8 Equipment function
Room control
RS Supply air controller (Room Supply)
RE Extract air controller (Room Extract).
M Room master for single controller, variable setpoint value
S Slave controller (only with room solutions)
Option 1: Power supply
No entry: 24 V AC/DC
T With EM-TRF for 230 V AC mains supply
U With EM-TRF-USV (including battery pack for uninterruptible 230 V AC power supply (UPS)
Option 2: Digital communication interface
No entry: without communication interface
B With EM-BAC-MOD for VACnet MS/TP
M With EM-BAC-MOD for Modbus RTU
I With EM-IP for BACnet IP, Modbus IP and web server
R With EM-IP (including real time clock, RTC) for BACnet IP, Modbus IP and web server
Option 3: Automatic zero point correction
No entry: no zero point correction
Z With EM-AUTOZERO solenoid valve for automatic zero point correction
12 Operating values for factory setting
Volume flow rate [m³/h or l/s]
For operating mode F
qᵥconst: constant volume flow rate1, 2
Other parameters are only relevant for the room master as part
of a room solution3; for single controllers enter 0
qᵥconst_sup: constant supply air (room value)
qᵥconst_ext: constant extract air (room value)
qᵥdiff: supply air/extract air difference (room value)
For operating mode M
qᵥmin: minimum volume flow rate1, 2
qᵥmax: maximum volume flow rate1, 2
Other parameters are only relevant for the room master as part
of a room solution3; for single controllers enter 0
qᵥconst_sup: constant supply air (room value)
qᵥconst_ext: constant extract air (room value)
qᵥdiff: supply air/extract air difference (room value)
For operating mode S
No parameters are required for the slave controller; all entries
have to be made on the room master
For volume flow rate operating values please note:
1 Single controller: qᵥmin, qᵥmax or qᵥconst apply to the controller
2 Room solutions: qᵥmin, qᵥmax, qᵥconst apply to the room
3 For more information on room solutions with several TROX
UNIVERSAL controllers connected with plug and play and for
order examples please refer to the product datasheet
Usefull additions
Optional room control panel
BE-LCD with 40-character display
Type | TVR |
Acoustic cladding | Without acoustic cladding |
Material | Galvanised sheet steel |
Duct connection | Push-fit, suitable for ducts according to EN 1506, with groove for optional lip seal |
Nominal size | 200 |
Accessories | Without accessories |
Attachments (control components) | VARYCONTROL Universal controller; static transducer; analogue control; safe position with spring return |
Operating mode | Variable operation |
Signal voltage range | 2 – 10 V DC |
Volume flow rate | 500 – 1200 [m³/h] |
Damper blade position | Power off to open (Normally/ Open) |
TVR | – | D | – | A2 | – | FL | / | 160 | / | G2 | / | TUNF | / | RS | / | M | / | 0 | / | UMZ | / | … | / | NC |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | ||||||||||||
TVR VAV terminal unit
2 Acoustic cladding
No entry required: None
D With acoustic cladding
3 Material
No entry: galvanised sheet steel
P1 Powder-coated RAL 7001, silver grey
A2 Stainless steel construction
4 Duct connection
No entry: push-fit, suitable for ducts according to EN
1506; with groove for optional lip seal
FL Flange both ends (not for TVR-D-P1)
5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400
6 Accessories
No entry required: None
D2 Double lip seal both sides
G2 Matching flanges both sides
7 Attachments (control components)
TROX UNIVERSAL controller with
TUN Actuator (150 s)
TUNF Spring return actuator (150 s)
TUS Fast-running actuator (3 s)
TUSD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
8 Equipment function
Room control
RS Supply air control (Room Supply)
RE Extract air control (Room Extract)
9 Volume flow rate setting
M Master (RMF function)S Slave
F Constant flow rate controller
10 Signal voltage range
0 0 – 10 V DC
2 2 – 10 V DC
11 Expansion of attachments
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V
AC, provides uninterruptible power supply (UPS)
Option 2: Digital communication interface
No entry required: None
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP: EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
Option 3: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO with solenoid valve
12 Operating values [m³/h or l/s] Master (RMF function)qᵥmin: minimum volume flow rateqᵥmax: maximum volume flow rateqᵥconst_Supply air: constant supply airqᵥconst_Extract air: constant extract airqᵥDiff: Supply air/extract air difference Constant valueqᵥconst: constant volume flow rate SlaveNo entry required
13 Damper blade position
Only spring return actuators
NO Power off to OPEN
NC Power off to CLOSE
Useful additions
Room control panel
BE-LCD 40-character display
Type | TVR |
Acoustic cladding | Without acoustic cladding |
Material | Galvanised sheet steel |
Duct connection | Flanges on both ends |
Nominal size [mm] | 250 |
Accessories | Without accessories |
Attachments (control components) | TROX UNIVERSAL controller with spring return actuator (150s) |
Equipment function | Extract air controller (Room Extract) |
Operating mode | Room master or single controller, variable setpoint value |
Signal voltage range | 0 – 10 V DC |
Expansion modules | 24 V AC/DC supply, without digital communication interface, without automatic zero point correction |
Operating values for factory setting | qvmin = 306 m³/h qvmax = 2205 m³/h |
Damper blade position | Power off to close (Normally Closed) |
TVR | – | D | – | A2 | – | FL | / | 160 | / | G2 | / | XF4 | / | PDS | / | V | / | 0 | / | 300-500 [Pa] | / | NO |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 |
For duct pressure control, enter the differential pressure [Pa] as an absolute value
∆pconst(with operating mode F)Type | TVR |
Acoustic cladding | Without acoustic cladding |
Material | Galvanised sheet steel |
Duct connection | Flanges on both ends |
Nominal size [mm] | 250 |
Accessories | Matching flanges for both ends |
Attachments (control components) | VARYCONTROL Universal controller for duct pressure; analogue interface |
Equipment function | Duct pressure control, supply air (Pressure Duct Supply) |
Operating mode | Constant value mode |
Signal voltage range | 0 – 10 V DC |
Operating value | 450 [Pa] |
Damper blade position | Power off to close (Normally Closed) |
TVR | – | D | – | … | – | FL | / | 160 | / | G2 | / | TUNF | / | PRS | / | MFP | / | 0 | / | UMZ | / | … | / | NC |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 |
D With acoustic cladding
3 Nominal size [mm]
125160200250315400
4 AccessoriesNo entry required: None
D1 Double lip seal
5 Attachments (control components)
For example
XF0 Compact controller for duct pressure
XF4 Universal controller for duct pressure (VARYCONTROL)
6 Equipment function/installation location
PDS Duct pressure control, supply air
PRS Room pressure control, supply air
7 Operating mode
F Constant value (a setpoint value)
V Variable (setpoint value range)
8 Signal voltage range
For the actual and setpoint value signals
0 0 – 10 V DC
2 2 – 10 V DC
9 Operating values for factory setting
Differential pressure [Pa]
For duct pressure control, enter the differential pressure [Pa] as an absolute value
Δpconst (in operating mode F)
Δpmin – Δpmax (in operating mode V)
10 Damper blade position
Only spring return actuators
NO Power off to OPEN
NC Power off to CLOSE
Nominal size | 160 mm |
Accessories | Double lip seal (one end) |
Attachments (control components) | VARYCONTROL Universal controller for duct pressure |
Equipment function | Duct pressure control, supply air |
Operating mode | Constant value |
Signal voltage range | 2 – 10 V DC |
Operating value | 470 Pa |
Damper blade position | Power off to OPEN |
TVZ | – | D | / | 160 | / | D1 | / | TUNF | / | PRS | / | MFP | / | 0 | / | UMZ | / | … | / | NC |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | ||||||||||
2 Acoustic cladding
No entry required: None
D With acoustic cladding
3 Nominal size [mm]
125160200250315400
4 Accessories
No entry required: None
D1 Double lip seal
5 Attachments (control components)
TROX UNIVERSAL controller with
TUN Actuator (150 s)
TUNF Spring return actuator (150 s)
TUS Fast-running actuator (3 s)
TUSD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
6 Equipment functionY
Pressure control
PRS Room pressure control, supply air
PDS Duct pressure control, supply air
7 Differential pressure setting
MFP Master, constant pressure control
MVP Master, variable differential pressure control
SFP Slave, constant pressure control
SVP Slave, variable differential pressure control
8 Signal voltage range
0 0 - 10 V DC
2 2 - 10 V DC
9 Expansion modules
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS)
Option 2: Digital communication interface
No entry required: None
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
Option 3: Volume flow rate measurement
No entry required: None
V EM-V Volume flow rate measurement for differential pressure control
Option 4: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO solenoid valve (only with V)
10 Operating values for factory setting
Pressure [Pa], volume flow rate [m³/h or l/s]
Slave SVP
Δpmin: minimum differential pressure
Δpmax: maximum differential pressure Slave SFP
Δpconst: Constant differential pressure Master MFP and MVP like Slave, but additionally
qᵥmin: minimum volume flow rate
qᵥmax: maximum volume flow rate
qᵥconst_CLOSED: constant supply air
qᵥconst_Exhaust: constant extract air
qᵥDiff: Supply air/extract air difference
11 Damper blade position
Only spring return actuators
NO Power off to OPEN
NC Power off to CLOSE
Useful additions Room control panel
BE-LCD 40-character display
The differential pressure transducer required for room or duct pressure control has to be ordered separately, e.g.
PT-699 for room pressure control
PT-699-DUCT for duct pressure control, including tube and pressure tap
Order example: TVZ/200/TUS/PRS/MVP/0/B/-10/-60/ 600/1250/ 0/ 0/-100
Nominal size | 200 mm |
Attachments (control components) | TROX UNIVERSAL controller, fast-running actuator (3 s) |
Equipment function | Room pressure control, supply air |
Differential pressure setting | Master, variable differential pressure control |
Signal voltage range | 0 – 10 V DC |
Expansion modules | with expansion module EM-BAC-MODBACnet MS/TP interface card |
Operating values | Δpmin = -10 Pa, Δpmax = -60 Paqᵥmin = 600 m³/h,qᵥmax = 1250 m³/hqᵥconst_Supply air = 0 m³/h, qᵥconst_Extract air = 0 m³/hqᵥDiff = - 100 m³/h |
TVZ | – | D | / | 160 | / | D1 | / | ELAB | / | S | / | RS | / | UMZ | / | LAB | / | … |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 9 | 10 | 11 |
3 Nominal size [mm]
125160200250315400
4 Accessories
No entry required: None
D1 Double lip seal
5 Attachments (control components)
ELAB EASYLAB controller TCU3
6 Actuators
S Fast-running actuator (3 s)
SD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
7 Equipment function Room control
RS Supply air control (Room Supply)
PC Differential pressure control (Pressure Control)
9 Expansion modules
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS)
Option 2: Digital communication interface
No entry required: None
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
Option 3: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO
Solenoid valve for automatic zero point correction
10 Additional functions
Without room management function
LAB Extract air led system (laboratories)
CLR Supply air led system (clean rooms)
With room management function
LAB-RMF Extract air led system
CLR-RMF Supply air led system
11 Operating values for factory setting
(only required when room management function is active)
Volume flow rate [m³/h or l/s], pressure [Pa]
Total extract air/supply air of room:
qv1: Standard mode
qv2: reduced operation
qv3: increased operation
qv4: constant supply air
qv5: constant extract air
qv6: Supply air/extract air difference
ΔpSet: Setpoint pressure (only with differential pressure control)
Useful additions
Room control panel (only for devices with RMF)
BE-LCD 40-character display
The differential pressure transducer required for room pressure control (equipment function) has to be ordered separately, e.g.
PT-699 Measuring range ±50 Pa or ±100 Pa
PT-GB604 Measuring range ±100 Pa
Acoustic cladding | without |
Nominal size | 200 mm |
Attachments (control components) | EASYLAB controller TCU3 with fast-running actuator (3 s) |
Actuator | Fast-running actuator (3 s), with digital communication interface |
Equipment function | Supply air control (Room Supply) |
Additional function | Supply air led system with room management function |
Operating values | qv1 = 3500 m³/hqv2 = 1000 m³/hqv3 = 5000 m³/hqv4 = 250 m³/hqv5 = 0qv6 = -150 m³/h |
TVZ | – | D | / | 160 | / | D1 | / | ELAB | / | S | / | SC | – | E0 | / | UMZ | / | … | ||||||
Valvula vav/ | ||||||||||||||||||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | ||||||||||||
TVR VAV terminal unit
2 Acoustic cladding
No entry required: None
D With acoustic cladding
3 Material
No entry: galvanised sheet steel
P1 Powder-coated RAL 7001, silver grey
A2 Stainless steel construction
4 Duct connection
No entry: push-fit, suitable for ducts according to EN
1506; with groove for optional lip seal
FL Flange both ends (not for TVR-D-P1)
5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400
6 Accessories
No entry required: None
D2 Double lip seal both sides
G2 Matching flanges both sides
7 Attachments (control components)
TROX UNIVERSAL controller with
TUN Actuator (150 s)
TUNF Spring return actuator (150 s)
TUS Fast-running actuator (3 s)
TUSD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
8 Equipment function
Room control
RS Supply air control (Room Supply)
RE Extract air control (Room Extract)
9 Volume flow rate setting
M Master (RMF function)S Slave
F Constant flow rate controller
10 Signal voltage range
0 0 – 10 V DC
2 2 – 10 V DC
11 Expansion of attachments
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V
AC, provides uninterruptible power supply (UPS)
Option 2: Digital communication interface
No entry required: None
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP: EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
Option 3: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO with solenoid valve
12 Operating values [m³/h or l/s] Master (RMF function)qᵥmin: minimum volume flow rateqᵥmax: maximum volume flow rateqᵥconst_Supply air: constant supply airqᵥconst_Extract air: constant extract airqᵥDiff: Supply air/extract air difference Constant valueqᵥconst: constant volume flow rate SlaveNo entry required
13 Damper blade position
Only spring return actuators
NO Power off to OPEN
NC Power off to CLOSE
Useful additions
Room control panel
BE-LCD 40-character display
Type | TVR |
Acoustic cladding | Without acoustic cladding |
Material | Galvanised sheet steel |
Duct connection | Flanges on both ends |
Nominal size [mm] | 250 |
Accessories | Without accessories |
Attachments (control components) | TROX UNIVERSAL controller with spring return actuator (150s) |
Equipment function | Extract air controller (Room Extract) |
Operating mode | Room master or single controller, variable setpoint value |
Signal voltage range | 0 – 10 V DC |
Expansion modules | 24 V AC/DC supply, without digital communication interface, without automatic zero point correction |
Operating values for factory setting | qvmin = 306 m³/h qvmax = 2205 m³/h |
Damper blade position | Power off to close (Normally Closed) |
TVR | – | D | – | A2 | – | FL | / | 160 | / | G2 | / | XF4 | / | PDS | / | V | / | 0 | / | 300-500 [Pa] | / | NO |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 |
For duct pressure control, enter the differential pressure [Pa] as an absolute value
∆pconst(with operating mode F)Type | TVR |
Acoustic cladding | Without acoustic cladding |
Material | Galvanised sheet steel |
Duct connection | Flanges on both ends |
Nominal size [mm] | 250 |
Accessories | Matching flanges for both ends |
Attachments (control components) | VARYCONTROL Universal controller for duct pressure; analogue interface |
Equipment function | Duct pressure control, supply air (Pressure Duct Supply) |
Operating mode | Constant value mode |
Signal voltage range | 0 – 10 V DC |
Operating value | 450 [Pa] |
Damper blade position | Power off to close (Normally Closed) |
TVR | – | D | – | … | – | FL | / | 160 | / | G2 | / | TUNF | / | PRS | / | MFP | / | 0 | / | UMZ | / | … | / | NC |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | ||||||||||||
2 Acoustic cladding
No entry: none
D With acoustic cladding
3 Material
No entry: galvanised sheet steel
P1 Powder-coated RAL 7001, silver grey
A2 Stainless steel construction
4 Duct connection
No entry: push-fit, suitable for ducts according to EN 1506; with groove for optional lip seal
FL Flanges both ends (not for TVR-D-P1)
5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400
6 Accessories
No entry: without accessories
D2 Double lip seal both ends
G2 Matching flanges for both ends
7 Attachments (control components)
TROX UNIVERSAL controller with
TUN with actuator (150 s)
TUNF with spring return actuator (150 s)
TUS with fast-running actuator (3 s)
TUSD with fast-running actuator (3 s) and digital communication interface (TROX HPD)
8 Equipment function
PDS Duct pressure controller – supply air (Pressure Duct Supply)
PDE Duct pressure controller – extract air (Pressure Duct Extract)
PRS Room pressure controller – supply air (Pressure Room Supply)
PRE Room pressure controller – extract air (Pressure Room Extract)
9 Differential pressure setting
MFP Room master or single controller, constant pressure setpoint value
MVP Room master or single controller, variable pressure setpoint value
With room solutions
SFP Slave, constant pressure setpoint
SVP Slave, variable pressuure setpoint
10 Signal voltage range
For the actual and setpint value signals
0 0 – 10 V DC
2 2 – 10 V DC
11 Expansion modules
Option 1: Power supply
No entry required: 24 V AC/DC
T With EM-TRF for 230 V AC mains supply
U With EM-TRF-USV (including battery pack) for uninterruptible 230 V AC power supply (UPS)
Option 2: Digital communication interface
No entry: without digital communication interface
B With EM-BAC-MOD-01 for BACnet MS/TP
M With EM-BAC-MOD-01 for Modbus RTU
I With EM-IP: EM-IP for BACnet/IP, Modbus/IP and web server
R With EM-IP (including real time clock, RTC) for BACnet IP, Modbus IP and web server
Option 3: Volume flow rate measurement
No entry: without volume flow rate measurement
V With EM-V for volume flow rate measurement with the differential pressure controller
Option 4: Automatic zero point correction
No entry: no automatic zero pint correction
Z With EM-AUTOZERO solenoid valve for automatic zero pint correction (only togehter with EM-V)
12 Operating values for factory setting
Volume flow rate[m³/h or l/s], pressure [Pa]
For operating mode MFP or SFP
Δpconst: Constant differential pressure
For operating mode MVP or SVP
Δpmin: minimum differential pressure
Δpmax: maximum differential pressure
Other parameters for operating modes MFP and MVP
Only relevant for the room master as part of a room solution; for single controllers enter 0
qᵥmin: minimum volume flow rate (room value)
qᵥmax: maximum volume flow rate (room value)
qᵥconst_Supply air: constant supply air (room value)
qᵥconst_Extract air: constant extract air (room value)
qᵥDiff: Supply air/extract air difference (room value)
Please note
For more information on room solutions with several TROX UNIVERSAL controllers connected with plug and play and for order examples please refer to the product datasheet
13 Damper blade position
Only with spring return actuators
NO Power off to open (Normally Open)
NC Power off to close (Normally Closed)
Useful additions
Differential pressure transducers required for room or duct pressure control have to be ordered separately or provided by others, e.g.
PT-699 Differential pressure transducer for room pressure control
PT-699-DUCT Differential pressure transducers for duct pressure control, including pressure measurement kit
Room control panel
Optional room control panel
BE-LCD 40-character display
Order example: TVR-D-FL/160/G2/TUNF/PRS/MFP/0/UMZ/250[Pa]/NC
Type | TVR |
Acoustic cladding | Without acoustic cladding |
Material | Galvanised sheet steel |
Duct connection | Push-fit, suitable for ducts according to EN 1506; with groove for optional lip seal |
Nominal size [mm] | 160 |
Accessories | Matching flanges for both ends |
Attachments (control components) | TROX UNIVERSAL controller with fast-running actuator, analogue interface |
Equipment function | Room pressure contoller - supply air (Pressure Room Supply) |
Operating mode | Room master or single controller, constant pressure setpoint value |
Signal voltage range | 0 – 10 V DC |
Expansion modules | With EM-TRF-USV (including battery pack) for uninterruptible 230 V AC power supply (UPS) With EM-BAC-MOD for Modbus RTU Without volume flow rate measurement With EM-AUTOZERO solenoid valve for automatic zero pint correction |
Damper blade position | 250 [Pa] |
Operating values for factory setting | Power off to close (Normally Closed) |
TVR | – | D | – | … | – | FL | / | 160 | / | G2 | / | ELAB | / | S | / | RS | / | UMZ | / | LAB | / | … |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 |
D With acoustic cladding
3 Nominal size [mm]
125160200250315400
4 AccessoriesNo entry required: None
D1 Double lip seal
5 Attachments (control components)
For example
XF0 Compact controller for duct pressure
XF4 Universal controller for duct pressure (VARYCONTROL)
6 Equipment function/installation location
PDS Duct pressure control, supply air
PRS Room pressure control, supply air
7 Operating mode
F Constant value (a setpoint value)
V Variable (setpoint value range)
8 Signal voltage range
For the actual and setpoint value signals
0 0 – 10 V DC
2 2 – 10 V DC
9 Operating values for factory setting
Differential pressure [Pa]
For duct pressure control, enter the differential pressure [Pa] as an absolute value
Δpconst (in operating mode F)
Δpmin – Δpmax (in operating mode V)
10 Damper blade position
Only spring return actuators
NO Power off to OPEN
NC Power off to CLOSE
Nominal size | 160 mm |
Accessories | Double lip seal (one end) |
Attachments (control components) | VARYCONTROL Universal controller for duct pressure |
Equipment function | Duct pressure control, supply air |
Operating mode | Constant value |
Signal voltage range | 2 – 10 V DC |
Operating value | 470 Pa |
Damper blade position | Power off to OPEN |
TVZ | – | D | / | 160 | / | D1 | / | TUNF | / | PRS | / | MFP | / | 0 | / | UMZ | / | … | / | NC |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | ||||||||||
2 Acoustic cladding
No entry required: None
D With acoustic cladding
3 Nominal size [mm]
125160200250315400
4 Accessories
No entry required: None
D1 Double lip seal
5 Attachments (control components)
TROX UNIVERSAL controller with
TUN Actuator (150 s)
TUNF Spring return actuator (150 s)
TUS Fast-running actuator (3 s)
TUSD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
6 Equipment functionY
Pressure control
PRS Room pressure control, supply air
PDS Duct pressure control, supply air
7 Differential pressure setting
MFP Master, constant pressure control
MVP Master, variable differential pressure control
SFP Slave, constant pressure control
SVP Slave, variable differential pressure control
8 Signal voltage range
0 0 - 10 V DC
2 2 - 10 V DC
9 Expansion modules
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS)
Option 2: Digital communication interface
No entry required: None
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
Option 3: Volume flow rate measurement
No entry required: None
V EM-V Volume flow rate measurement for differential pressure control
Option 4: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO solenoid valve (only with V)
10 Operating values for factory setting
Pressure [Pa], volume flow rate [m³/h or l/s]
Slave SVP
Δpmin: minimum differential pressure
Δpmax: maximum differential pressure Slave SFP
Δpconst: Constant differential pressure Master MFP and MVP like Slave, but additionally
qᵥmin: minimum volume flow rate
qᵥmax: maximum volume flow rate
qᵥconst_CLOSED: constant supply air
qᵥconst_Exhaust: constant extract air
qᵥDiff: Supply air/extract air difference
11 Damper blade position
Only spring return actuators
NO Power off to OPEN
NC Power off to CLOSE
Useful additions Room control panel
BE-LCD 40-character display
The differential pressure transducer required for room or duct pressure control has to be ordered separately, e.g.
PT-699 for room pressure control
PT-699-DUCT for duct pressure control, including tube and pressure tap
Order example: TVZ/200/TUS/PRS/MVP/0/B/-10/-60/ 600/1250/ 0/ 0/-100
Nominal size | 200 mm |
Attachments (control components) | TROX UNIVERSAL controller, fast-running actuator (3 s) |
Equipment function | Room pressure control, supply air |
Differential pressure setting | Master, variable differential pressure control |
Signal voltage range | 0 – 10 V DC |
Expansion modules | with expansion module EM-BAC-MODBACnet MS/TP interface card |
Operating values | Δpmin = -10 Pa, Δpmax = -60 Paqᵥmin = 600 m³/h,qᵥmax = 1250 m³/hqᵥconst_Supply air = 0 m³/h, qᵥconst_Extract air = 0 m³/hqᵥDiff = - 100 m³/h |
TVZ | – | D | / | 160 | / | D1 | / | ELAB | / | S | / | RS | / | UMZ | / | LAB | / | … |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 9 | 10 | 11 |
3 Nominal size [mm]
125160200250315400
4 Accessories
No entry required: None
D1 Double lip seal
5 Attachments (control components)
ELAB EASYLAB controller TCU3
6 Actuators
S Fast-running actuator (3 s)
SD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
7 Equipment function Room control
RS Supply air control (Room Supply)
PC Differential pressure control (Pressure Control)
9 Expansion modules
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS)
Option 2: Digital communication interface
No entry required: None
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
Option 3: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO
Solenoid valve for automatic zero point correction
10 Additional functions
Without room management function
LAB Extract air led system (laboratories)
CLR Supply air led system (clean rooms)
With room management function
LAB-RMF Extract air led system
CLR-RMF Supply air led system
11 Operating values for factory setting
(only required when room management function is active)
Volume flow rate [m³/h or l/s], pressure [Pa]
Total extract air/supply air of room:
qv1: Standard mode
qv2: reduced operation
qv3: increased operation
qv4: constant supply air
qv5: constant extract air
qv6: Supply air/extract air difference
ΔpSet: Setpoint pressure (only with differential pressure control)
Useful additions
Room control panel (only for devices with RMF)
BE-LCD 40-character display
The differential pressure transducer required for room pressure control (equipment function) has to be ordered separately, e.g.
PT-699 Measuring range ±50 Pa or ±100 Pa
PT-GB604 Measuring range ±100 Pa
Acoustic cladding | without |
Nominal size | 200 mm |
Attachments (control components) | EASYLAB controller TCU3 with fast-running actuator (3 s) |
Actuator | Fast-running actuator (3 s), with digital communication interface |
Equipment function | Supply air control (Room Supply) |
Additional function | Supply air led system with room management function |
Operating values | qv1 = 3500 m³/hqv2 = 1000 m³/hqv3 = 5000 m³/hqv4 = 250 m³/hqv5 = 0qv6 = -150 m³/h |
TVZ | – | D | / | 160 | / | D1 | / | ELAB | / | S | / | SC | – | E0 | / | UMZ | / | … |