8 Equipment function
Room control
RS Supply air controller (Room Supply)
RE Extract air controller (Room Extract).
M Room master for single controller, variable setpoint value
S Slave controller (only with room solutions)
Option 1: Power supply
No entry: 24 V AC/DC
T With EM-TRF for 230 V AC mains supply
U With EM-TRF-USV (including battery pack for uninterruptible 230 V AC power supply (UPS)
Option 2: Digital communication interface
No entry: without communication interface
B With EM-BAC-MOD for VACnet MS/TP
M With EM-BAC-MOD for Modbus RTU
I With EM-IP for BACnet IP, Modbus IP and web server
R With EM-IP (including real time clock, RTC) for BACnet IP, Modbus IP and web server
Option 3: Automatic zero point correction
No entry: no zero point correction
Z With EM-AUTOZERO solenoid valve for automatic zero point correction
12 Operating values for factory setting
Volume flow rate [m³/h or l/s]
For operating mode F
qᵥconst: constant volume flow rate1, 2
Other parameters are only relevant for the room master as part
of a room solution3; for single controllers enter 0
qᵥconst_sup: constant supply air (room value)
qᵥconst_ext: constant extract air (room value)
qᵥdiff: supply air/extract air difference (room value)
For operating mode M
qᵥmin: minimum volume flow rate1, 2
qᵥmax: maximum volume flow rate1, 2
Other parameters are only relevant for the room master as part
of a room solution3; for single controllers enter 0
qᵥconst_sup: constant supply air (room value)
qᵥconst_ext: constant extract air (room value)
qᵥdiff: supply air/extract air difference (room value)
For operating mode S
No parameters are required for the slave controller; all entries
have to be made on the room master
For volume flow rate operating values please note:
1 Single controller: qᵥmin, qᵥmax or qᵥconst apply to the controller
2 Room solutions: qᵥmin, qᵥmax, qᵥconst apply to the room
3 For more information on room solutions with several TROX
UNIVERSAL controllers connected with plug and play and for
order examples please refer to the product datasheet
Usefull additions
Optional room control panel
BE-LCD with 40-character display
Type | TVR |
Acoustic cladding | Without acoustic cladding |
Material | Galvanised sheet steel |
Duct connection | Push-fit, suitable for ducts according to EN 1506, with groove for optional lip seal |
Nominal size | 200 |
Accessories | Without accessories |
Attachments (control components) | VARYCONTROL Universal controller; static transducer; analogue control; safe position with spring return |
Operating mode | Variable operation |
Signal voltage range | 2 – 10 V DC |
Volume flow rate | 500 – 1200 [m³/h] |
Damper blade position | Power off to open (Normally/ Open) |
TVR | – | D | – | A2 | – | FL | / | 160 | / | G2 | / | TUNF | / | RS | / | M | / | 0 | / | UMZ | / | … | / | NC |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | ||||||||||||
TVR VAV terminal unit
2 Acoustic cladding
No entry required: None
D With acoustic cladding
3 Material
No entry: galvanised sheet steel
P1 Powder-coated RAL 7001, silver grey
A2 Stainless steel construction
4 Duct connection
No entry: push-fit, suitable for ducts according to EN
1506; with groove for optional lip seal
FL Flange both ends (not for TVR-D-P1)
5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400
6 Accessories
No entry required: None
D2 Double lip seal both sides
G2 Matching flanges both sides
7 Attachments (control components)
TROX UNIVERSAL controller with
TUN Actuator (150 s)
TUNF Spring return actuator (150 s)
TUS Fast-running actuator (3 s)
TUSD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
8 Equipment function
Room control
RS Supply air control (Room Supply)
RE Extract air control (Room Extract)
9 Volume flow rate setting
M Master (RMF function)S Slave
F Constant flow rate controller
10 Signal voltage range
0 0 – 10 V DC
2 2 – 10 V DC
11 Expansion of attachments
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V
AC, provides uninterruptible power supply (UPS)
Option 2: Digital communication interface
No entry required: None
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP: EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
Option 3: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO with solenoid valve
12 Operating values [m³/h or l/s] Master (RMF function)qᵥmin: minimum volume flow rateqᵥmax: maximum volume flow rateqᵥconst_Supply air: constant supply airqᵥconst_Extract air: constant extract airqᵥDiff: Supply air/extract air difference Constant valueqᵥconst: constant volume flow rate SlaveNo entry required
13 Damper blade position
Only spring return actuators
NO Power off to OPEN
NC Power off to CLOSE
Useful additions
Room control panel
BE-LCD 40-character display
Type | TVR |
Acoustic cladding | Without acoustic cladding |
Material | Galvanised sheet steel |
Duct connection | Flanges on both ends |
Nominal size [mm] | 250 |
Accessories | Without accessories |
Attachments (control components) | TROX UNIVERSAL controller with spring return actuator (150s) |
Equipment function | Extract air controller (Room Extract) |
Operating mode | Room master or single controller, variable setpoint value |
Signal voltage range | 0 – 10 V DC |
Expansion modules | 24 V AC/DC supply, without digital communication interface, without automatic zero point correction |
Operating values for factory setting | qvmin = 306 m³/h qvmax = 2205 m³/h |
Damper blade position | Power off to close (Normally Closed) |
TVR | – | D | – | A2 | – | FL | / | 160 | / | G2 | / | XF4 | / | PDS | / | V | / | 0 | / | 300-500 [Pa] | / | NO |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | ||||||||||||
Nominal size | 125 mm |
Attachments (control components) | Controller TROX UNIVERSAL; fast-running actuator (3 s) with digital communication interface (TROX HPD) |
Equipment function | Room pressure control, extract air |
Effective pressure setting | Slave, constant pressure control |
Signal voltage characteristics | 0 – 10 V DC |
Extension of attachments | with expansion module EM-V, Volume flow rate measurement for differential pressure control |
Operating values | Δpconst = 20 Pa |
TVA | – | D | / | 160 | / | D1 | / | ELAB | / | S | / | RE | / | UMZ | / | LAB | / | … |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 9 | 10 | 11 |
VAV terminal unit, extract air
2 Acoustic cladding
No entry required: None
D With acoustic cladding
3 Nominal size [mm]
125
160
200
250
315
400
4 Accessories
No entry required: None
D1 Double lip seal (one side)
5 Attachments (control components)
ELAB EASYLAB controller TCU3
6 Actuators
S Fast-running actuator (3 s)
SD Fast-running actuator (3 s), with digital communication interface (TROX HPD)
7 Equipment function
Room control
RE Extract air control (Room Supply)
PC Differential pressure control (Pressure Control)
9 Expansion modules
Option 1: Power supply
Option 2: Digital communication interface
No entry required: None
B EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock
Option 3: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO Solenoid valve for automatic zero point correction
10 Additional functions
Without room management function11 Operating values for factory setting
Volume flow rates [m3/h, l/s], pressure [Pa](only required when room management function is active)
Total extract air/supply air of room
qv1: Standard mode
qv2: Reduced operation
qv3: Increased operation
qv4: Constant supply air
qv5: Constant extract air
qv6: Supply air/extract air difference
Δpset: Setpoint pressure (only with differential pressure control)
Useful additions
Room control panel (only for devices with RMF)
BE-LCD 40-character display
Acoustic cladding | None |
Nominal size | 200 mm |
Attachments (control component) | EASYLAB controller TCU3 |
Actuator | Fast-running actuator (3 s) |
Equipment function | Extract air control (Room Exhaust) |
Expansion modules | With expansion module EM-TRF Transformer for 230 V AC supply With expansion module EM-AUTOZERO solenoid valve for automatic zero point correction |
Additional function | Supply air led system (clean rooms) Room management function not activated |
TVA | – | D | / | 160 | / | D1 | / | ELAB | / | S | / | EC | – | E0 | / | UMZ | / | … | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
ATEX-compliant parts and units TVR-EXFor the control of variable air volume flows in potentially explosive atmospheres (ATEX)Circular VAV terminal units for variable air volume systems, approved and certified for potentially explosive atmospheres (ATEX)
Optional equipment and accessories
General informationApplication
Special features
Nominal sizes
Classification Electronic control: Equipment group II
Pneumatic control: Equipment group II
Parts and characteristics
Attachments
Accessories
Technical data
Useful additions
Construction features
Materials and surfaces
Standards and guidelines
Maintenance
Electronic control:
Technical informationFunction, Technical data, Quick sizing, Specification text, Order code, Related Products
Schematic illustration of the TVR-Ex with electronic control ① Auxiliary switch The VAV terminal unit is fitted with a differential pressure sensor for measuring the volume flow rate. The control components (attachments) include a differential pressure transducer that transforms the differential pressure (effective pressure) into an electric signal, a controller, and an actuator. For most applications, the setpoint value comes from a room temperature controller which is installed outside of the potentially explosive atmosphere. The controller compares the actual value with the setpoint value and alters the control signal of the damper actuator if there is a difference between the two values. The connections for the supply voltage and for the voltage signals are made in a terminal box that is suitable for use in potentially explosive atmospheres.
Electronic control with attachment S1S, S1F, S1X or S1Y
For the latest information on the electronic attachments please refer to the technical data in the manufacturer's product documentation: Electronic control with attachment TES, TEF, TEX or TEY
Controller TCU3 (TROX)
Differential pressure transducer (Schischek)
Actuator/spring return actuator (Schischek)
The information given here is just to give you an idea.
Pneumatic
Quick sizing tables provide a good overview of the room sound pressure levels that can be expected. Approximate intermediate values can be interpolated. Precise intermediate values and spectral data can be calculated with our Easy Product Finder design program. The first selection criteria for the nominal size are the actual volume flow rates qᵥmin and qᵥmax. The quick sizing tables are based on generally accepted attenuation levels. If the sound pressure level exceeds the required level, a larger air terminal unit and/or a silencer is required. Volume flow rate ranges Sufficient duct pressure must be ensured for all operating conditions and for all control units. The measurement points for fan speed control must be selected accordingly. The volume flow rates given for VAV terminal units depend on the nominal size and on the control component (attachment) that is installed. The tables give the minimum and maximum values for a VAV terminal unit. Some control components may only have a limited volume flow rate range. This applies in particular to control components with a static differential pressure transducer. For volume flow rate ranges for all control components refer to our Easy Product Finder design program. TVR-Ex – electronic, volume flow rate ranges and minimum differential pressures
① TVR-Ex
TVR-Ex – pneumatic, volume flow rate ranges and minimum differential pressures
① TVR-Ex
TVR-Ex, electronic, sound pressure level at differential pressure 150 Pa
① TVR-Ex TVR-Ex, pneumatic, sound pressure level at differential pressure 150 Pa
① TVR-Ex Specification text VAV terminal units for variable and constant air volume systems in potentially explosive atmospheres, suitable for supply or extract air, available in 6 nominal sizes. High control accuracy (even with upstream bend R = 1D). Ready-to-commission unit which consists of the mechanical parts, the electronic control components, and parts for equipotential bonding and for use in potentially explosive atmospheres. Each unit contains an averaging differential pressure sensor for volume flow rate measurement and a damper blade. Factory mounted control components complete with wiring and tubing. Special features
Materials and surfaces
Construction
Technical data
Attachments Variable volume flow control with electronic controller to connect an external control signal; actual value signal can be integrated into the central BMS.
Sizing data
Air-regenerated noise
Case-radiated noise
TVR-Ex with ATEX control component Universal
TVR-Ex VAV terminal unit for use in potentially explosive atmospheres 2 Material No entry: galvanised sheet steel P1 Inner duct powder-coated, silver grey (RAL 7001) A2 Inner duct in stainless steel 3 Nominal size [mm] 125, 160, 200, 250, 315, 400 4 Attachments (control components) Electronic control S1S ExReg controller and actuator S1F ExReg controller and spring return actuator S1X ExReg controller, actuator and auxiliary switch S1Y ExReg controller, spring return actuator and auxiliary switch 5 Operating mode V Variable operation (adjustable setpoint value range) 6 Signal voltage range For the actual and setpoint value signals 0 0 – 10 V DC 2 2 – 10 V DC 7 Operating values for factory setting Volume flow rate [m³/h or l/s] qᵥmin – qᵥmax 8 Damper blade position Only with spring return actuators (S1F and S1Y) NO Power off to open (Normally Open) NC Power off to close (Normally Closed) Order example: TVR-Ex-P1/125/S1F/V0/200-400[m³/h]/NO
TVR-Ex with ATEX control component based on TCU3
TVR-Ex VAV terminal unit for use in potentially explosive atmospheres 2 Material No entry: galvanised sheet steel P1 Inner duct powder-coated, silver grey (RAL 7001) A2 Inner duct in stainless steel 3 Nominal size [mm] 125, 160, 200, 250, 315, 400 4 Attachments (control components) Electronic control (controller outside of the Ex zone) TES TCU3 controller and actuator TEF TCU3 controller and spring return actuator TEX TCU3 controller, actuator and auxiliary switch TEY TCU3 controller, spring return actuator and auxiliary switch 5 Equipment function Single operation SC Single controller – supply air (Supply Controller) EC Single controller – extract air (Extract Controller) 6 External volume flow rate default setting E0 Variable, signal voltage range 0 – 10 V DC E2 Variable, signal voltage range 2 – 10 V DC 2P 2 switching steps (for one switch contact, by others) 3P 3 switching steps (for two switch contacts, by others) F Constant value mode, one setpoint value (no external switch contact) 7 Expansion modules Option 1: Power supply No entry: 24 V AC/DC T With EM-TRF for 230 V AC mains supply U With EM-TRF-USV (including battery pack) for uninterruptible 230 V AC power supply (UPS) Option 2: Digital communication interface No entry: without digital communication interface B With EM-BAC-MOD for BACnet MS/TP M With EM-BAC-MOD for Modbus RTU I With EM-IP for BACnet IP, Modbus IP and web server R With EM-IP (including real time clock, RTC) for BACnet IP, Modbus IP and web server 8 Operating values for factory setting Volume flow rate [m3/h or l/s] Depends on external volume flow rate setting E0: qᵥmin – qᵥmax E2: qᵥmin – qᵥmax 2P: qᵥ1/qᵥ2 3P: qᵥ1/qᵥ2/qᵥ3 F: qᵥ1 9 Damper blade position Only with spring return actuators (TEF and TEY) NO Power off to open (Normally Open) NC Power off to close (Normally Closed) Order example: TVR-Ex-P1/160/TEF/EC-E0/M/200-400[m3/h]/NO
TVR-Ex with pneumatic attachments
1 Type TVR VAV terminal unit 2 Acoustic cladding 3 Material 4 Duct connection 5 Nominal size [mm] 6 Accessories 7 Attachments (control components) 8 Equipment function 9 Volume flow rate setting 10 Signal voltage range 11 Expansion of attachments 12 Operating values [m³/h or l/s] Master (RMF function)qᵥmin: minimum volume flow rateqᵥmax: maximum volume flow rateqᵥconst_Supply air: constant supply airqᵥconst_Extract air: constant extract airqᵥDiff: Supply air/extract air difference Constant valueqᵥconst: constant volume flow rate SlaveNo entry required 13 Damper blade position Useful additions Order example: TVR-FL/250/TUNF/RE/M0/306-2205-0-0-0 [m³/h] /NC
Order code for differential pressure control (with VARYCONTROL attachment)
TVRVAV terminal unit 2 Acoustic cladding No entry: none D With acoustic cladding 3 Material No entry: galvanised sheet steel P1Powder-coated RAL 7001 (silver grey) A2Stainless steel construction 4 Duct connection No entry: push-fit, suitable for ducts according to EN 1506; with groove for optional lip seal FLFlanges both ends (not for TVR-D-P1) 5 Nominal size [mm] 100, 125, 160, 200, 250, 315, 400 6 Accessories No entry: without accessories D2Double lip seal both ends G2Matching flanges for both ends 7 Attachments (control components) For example XF0Compact controller for duct pressure XF4Universal controller for duct pressure (VARYCONTROL) 8 Equipment function/Installation location PDSDuct pressure controller – supply air (Pressure Duct Supply) PDEDuct pressure controller – extract air (Pressure Duct Extract) PRSRoom pressure controller – supply air (Pressure Room Supply) PRERoom pressure controller – extract air (Pressure Room Extract) 9 Operating mode FConstant value mode, one setpoint value (no externals switch conact) V Variable operation (adjustable setpoint value range) 10 Signal voltage range For the actual and setpoint value signals 00 – 10 V DC 22 – 10 V DC 11 Operating values for factory setting Differential pressure [Pa] For duct pressure control, enter the differential pressure [Pa] as an absolute value ∆pconst(with operating mode F)∆pmin – ∆pmax (with operating mode V) 12 Damper blade position Only with spring return actuators NO Power off to open (Normally Open) NC Power off to close (Normally closed) Order example 1: TVR-FL/250/G2/XF4/PDS/F0/450 [Pa]/NC
, Order code for differential pressure control (with TROX UNIVERSAL controller as attachment)
1 Type TVRVAV terminal unit 2 Acoustic cladding 3 Material 4 Duct connection 5 Nominal size [mm] 6 Accessories 7 Attachments (control components) 8 Equipment function 9 Differential pressure setting With room solutions 10 Signal voltage range 11 Expansion modules Option 2: Digital communication interface Option 3: Volume flow rate measurement Option 4: Automatic zero point correction 12 Operating values for factory setting Please note 13 Damper blade position Only with spring return actuators
Order example: TVR-D-FL/160/G2/TUNF/PRS/MFP/0/UMZ/250[Pa]/NC
, Order code for room control (with EASYLAB attachment)
|