 2013

We are committed to using environmentally

Supersedes VAV-SVX08C-EN (29 May 2012)

conscious print practices that reduce waste.

Trane VAV Box Retrofit

Some of us may have customers who have encountered the pesky old Trane VariCone or air valve style Old trane vav boxes boxes.  This outdated technology often consists of worn or broken end switches and/or burnt out damper motors.  Due to an overpriced retrofit solution from Trane, end users generally learn to deal with some of these boxes in their building just not working.  Here at Stromquist we can provide our customers with a relatively painless and low cost retrofit solution using Honeywell D690 dampers and  Honeywell ML6161 floating actuators or the MARD zone control damper assembly.

These 9 easy steps will get the box up and running.  The first install should take about 4 hours, and once your customers are familiar with the process they will be able to cut the retrofit time down considerably.

Step 1.  Determine the diameter of the box being retrofitted.

Step 2.  Provide the customer with the proper size  Honeywell D690 and Honeywell ML6161 actuator or MARD damper assembly.

Step 3.  Power down the VAV box, open the access panel at the bottom of the box, and disconnect the wires going to the floating damper motor.

Step 4.  Remove the duct from the inlet side of the VAV box, revealing the attachment hardware for the air valve assembly.  Unbolt and remove the cone.

Step 4.  After the air valve has been removed carefully, detach the air flow ring from the assembly.  If the air flow ring has been damaged or is badly clogged you can provide a KMC SSS-series differential pressure air flow sensor as a replacement.

Step 5.  At this point there are two directions the installer can go to attach the Honeywell damper to the box:

a) Option one is to attach a piece of sheet metal to the inlet side of the box with a hole cut in it to match the outside diameter of the round damper. Then insert the damper and attach it to the back of the box with angle brackets and use duct mastic to seal the edge.

b) Option two is to have the installer fabricate a flanged ring with an inside diameter matching the outside diameter of the new old trane vav boxes assembly and a flange that is wide enough to cover the excess in the opening left by the air valve.  Use sheet metal screws to attach and duct mastic to seal.

Step 6.  Notch the inlet side of the Honeywell damper and install the air flow ring or cut a 1″ hole in the inlet side of the damper and install the KMC SSS-series differential pressure air flow sensor.  Then hook up the air flow pick up tubes.

Step 7.  Install and/or wire the  Honeywell ML6161 floating actuator on the newly installed round damper.

Step 8.  Reconnect the duct to old trane vav boxes inlet side of the damper and re-seal.

Step 9.  Change the run time in the VAV controller from 360 seconds to 90 seconds to match the run time of the Honeywell ML6161, and reconfigure for new air flow sensor if needed.

That’s it!  Less than 10 easy steps to retrofit the antiquated Trane air valve without replacing the VAV box!

vave benchmarking services

Org3551-portal. html]div divh2iCare Data Recovery Pro 8. 6 Crack Keygen [2020]h2divpUtilize it; we will reconstruct records from hard disks, memory credit cards and outside storage area media which might have been detached predictable to a consumer difficulty, illness action or hardware or application failure.

In a utterance, any deleted folder is recoverable from our hard disk with the assist of this strongapplication strongas extended as liberty anywhere recently written data do not overwrite the deleted records.