Eti vav boxes post:16.02.2024 at 07:27

Eti vav boxes

 
eti vav boxes eti vav boxes

Using 2k will save tonns of VRAM and you're still having beautiful textures. The only where you can install 4k textures are interior cells (cavesmines etc) as interior use much less VRAM and some underground creature retextures (DwemerFalmer) due to the same reasons, as well as personal standalone armorsweapons mods. If your PC is not the strongest, or you just want to save some VRAM for something else - for example, latest ENB effects or 3D LODs from DyndoLOD - simply don't waste your memory on that.

Graphics quality will be just fine.

Eti vav boxes/

Innovative Design - Enviro-tec CRB Series and CRQ Series

Enviro-tec products for zone control air conditioning meet the highest standards for quiet, efficient performance, and they’ve just introduced their next generation series flow fan boxes, the CRB and Eti vav boxes – both with significant improvements in acoustic performance.

  • Improved Access with Std. Top/Bottom Panel Fasteners, Side Access
  • Integrated 180-degree Electrical Control Enclosure with Hinged NEC Bottom Access Doors
  • Optional 90-degree Electrical Control Enclosure

DMR is proud to represent products from Enviro-tec, and we look forward to assisting you with your next project.

View the Enviro-tec Product Brochures in our Learning Center.

CRB Series - Series Flow, Fan-Powered, VAV Terminal Units

CRQ Series - Ultra-Quiet Series Flow, Fan-Powered VAV Terminals

View a Sound Comparison Chart

ETI CRQ Ultra-Quiet vs. Competition

ETI Electronic VAV

BY JOHNSON CONTROLS ELECTRONIC CONTROLS

Installation, Operation & Maintenance New Release Form ET130.13-NOM5 (209)


FORM ET130.13-NOM5 (209)

eti vav boxes TABLE OF CONTENTS
TABLE OF CONTENTS.2
safety symbols.3
1.0 - DEFINITIONS AND DESCRIPTIONS.4
eti vav boxes 1.1 - Thermostat. .4
adalaj vav stepwell 1.2 - Controller and Modules shop vav qpl45a power switch 1.3 - M9104 Series Floating Point Actuator .6
2.0 - installation.7
2.1 - Inspection .7
2.2 - Coordination of Trades.7
2.3 - Thermostat Eti vav boxes .7
2.4 - Wiring Installation .9
2.5 - Controller Wiring .9
2.6 - Thermostat Wiring .9
2.7 - Actuator Installation and Removal (Service Only) .9
eti vav boxes 2.8 - Module Installation and Removal.10
3.0 - COMMISSIONING AND BALANCING. 11
eti vav boxes 3.1 - Commissioning Procedure .11
3.2 vav surat Air Balancing Procedures .11
3.3 - Most Terminal Units .12
3.4 - Constant Primary Volume .13
3.5 - Dual Duct .14
4.0 - TROUBLESHOOTING.16
4.1 - DAMPER MOTION .17
4.2 - FAN .18
4.3 - ELECTRIC OR HOT WATER HEAT .19
4.4 - NIGHT SETBACK.21
eti vav boxes 4.5 - NIGHT MODE, COMMON PROBLEMS.22
4.6 - MORNING WARM-UP / CHANGEOVER.23
4.7 - AUXILIARY MINIMUM.24
4.8 - AIRFLOW READINGS.25
4.9 - NO RESPONSE FROM THERMOSTAT.26
4.10 - CORRECTIVE ACTIONS.27
5.0 - TEMPERATURE CALIBRATION .28
5.1 - THERMOSTAT .28
5.2 - D UCT (SUPPLY AIR) TEMPERATURE SENSOR .28
6.0 - part numbers & sequence number cross reference .29
6.1 - THERMOSTAT PART NUMBERS .29
6.2 - 700 TO 7000 SEQUENCE NUMBER CROSS REFERENCE .29
6.3 - 700 TO 7000 CONTROLLER MODEL NUMBER CROSS REFERENCE. .31
AIRFLOW CALIBRATION CURVES.32

2 eti vav boxes eti vav boxes vav box cfm chart Johnson Controls
FORM ET130.13-NOM5 (209)

safety symbols
The following symbols are used in this document to alert the reader to areas of potential hazard:

DANGER indicates an imminently CAUTION identifies a hazard which


hazardous situation which, if not could lead to damage to the machine,
avoided, will result in death or seri- damage to other equipment and/or
ous injury. environmental pollution. Usually an
eti vav boxes instruction will be given, together with
a brief explanation.

WARNING indicates a potentially NOTE is used to highlight additional


hazardous situation which, if not information which may be helpful to
avoided, could result in death or seri- you.
ous injury.

Johnson Controls shop vav qpl45a power switch 3
eti vav boxes FORM ET130.13-NOM5 (209)

1.0 - DEFINITIONS AND DESCRIPTIONS


This manual applies to Series 7000 Modular Analog c. Enclosure. Protects thermostat and provides
Electronic Controls. It does not apply to earlier 700 stable temperature environment for sensing. To
Series controls. A manual for that series is eti vav boxes remove cover, push firmly on one side (not top or
from the ENVIRO-TEC website at www.enviro-tec. eti vav boxes bottom) of cover, and pull other side away from
com under the title 700 Series Analog Electronic base.
Controls, Operation & Balancing Manual (Stock I.D. d. Connectors. Protected terminal block on back
IOM-700). of thermostat base. Terminal designations are
engraved on back of base.
The 700 Series thermostats should e. Thermostat Packaging. Bubble pack design for
not be used with Series 7000 controls. protection during shipment. Terminal numbers,
Eti vav boxes, Series 7000 thermostat may eti vav boxes signal designations, serial number, inventory
vav surat be used with 700 Series controls. You number and CO number are shown on outside
may require both manuals. of package, as well as min, max, and fan CFM
eti vav boxes eti vav boxes eti vav boxes on set CFM projects.
Specific part numbers and their rela- f. Minimum Flow Adjustment. White potenti-
tion to application numbers may be ometer on printed circuit board (see Fig. 1). CW
found in Section 6.0. rotation eti vav boxes minimum CFM.
g. Maximum Flow Adjustment. White potenti-
eti vav boxes ometer on printed circuit board (see Fig. 1). CW
vav surat eti vav boxes eti vav boxes rotation increases maximum CFM.
1.1 - Thermostat eti vav boxes. 1) h. Auxiliary (Heating) Minimum Adjustment.
a. Thermistor. Glass-encapsulated, hermetically White potentiometer allowing increased flow
sealed temperature sensing device mounted on when heat is energized. CW rotation increases
front of the thermostat printed circuit board. heating CFM. Should always be turned fully
clockwise if heating minimum feature is not
b. Setpoint Control. Hidden eti vav boxes shown. Also
used.
available with exposed dial in English or metric
scale (see Fig. 6). i. Temperature Calibration. Factory set. Adjust-
eti vav boxes ment rarely required.

eti vav boxes LD13964

FIG. 1 - THERMOSTAT

4 vav boxes titus team vav surat Johnson Controls
eti vav boxes eti vav boxes eti vav boxes FORM ET130.13-NOM5 (209)

b shop vav qpl45a power switch LD13963
kacie off shoulder top vava by joy han c
d
FIG. 2A - MASTER CONTROLLER

1.2 - Controller and Modules 1.2.2 - Heat/Fan Modules (Fig. 2b)

a. Thermostat Connectors. One-piece, captive vava 8 in 1 Series of modules incorporating a variety of fan and
screw terminal type for reliable connections. heat control applications including series or parallel
eti vav boxes fan control and/or staged, floating or proportional heat
b. 24 VAC and Control Output Connectors. Male,
control. This series can be identified by red color of
", quick connect type.
eti vav boxes circuit board.
c. Labels. Computer printed with serial number,
inventory number and CO number. eti vav boxes vav members shes mine Thermostat Sensor
24 VAC Fan and and Valve Actuator
eti vav boxes Heat Outputs vav surat Inputs/Outputs
1.2.1 - Master Controller (Fig. 2a)
Incorporates flow transducer, damper control and power
supply for modules. Sockets on modules slide onto
pins on master controller. A screw inserted through the
solder side of the master controller screws into threads
of a modules mounting bracket.
a. Flow Transducer. Device mounted on controller
which produces electronic signal proportional
vav vlive 190324 to flow. Fittings for this device are connected to
the inlet of the VAV terminal at the factory with
tubing.
b. A.C. Actuator Drive. When replacing a 700
Series DC drive controller, an M9104 Series
eti vav boxes actuator must be installed.
c. Desired Flow (VSP) Test Loop
d. Actual Flow (VF) Test Loop (located underneath
flow transducer)
e. Common (Com) Test Loop.

shop vav qpl45a power switch vav surat Deadband
eti vav boxes shop vav qpl45a power switch Mounting Bracket Adjustment
Master Controller eti vav boxes (Optional)
eti vav boxes Mating Sockets LD13969

FIG. 2B - HEAT/FAN MODULE

Johnson Controls 5
eti vav boxes eti vav boxes eti vav boxes FORM ET130.13-NOM5 (209)

1.2.3 - Setback/Warmup Modules (Fig. 2c) vava definition 1.3 - M9104 SERIES FLOATING POINT
Series of modules incorporating night setback and/or Actuator (Fig. 3)
morning eti vav boxes. Depending on model, warmup may Direct-coupled, AC drive actuator. Incorporates current
be accomplished through cooling/heating (summer/ eti vav boxes shop vav qpl45a power switch limit circuitry that removes power from motor when a
winter) changeover, or setting damper to maximum mechanical stop is met. See Installation Instructions
airflow setpoint. This series can be identified by green (Part No. 34-636-1433) at www.enviro-tec.com.
color of circuit board.
Thermostat and Sensor
eti vav boxes Supply Air Changeover
Inputs/Outputs
Temperature Adjustment

Night
shop vav qpl45a power switch Setback
Offset
Adjustment

Mounting Bracket LD13972


Master Controller eti vav boxes eti vav boxes eti vav boxes LD13973
Mating Sockets

FIG. 2C - SETBACK/WARMUP MODULE eti vav boxes FIG. 3 eti vav boxes M9104 SERIES Is the vava baby monitor wifi POINT ACTUATOR

1.2.4 - Flow Control Modules (Fig. 2d)


Series of modules incorporating a variety of applications
including dual duct, constant primary air volume, air
volume tracking, or building management system
analog interface. This series can be identified by blue
color of circuit board, labeled DD/CV/TB/BMS on
early models.
Thermostat, Contact Closure
vhod vav facebook or Voltage Inputs / Outputs

rani ki vav note Maximum Airflow
eti vav boxes vav surat vav surat Adjustment

Auxiliary Minimum
Airflow Adjustment
Minimum Airflow
13400 bee cave parkway bee vave tx Adjustment

Shop vav qpl45a power switch Controller eti vav boxes Mounting Bracket LD13968


Mating Socket

FIG. 2D - FLOW CONTROL MODULE

6 eti vav boxes eti vav boxes eti vav boxes Johnson Controls
FORM ET130.13-NOM5 (209)

eti vav boxes 2.0 - installation
FRONT eti vav boxes eti vav boxes SIDE
VIEW VIEW

MODULAR CONTROLLER

FLOWSTARTM, CENTER AVERAGING AIRFLOW


SENSOR WITH EXTERNAL BALANCING TAPS LD13957

FIG. 4 - TYPICAL COMPONENT MOUNTING


2.1 - Inspection (Fig. 4) 2.3 - Thermostat Mounting
Upon receipt of VAV terminals, check controls for Thermostats are shipped inside the control enclosure
shipping damage such as loose or eti vav boxes connectors, or shipped separately from the Terminal units. The
loose actuator or broken controller circuit board, loose thermostat may be mounted directly to drywall or,
or disconnected tubing eti vav boxes loose wiring. Also inspect optionally, to a horizontally mounted, single gang
both before and after installation for damage caused by junction box.
abuse or mishandling. A diagram of a typical control
component mounting configuration is provided (see 2.3.1 - Drywall Mounting (Fig. 5)
Fig. 4).
eti vav boxes a. Decide where to mount the thermostat and drill a
2.2 - Coordination of Trades eti vav boxes 1-3/8" hole for the wire mounting block, on the
eti vav boxes back of the thermostat, to fit eti vav boxes the wall.
Contractor should see eti vav boxes all trades involved with both
the VAV terminals and the electronic controls shop vav qpl45a power switch b. Remove the thermostat cover by pushing firmly
thermostats) eti vav boxes a copy of the documentation and on one side (not top or bottom) of cover, and
submitted control sequence data prior to installation. pulling other side away from base.

eti vav boxes WALL ANCHOR
eti vav boxes TEMPERATURE CALIBRATION
eti vav boxes las perlas de vavo MINIMUM AIRFLOW
AUX (HEATING MINIMUM)

SETPOINT POTENTIOMETER
FRONT COVER
eti vav boxes CONCEALED
vav surat MAXIMUM AIRFLOW eti vav boxes SETPOINT

INSULATING WASHER
MOUNTING SCREW (2)
shop vav qpl45a power switch 6-20 X 1 SHEET METAL
eti vav boxes LD13965

FIG. 5 - DRYWALL MOUNTING AND DRYWALL POTENTIOMETERS

Johnson Controls single duct vav system eti vav boxes 7
FORM ET130.13-NOM5 (209)

c. Hold the thermostat on the wall with the mount- greenheck vav box 2.3.2 - Junction Box Mounting (Fig. 6)
ing block in the hole drilled in step a. Mark the
location of the two mounting holes to either side a. The junction box cover provided can be used
of the center hole. DO NOT drill vav surat mounting either horizontally or vertically by simply break-
holes with the eti vav boxes on the wall; use the ing out the appropriate tab. To mount horizontally
thermostat only to locate the holes. break out tab "B", to mount vertically breakout
tab "A".
d. Remove the thermostat and drill two 3/16"
mounting holes. Insert the wall anchors into the b. Attach the 2 inch thermostat to the junction box
mounting holes eti vav boxes cover with the two 6-32X1/2" round head screws,
eti vav boxes nuts, washers, and insulating washers provided.
e. Connect the wires to the appropriate terminals
according to the application submittal data. Be c. Connect the wires vav photoshoot the appropriate terminals
eti vav boxes to connect the jumper wire from terminal #3 according to the application submittal data. Be
to #1 for all sequences except those incorporating sure to connect the jumper wire from terminal #3
eti vav boxes a duct temperature sensor. vav kpop puerto rico eti vav boxes to #1 for all sequences except those incorporating
eti vav boxes eti vav boxes a duct temperature sensor.
f. Position the thermostat eti vav boxes the wall. Fasten the
thermostat with eti vav boxes two 6-20x1" sheet metal d. Mount the cover to the junction box using the
screws, and insulating washers provided. eti vav boxes two 6-32X1/2" shop vav qpl45a power switch sunk screws provided.
g. (Optional) For exposed setpoint thermostats, e. (Optional) For exposed setpoint thermostats,
turn the setpoint potentiometer to the desired turn the setpoint potentiometer to the desired
temperature and place the setpoint knob onto the eti vav boxes temperature and place the setpoint knob onto the
setpoint potentiometer with the desired tempera- setpoint potentiometer with the desired tempera-
ture marking at the top of the dial. trane low profile vav box ture marking at the top of the dial.
h. Eti vav boxes the cover back in place with the ENVIRO- f. Snap the cover back in place with the ENVIRO-
TEC logo at the bottom of the thermostat. TEC logo at the bottom of the thermostat.

6-32 NUT (2)


eti vav boxes WASHER vav surat INSULATING WASHER
MOUNTING SCREW (2)
JUNCTION BOX
vava moov multipoint vav surat vav surat 6-32 X 1/2 ROUND HEAD
(SHOWN HORIZONTAL)
eti vav boxes eti vav boxes SETPOINT KNOB
shop vav qpl45a power switch eti vav boxes (OPTIONAL)

eti vav boxes FRONT COVER
JUNCTION BOX
EXPOSED SETPOINT
COVER
eti vav boxes MOUNTING SCREW (2) eti vav boxes BALANCE POST (OPTIONAL)
6-32 X 1/2 COUNTER GROUND LOOP
shop vav qpl45a power switch SUNK HEAD

shop vav qpl45a power switch Eti vav boxes. 6 - SINGLE GANG JUNCTION BOX SHOWN WITH EXPOSED SETPOINT

8 eti vav boxes vav surat Johnson Controls
eti vav boxes eti vav boxes eti vav boxes eti vav boxes trox vav box kvs FORM ET130.13-NOM5 (209)

2.4 - Wiring Vava 4k hdr ultra-short-throw projector eti vav boxes vava va cl006 3. Turn screw eti vav boxes CW. Make sure connector
vav surat clamps eti vav boxes portion of wire. Do not
Disconnect all power supplies to the overtighten.
eti vav boxes system before wiring to avoid damage b. 24 VAC Input and Control Output Connec-
to the equipment or possible electrical tions:
shock. eti vav boxes 1. Strip 1/4" of insulation from 18-20
eti vav boxes eti vav boxes eti vav boxes AWG stranded copper wire.
eti vav boxes 2. Attach a 1/4" quick connect spade type
a. Required Wire Type for external control connec- eti vav boxes receptacle to the uninsulated portion
tions 18 to 20 AWG stranded, copper. eti vav boxes of eti vav boxes wire using a set of crimpers.
shop vav qpl45a power switch eti vav boxes Wiring Diagrams Refer to ENVIRO-TEC vav life sciences pvt ltd mumbai 3. Push receptacle over spade and printed
Submittal Data in submittal package and/or on circuit board.
cover of control enclosure to determine correct
terminals for wiring. Prior to wiring, insure that Fit is tight. Wiggling off or pulling
the submittal sequence matches the control model off with pliers may damage board. If
number. (Refer to parts list in section vav surat. Obtain removal of a connector is required,
control sequence wiring diagram from your eti vav boxes pry off with screwdriver, supporting
ENVIRO-TEC sales representative. eti vav boxes PC board with your fingers.
c. To reduce the possibility of electrical interfer-
ence, control wiring to thermostat and optional
remote contact closures should not be routed eti vav boxes 2.6 - Thermostat Wiring
close to A.C. power (line voltage) wiring, electri-
eti vav boxes a. If thermostat has already been mounted to wall,
cal machinery or lighting.
eti vav boxes eti vav boxes remove it. Terminal eti vav boxes are engraved on
eti vav boxes eti vav boxes back of thermostat above and below two row,
2.5 - Controller Wiring six position barrier terminal block.
a. Thermostat and Control Input Connections: b. Strip 1/4" insulation from wire.
1. Using a small screwdriver, turn screw fully eti vav boxes c. Insert wire under terminal retainer. Make sure
CCW. eti vav boxes retainer clamps bare wire, not insulation.
nuku alofa to vava u eti vav boxes Insert stripped wire(s); 18-20 AWG stranded d. Repeat steps b. and c. for all wires shown on
copper (see Fig. 7). eti vav boxes submittal diagram. If diagram shows a wire from
eti vav boxes controller connected to terminal three, remove
factory installed jumper wire. Otherwise, attach
vav surat eti vav boxes bare end of factory installer jumper to terminal
static pressure reset vav shop vav qpl45a power switch 1.

2.7 - Actuator Installation and


eti vav boxes eti vav boxes Removal (Service Only)
vava 中国游戏哈 See M9104 Series Installation Instructions at www.
1/4 STRIP
eti vav boxes enviro-tec.com (Part No. 34-636-1433).

LD13966

FIG. 7 - SCREW TERMINAL CONNECTOR

Johnson Controls 9
eti vav boxes eti vav boxes FORM ET130.13-NOM5 (209)

2.8 - Module Installation and Removal g. Locate the correct position on the Master Control-
This procedure should only be required if a feature eti vav boxes shop vav qpl45a power switch for the module being installed. These positions
is being added to the control, or in the rare case of a are labeled on eti vav boxes Master Controller with both the
damaged or defective module. vava speaker bluetooth module series name and the color of the module
eti vav boxes circuit board.
a. Remove power from the controls. If a disconnect
is not supplied with the terminal and it is not h. Slide the socket(s) of the new module onto the
practical to disconnect at breaker, this may be pins provided on the master controller. Make
accomplished by removing the end of the fuse vav surat sure all the pins line up with the socket.
next to terminal 16A of the master controller with j. Insert the screw provided with the module
a non-conductive tool. If module removal is not eti vav boxes through the appropriate hole in the back of the
required, proceed to step f. control bracket, and through the master controller
b. Disconnect any wiring from the module to be into eti vav boxes threaded bracket riveted to the module.
eti vav boxes removed. eti vav boxes Tighten the screw so the module is pulled down
eti vav boxes vav surat onto the Master Controller circuit board.
If the power was removed by pulling
eti vav boxes eti vav boxes eti vav boxes If the screw does not want to start,
one end of the fuse, these wires could
the most likely cause is that the Mas-
eti vav boxes still be hot. Do not allow them to touch
eti vav boxes ter Controller pins are not correctly
the control enclosure, control bracket,
eti vav boxes eti vav boxes aligned with the module socket(s). Re-
controls or each other.
move the eti vav boxes and reinstall. Under
eti vav boxes no circumstances should the module
c. If the back of the control bracket is positioned be installed without the screw as this
against the side of the control enclosure, remove action could lead to future service
the two sheet metal screws holding the control
eti vav boxes problems.
bracket to the control enclosure. Pull the bracket
away from the side of the enclosure.
k. Wire the module per the appropriate application
d. Remove the screw securing the module to the
shop vav qpl45a power switch submittal data and the techniques and recom-
shop vav qpl45a power switch Master Controller by inserting a Phillips screw
mendations in Sections 2.4 and 2.5.
driver through the appropriate hole provided in
the back of the control bracket.
Always verify that wiring is eti vav boxes e. Remove the module by pulling straight back from before applying power.
Master Controller.
f. Remove the screw from the bracket in the new
module. Save it as it will be used later in the
procedure.

10 eti vav boxes mount vava baby monitor Johnson Controls
eti vav boxes eti vav boxes FORM ET130.13-NOM5 (209)

3.0 - COMMISSIONING AND BALLANCING


Required Items b. Check primary voltage to the control voltage
eti vav boxes eti vav boxes transformer (if applicable). Use caution, as the
a. Tools required: 1/8" flat blade screwdriver. primary power connections to the transformer
b. Digital voltmeter capable of reading eti vav boxes the hun- are lethal. Check output voltage from the trans-
dredths place and capable of reading 30 Volts former. This should be between 22 and 28 VAC.
AC/DC. Low impedance meters will not work If outside these limits immediately remove power
correctly. and determine the reason vavau tonga map improper power.
c. Airflow Calibration Curves (see Fig. 11). (See Troubleshooting, Section 4.0.)
eti vav boxes eti vav boxes c. Check that there is primary airflow (or static pres-
Optional Items eti vav boxes sure if the damper is closed) in the inlet duct.
a. Test Clips for voltmeter (optional): Test Clips d. The unit should be checked for proper sequence
(see Fig. eti vav boxes are not absolutely necessary but are response using the Application Submittal Data
very helpful. They may be obtained from a local before attempting to balance system.
consumer electronics store.
b. Magnahelic gauge incline manometer or other 3.2 - Air Balancing Procedures
differential pressure measuring device.
c. Flow hood. shop vav qpl45a power switch eti vav boxes These procedures apply to the 2"
eti vav boxes shop vav qpl45a power switch eti vav boxes square low profile thermostat. If an
when is the vava cam era shipping shop vav qpl45a power switch older model thermostat is installed,
vav surat refer to the 700 Series Analog Elec-
eti vav boxes shop vav qpl45a power switch vav surat eti vav boxes tronic Controls Operation & Shop vav qpl45a power switch ing Manual (Stock ID IOM-700).

eti vav boxes eti vav boxes Most described adjustments are made at the thermostat.


FIG. 8 - TEST CLIP LD13967 Additional adjustments may be required at the terminal
unit itself with some applications. Remove the
3.1 - Commissioning Procedure eti vav boxes thermostat cover by pushing firmly on one side (not top
eti vav boxes eti vav boxes or bottom) of cover, and pulling other side away from
base. In most cases, flow adjustments are located on the
shop vav qpl45a power switch Lethal voltages are present on the
thermostat printed circuit board (see Fig. 1). NOTE: Do
primary windings. not adjust the uppermost potentiometer. This is used for
eti vav boxes eti vav boxes temperature calibration, which is rarely required.

eti vav boxes vav surat The procedures described below use voltage-flow


setpoints for setting airflow rates for each size unit.
Always verify that wiring is correct The curves provided in this manual (see Fig.s 11, 12,
vav surat before applying power. e 0-10vdc modulating vav damper 13) allow setting of maximum and minimum volume to
vav surat vav surat design air limits (Optional). The pressure eti vav boxes from
ut autin new hire vav interactive theatre specialist the inlet sensors can be used to verify flows and assist
eti vav boxes in the system balance. Connect a magnahelic, inclined
eti vav boxes manometer or other differential pressure measuring
The following items must be checked before beginning device to the balancing tees provided vava va-uc017 7-in-1 hub Fig. 4). The
the air balancing procedure. high pressure signal is delivered from the eti vav boxes connected
a. Inspect all electrical connections to assure proper at the bottom of the probe, and the low pressure
fit and location, in accordance with the proper signal is delivered from the top of the probe. The
wiring diagram. Remember that transformer pressure differential between high and low represents
leads carry a high voltage on the primary wind- the sensed velocity pressure amplified in the inlet duct.
shop vav qpl45a power switch ings and associated terminals. LETHAL VOLT- (The manometer should have a full scale reading of
AGES MAY BE PRESENT. 0" 2.0" in W.G.)

Johnson Controls vav st.van art tattoo eti vav boxes eti vav boxes 11
eti vav boxes eti vav boxes eti vav boxes eti vav boxes FORM ET130.13-NOM5 (209)
Section 3.3 should be followed for all applications c. Turn setpoint potentiometer to full heating. Verify
except single duct (SDR) constant primary air volume the small white potentiometer labeled "AUX"
(Section 3.4) and dual duct (DDR) applications (Section is turned fully clockwise. Adjust small vav surat. potentiometer labeled "MIN" for the desired
shop vav qpl45a power switch eti vav boxes minimum Eti vav boxes voltage for VSP. If "AUX" is not
NOTES: eti vav boxes vav surat eti vav boxes turned fully clockwise, eti vav boxes step will not work
eti vav boxes correctly.
1. Room temperature must be between 65 and
85F. d. Turn the setpoint potentiometer to full cooling.
Adjust the small shop vav qpl45a power switch potentiometer labeled
2. Minimum airflow must always be set first. "MAX" for the desired maximum CFM voltage
3. For optimum control accuracy on units with inlet for VSP.
sizes of 6" or greater, a straight section of duct at
least 1.5 duct diameters long and the same diameter 3.3.2 - Warm Up/Changeover
as the inlet collar should be installed upstream of
eti vav boxes the terminal inlet. For units with 4" or 5" inlet, use If sequence wiring diagram does not
3 to 5 duct diameters. eti vav boxes show a wire from terminal #3 on the
4. For 2" thermostats with ET numbers before March eti vav boxes thermostat to terminal #2 on the con-
1, 1997, connect the black lead (-) to the left side troller (ETPCO module), proceed to
of D2, above the balance post and to the right of Step Eti vav boxes the setpoint potentiometer.
a. If the thermostat has been wired to the controller,
3.3 - Most Terminal Units the eti vav boxes supplied jumper from terminal #1 to
Some sequences have balancing adjustments on the flow #3 should already be removed and terminal #3 on
control module. If balancing one of these sequences, vav surat the thermostat should be connected to terminal
connect voltmeter to VSP and COM test loops on eti vav boxes #2 on the controller. This may be a good time to
master controller instead of balancing post and common vav versus vvt remove the thermostat and verify that the jumper
loop on the thermostat. If application incorporates eti vav boxes has been removed. If the jumper is still on the
warmup or changeover, verify unit is in cooling mode back of the thermostat remove it and verify the
by measuring voltage between terminals 3 (+) and 2 (-) wiring to the sequence.
of thermostat. If less than 14 VDC, temporarily remove
duct sensor wire from terminal 3 of controller. vav surat b. Adjust the blue potentiometer on the setback/
eti vav boxes eti vav boxes eti vav boxes warmup module labeled "Duct Sensor" to a tem-
3.3.1 - ALL TERMINAL UNITS
vava support perature midway between the expected cold and
Steps 3.3.1 and 3.3.6 should be followed for all warm air temperatures. Recommended minimum
applications, while steps 3.3.2 through 3.3.5 are only difference in cold and warm air temperature is
used for the particular application listed in each step. 10F.
a. Remove cover as described in Section 3.2 and
setpoint knob (if applicable) from thermostat. eti vav boxes eti vav boxes If you turn the Duct Sensor potenti-
Use Airflow Calibration Curves (see Fig.s 11 and eti vav boxes ometer fully CCW, the sensor is set to
13) to determine VSP voltages required for the switch at 50F. If you turn the Duct
desired minimum and maximum airflow settings. Sensor potentiometer fully CW, the
For SDR, VFR and CFR terminals, use graph in sensor is set to switch at 90F (e.g.,
Fig. 11. For SSD, VVF and CVF terminals, eti vav boxes if it is desired for the controller to
the graph in Fig. 13. For instance, if a minimum
CFM value of 200 is desired for a 6" SDR box, operate in the daytime mode for duct
the corresponding VSP voltage is 9.2VDC. temperatures less than 75F, and oper-
eti vav boxes ate in the morning warm-up mode for
b. To vava baby monitor only VSP, connect the red lead (+) from a DC
voltmeter to the post at terminal #5 under the duct temperatures more than 75F, the
setpoint potentiometer (shown in Fig. 6). Connect Duct Sensor potentiometer located on
the black lead (-) to the common loop (shown in eti vav boxes the controller should be adjusted just
vav surat Fig. 6) above and to the right of the balance post. past the halfway point towards the
For single duct applications with dual minimums, "90" mark).
remove the wire connected to terminal #4 of the
heat/fan module.
12 eti vav boxes eti vav boxes eti vav boxes eti vav boxes Johnson Controls
FORM ET130.13-NOM5 (209)

3.3.3 - Dual Minimum (Single Duct Applications d. Remove power. Remove end of jumper con-
Incorporating a Heat/Fan Module) eti vav boxes nected to "Low Spd" terminal and reinstall on
eti vav boxes the eti vav boxes Spd" terminal.
a. Reconnect the wire on terminal #4 (removed in
step 3.3.1.b). eti vav boxes e. Re-apply power. If air is leaving the plenum air
eti vav boxes inlet, go to step 3.3.4.f. Otherwise, go to step
b. Connect a DC voltmeter (as described in step
3.3.4.g.
#3.3.1.b).
eti vav boxes f. Remove power. Remove end of jumper con-
c. Refer to the Airflow Calibration curves again to
nected to "Med Spd" terminal and reinstall on
determine the required voltage for the desired
eti vav boxes eti vav boxes "High Spd" terminal. Re-apply power.
heating minimum CFM setting.
g. Using the hole in the front cover of the fan speed
d. Turn the temperature setpoint potentiometer to
eti vav boxes eti vav boxes controller and a small screwdriver, slowly adjust
full heating. Adjust the small white potentiom-
eti vav boxes eti vav boxes CCW until no air is either entering or leaving the
eter labeled "AUX" until the voltmeter reads the
plenum air inlet.
desired voltage.
eti vav boxes shop vav qpl45a power switch vav-a2-1 3.3.5 - N
eti vav boxes eti vav boxes vav give me more un poco mas zumba  ight Setback (Fan Powered Applica-
3.3.4 - All Series Flow Fan Terminals
tions Incorporating a Setback/Warmup
(Models CFR, CFRQ)
eti vav boxes shop vav qpl45a power switch Module and a Pressure Switch)
a. These terminals need the fan speed adjusted so The temperature setting for night set back is located on
that when drawing maximum primary airflow, the setback/warmup module. The controller is factory
no air is either entering or leaving the plenum air set at a maximum of 15 degrees below setpoint, (offset
inlet. Turn temperature setpoint to full cooling, adjustment turned fully clockwise). (i.e. if the thermostat
and wait for damper to move to maximum CFM setpoint is 74 degrees the heat will energize at 59 degrees
setpoint. shop vav qpl45a power switch during night set back). Turn the adjustment fully counter
b. A motor speed adjustment terminal strip and an clockwise for a 0 degree offset, eti vav boxes halfway for a 7.5
vav surat electronic fan speed controller are used to make degree shop vav qpl45a power switch this adjustment. Locate these components in the
terminal's control or electric heat enclosure. A 3.3.6 - All Terminal Units with Thermostats
hole in the front cover of the fan speed control-
ler allows adjustment using a small screwdriver. a. When all the applicable balance procedures
Verify the adjustment if fully CW. from above are completed, turn the setpoint
vav surat potentiometer to the desired temperature. Place
the (optional) setpoint knob eti vav boxes the setpoint po-
Lethal Voltages are Present!
eti vav boxes tentiometer with the desired temperature marking
eti vav boxes at the eti vav boxes of the dial.
Disconnect all power before attempt-
b. Snap the cover back in place with the ENVIRO-
ing to adjust motor speed using the
TEC logo at the bottom of the thermostat.
motor eti vav boxes adjustment terminal
strip. 3.4 - Constant Primary Volume
Do not adjust the fan speed controller
vav surat eti vav boxes 3.4.1 - Applications Incorporating a Heat/Fan
eti vav boxes using the hand! eti vav boxes vavs costa rica Module
Do not touch the back of the fan
speed controller! a. Verify that small white potentiometer labeled
vavs nac membership subcommittee Do not adjust the second, factory "AUX" is turned fully clockwise. Eti vav boxes it is not
set potentiometer only accessible turned fully clockwise this step will not work
eti vav boxes correctly.
eti vav boxes from the back or warranty will be
voided. b. Turn the "MAX" potentiometer fully counter
eti vav boxes eti vav boxes clockwise.
c. If eti vav boxes is leaving the plenum air inlet, go to step
3.3.4.d. Otherwise, go to step 3.3.4.g.

Johnson Controls eti vav boxes vava chroma vs samsung lsp9t 13
shop vav qpl45a power switch shop vav qpl45a power switch FORM ET130.13-NOM5 (209)

c. Use the Airflow Calibration Curves (see Fig.s 11 3.5.1 - DD7100


and 13) to vav surat the VSP voltage required for
the desired constant airflow setting. Determine a. Connect the red (+) lead from the DC voltmeter
the proper curve to use as described in step to the "VSP" test loop and the black (-) lead to
3.3.1.a. the "COM" test loop on the hot deck master
eti vav boxes controller. Turn the adjustment labeled "AUX"
d. To read VSP, connect a DC volt meter (as de-
on the hot deck ETPCV2 module to eti vav boxes voltage
scribed in step 3.3.1.b).
corresponding to the desired total air flow for
e. Adjust the small white potentiometer labeled vav logosu constant volume applications, or the desired
"MIN" for the desired voltage for VSP that cor- maximum heating air flow for variable volume
responds to the desired airflow. applications.
f. Go to 3.3.6. vav magazine sweden b. Turn the temperature setpoint knob to full cool-
eti vav boxes ing. Connect the red (+) lead from the DC
3.4.2 - A
 pplications incorporating a Flow eti vav boxes voltmeter to the "VSP" test loop and the black
Control Module eti vav boxes eti vav boxes (-) lead to the "COM" test loop on the cold shop vav qpl45a power switch a. Constant primary volume applications not requir- master controller. Turn the adjustment labeled
ing a thermostat have the air flow adjustments eti vav boxes "MAX" on the cold deck ETPUC module fully
on the Flow Control module. Disregard all state- counter clockwise. Set the adjustment labeled
ments that refer to the air flow adjustments on the eti vav boxes "MIN" on the cold deck ETPUC module to the
thermostat when dealing with these applications. desired minimum cold deck airflow.
The flow curves at the end of the manual are still c. Set the adjustment labeled "MAX" on the cold
used for setting CFM. deck ETPUC module to the desired maximum
b. Connect the red (+) lead from the DC voltmeter eti vav boxes cold deck airflow. For constant volume appli-
to the VSP test loop and the black (-) lead to cations, if a zero heating minimum shop vav qpl45a power switch desired,
the COM test loop on the master controller. this setting will be the same as the desired total
If the application requires two constant primary eti vav boxes airflow set in vav paper "a". If a heating minimum is
volume settings controlled by a contact eti vav boxes, desired, the maximum cold deck air flow setting
eti vav boxes open the contact. Vav surat the adjustment labeled shop vav qpl45a power switch should be less in CFM (greater in voltage) than
AUX on the Flow Control module to the shop vav qpl45a power switch the desired total airflow setting by the value of
eti vav boxes voltage corresponding to the required constant the desired heating minimum.
primary air volume.
3.5.2 - DD7200
c. If the application requires two constant primary
volume settings controlled by a contact closure, a. Turn the temperature setpoint knob to full heat.
close the contact. Turn the adjustment labeled Connect the red (+) lead from the DC voltmeter
MIN on the Flow Control module to eti vav boxes to the "VSP" test loop and the black (-) lead to
voltage corresponding to the required constant the "COM" test loop on the hot deck master
primary air volume. vav surat controller. Turn the adjustment labeled "MAX"
eti vav boxes on the hot deck ETPUH module fully counter
3.5 - Dual Duct eti vav boxes shop vav qpl45a power switch clockwise. Turn the adjustment labeled "MIN" on
Dual Duct applications have the air flow adjustments on the ETPUH module to the voltage corresponding
the Flow Control module. Disregard all statements that to the desired total minimum airflow.
refer to the air flow adjustments on the thermostat when b. Set the adjustment labeled "MAX" on the ET-
dealing with Dual Duct applications. The flow curves PUH module to the desired maximum hot deck
at the end of the manual are still used for setting CFM. airflow.
If flow readings are being set/verified with a hood, a c. Connect the red (+) lead from the DC voltmeter
deck can be isolated by temporarily disconnecting the to either end of JP6 on the ETPUH module (see
"COM" wire from the actuator of the other deck, and Fig. 9). Shop vav qpl45a power switch the black (-) lead attached eti vav boxes the
using the manual override to close the damper. eti vav boxes "COM" test loop on the hot deck master control-

14 eti vav boxes Johnson Controls
FORM ET130.13-NOM5 (209)

ler. Use the following equation shop vav qpl45a power switch calculate the 3.5.3 - DD7300


value of voltage to be set for the desired eti vav boxes band: eti vav boxes a. Connect the red (+) lead from the DC voltmeter
eti vav boxes to the eti vav boxes test loop and the black (-) lead to
V = 8.3 - (0.25 x desired mixing band) +
vav surat shop vav qpl45a power switch the "COM" test loop on the eti vav boxes deck master
eti vav boxes total airflow setpoint/maximum
eti vav boxes eti vav boxes controller. If installed, disconnect the wire from
cooling airflow setpoint)
eti vav boxes eti vav boxes eti vav boxes the optional CO2 sensor from terminal 4 of the
hot deck ETPCV2 module. Turn the adjustment
The mixing band is in degrees Fahrenheit and the airflow labeled "AUX" on the ETPCV2 module to the
setpoints are in CFM. Set the calculated voltage using eti vav boxes voltage corresponding to the desired outside
R11 on the ETPUH module (see Fig. 9). eti vav boxes airflow. If the CO2 sensor option is to be used,
Thermostat eti vav boxes temporarily short terminal 4 to terminal 7 on the
Input ETPCV2 module and turn the adjustment labeled
eti vav boxes eti vav boxes "MIN" to the voltage corresponding to eti vav boxes desired
eti vav boxes eti vav boxes low level eti vav boxes air flow.
Maximum
eti vav boxes shop vav qpl45a power switch b. Turn the temperature setpoint knob to full cool-
Hot Deck ing. Connect the red (+) lead from the DC
eti vav boxes vav surat Airflow voltmeter to the "VSP" test loop and the black
eti vav boxes Adjustment
(-) lead to the eti vav boxes test loop on the cold deck
korean group vav shop vav qpl45a power switch master controller. Turn the adjustment labeled
eti vav boxes Total "MAX" on the cold deck ETPUC module fully
comfort point vav controller Minimum counter clockwise. Set the adjustment labeled
where can i buy a vava ust projector eti vav boxes Airflow
Adjustment "MIN" on the cold deck ETPUC module to the
vav surat desired minimum cold deck airflow.
eti vav boxes eti vav boxes c. Set the adjustment labeled "MAX" on the cold
vavada live JP6 deck ETPUC module to the desired maximum
eti vav boxes vav surat shop vav qpl45a power switch cold deck airflow.

Master Controller R11


Mating Socket Mounting Bracket
LD13962

FIG. 9 - ETPUH MODULE

d. Turn the temperature setpoint knob to full


cooling. Connect the red (+) lead from the DC
voltmeter to the "VSP" test loop and the black
eti vav boxes (-) lead to the "COM" test loop on the cold deck
master controller. Turn the adjustment labeled
"MAX" on the cold deck ETPUC module fully
counter clockwise. Set the adjustment labeled
"MIN" on the cold deck ETPUC module to the
desired minimum cold deck airflow.
e. Set the adjustment labeled "MAX" on the cold
deck ETPUC module eti vav boxes the desired maximum
cold deck airflow.

Johnson Controls 15
pics hq vave own eti vav boxes FORM ET130.13-NOM5 (209)

eti vav boxes 4.0 - TROUBLESHOOTING
With all electrical devices eti vav boxes is the d. Since most of the procedures are temperature
danger of electrical shock. Lethal volt- related, you must ensure that the ambient tem-
ages are present at the supply connec- perature at the thermostat is 55-85F. also, the
tions of all power transformers. Use primary air supply must be 55-85F, at 0.5-2.5"
caution when measuring operating W.G. inlet static pressure.
voltages of these units. eti vav boxes eti vav boxes e. Some sequences have balancing adjustments on
eti vav boxes eti vav boxes vav air terminal unit the Flow Control module. If troubleshooting one
eti vav boxes of these sequences, substitute terminal 3 of the
a. At the beginning of each section are Common
vav surat eti vav boxes thermostat for terminal 6 of the thermostat in
Problems. To save time, check these items
the troubleshooting instructions. Also substitute
first.
master controller VSP test loop for terminal
b. IMPORTANT: If a unit operates correctly when 5 of the thermostat.
forced into normal mode, the problem is with
f. The following table is a vava va-cl006 night lights for kids of unit functions. Fol-
the particular option being defeated. Many of
eti vav boxes low the table in the order presented to determine
the procedures refer to Normal and/or Option
the specific problem(s). For instance, to diagnose
Mode. Normal Mode refers to daytime, cooling
vav hahipuch prime eti vav boxes eti vav boxes eti vav boxes a single shop vav qpl45a power switch, cooling only terminal which does
operation. A eti vav boxes with options may be forced into
shop vav qpl45a power switch not move its damper when the thermostat is
Normal Mode by removing the duct sensor wire
shop vav qpl45a power switch eti vav boxes turned from full heating to full cooling (or vice
from controller Terminal 3, and/or removing a
versa), first go through section 4.1 (Damper Mo-
wire from the pressure switch.
eti vav boxes shop vav qpl45a power switch shop vav qpl45a power switch tion). Then, if the problem is not resolved, go to
c. Many of the procedures in this section require section 4.9 (No Response to Thermostat).
taking voltage readings. This may be done eas-
ily by using meter leads with spring-loaded clips
instead of the usual probes. These leads free your
hands for other work; they may be purchased at
eti vav boxes consumer electronics stores. For controller termi-
nals not having test loops, voltages may be read
by holding the meter lead directly on the screw
terminal or tab connector (as applicable). Test
points followed by a (+) are to be attached to
the + jack of your meter, eti vav boxes is usually the
red lead. Test points followed by a (-) are to
be attached vava alr projector screen 100-inch the - jack of your meter, which
is usually the black lead.

TABLE 4.0 - QUICK REFERENCE

PROBLEM WITH: : PROCEED TO SECTION


DAMPER MOTION 4.1
FAN 4.2
eti vav boxes ELECTRIC OR HOT WATER HEAT 4.3
NIGHT SETBACK 4.4
NIGHT MODE eti vav boxes FLOW TERMINAL ONLY) 4.5
youtube sela vave singing eti vav boxes Eti vav boxes WARM-UP eti vav boxes 4.6
shop vav qpl45a power switch AUXILIARY (HEATING) MINIMUM 4.7
AIRFLOW READINGS eti vav boxes 4.8
NO RESPONSE TO THERMOSTAT 4.9
vav 2018 group CORRECTIVE ACTIONS vav surat 4.10

16 eti vav boxes Johnson Controls
eti vav boxes eti vav boxes eti vav boxes FORM ET130.13-NOM5 (209)

4.1 - DAMPER MOTION


The current 7000 Series Master Con- These procedures apply only to Series
troller drives a Floating Point M9104 7000 used with the M9104 Series ac-
Series actuator. Since the output is tuator. Refer eti vav boxes the Series 700 IOM
time-proportioned, it will be neces- for legacy applications.
eti vav boxes sary to observe the actuator for up
to 30 seconds before proceeding with
eti vav boxes step. eti vav boxes COMMON PROBLEMS

eti vav boxes 1. Output wires backwards; Terminal 13 is CCW


vav wien Do not use the Series 7000 Master (open), Terminal 14 is CW (closed).
Controller with any other AC drive eti vav boxes 2. Option Mode enabled; verify that the unit is in Nor-
actuator, or serious damage to the mal Mode before continuing with this procedure.
controller may result. See Section 4.0.b.

TABLE 4.1

Proceed
Step Action eti vav boxes Result
eti vav boxes eti vav boxes shop vav qpl45a power switch eti vav boxes To
eti vav boxes Verify actuator is operating properly using checkout instructions on page 5 of
4.1.1
Installation Instructions (Part No. 34-636-1433) available at www.enviro-tec.com.
As previously described, force unit to normal mode. Attempt to set MIN (and AUX Good vav surat 4.1.3
4.1.2
MIN, if shop vav qpl45a power switch AIRFLOW to 15.2 VDC per Section 3.0, Balancing Bad 4.9
eti vav boxes eti vav boxes vav surat Good 4.1.4
4.1.3 Set MAX AIRFLOW to 5.0 VDC
eti vav boxes Bad 4.10.18
Connect DC voltmeter between VSP (+) and Com (-) test loops on controller. Vary Good 4.1.5
4.1.4
eti vav boxes wgat is the cost of a vave replacement the thermostat vav surat and verify that voltage goes from 15.2 VDC to 5.0 VDC. Bad 4.10.1
vavada casino no deposit bonus code Turn the thermostat setpoint to full heating and verify that the damper shaft
rotates in the CW (closed) direction at least once every 30 seconds. Then turn the Good 4.1.6
4.1.5
shop vav qpl45a power switch temperature setpoint to full cooling and verify that the damper shaft rotates in the Bad 4.8
CCW (open) direction at least once every 30 seconds.
Damper actuator and controller actuator drive are working correctly. If you have
4.1.6
other problems, refer to Table 4.0

Johnson Controls eti vav boxes 17
FORM ET130.13-NOM5 (209)

4.2 - FAN

On parallel fan terminals (VFR), the COMMON PROBLEMS


fan relay is controlled vav surat the electronic 1. Blown fan motor fuse.
controller based on ambient tempera- eti vav boxes 2. Option Mode enabled; verify that the unit is in Nor-
ture. eti vav boxes mal Mode before continuing with this procedure.
See Section 4.0.b.
On Series Flow fan terminals (CFR), eti vav boxes 3. Maximum airflow setpoint set below 3.0 VDC
the fan relay is kept Eti vav boxes in Normal dual duct vav box sequence operation diagram (Series Flow models only).
Mode. In the Option Mode, the eti vav boxes is eti vav boxes 4. Blue and yellow wires swapped between trans-
either a: CYCLED to maintain tem- former and controller.
perature, or b: kept OFF, depending
on your shop vav qpl45a power switch 4.2
Proceed
Step eti vav boxes eti vav boxes Action eti vav boxes Result
eti vav boxes eti vav boxes to
As previously described in 4.0.6, force unit to normal mode. Eti vav boxes the unit in question is a
parallel fan terminal: 4.2.2
4.2.1

If the unit in question is a series flow fan terminal: 4.2.6


Connect DC voltmeter between terminal 6 (+) and terminal 2 (-) on thermostat. Vary
eti vav boxes size of vava chroma va-sp003 eti vav boxes vav surat Good 4.2.3
4.2.2 the thermostat eti vav boxes and verify that voltage goes from approximately 1VDC (CCW)
vav surat vav surat vav surat Bad 4.9
to 17 VDC (CW).
eti vav boxes Connect DC voltmeter between terminal 5 (+) on the Heat/Fan Module and Com test
shop vav qpl45a power switch eti vav boxes eti vav boxes Good 4.2.4
4.2.3 loop (-) on master controller. Vary the thermostat setpoint and verify that voltage goes
shop vav qpl45a power switch eti vav boxes Bad 4.10.1
from approximately 1VDC (CCW) to 17 VDC (CW).
Within the control or electric heat enclosure, locate the fan relay (or magnetic Good
4.2.4
contactor if installed). eti vav boxes Bad
eti vav boxes Turn eti vav boxes thermostat setpoint to full cooling, then slowly turn it toward full heating.
vav st van senorita eti vav boxes Good 4.2.8
4.2.5 Verify that the fan relay (magnetic contactor) engages at 1 to 2 degrees above ambi-
eti vav boxes eti vav boxes Bad 4.2.6
ent temperature.
vava viana eti vav boxes eti vav boxes Good 4.2.7
4.2.6 Carefully check wiring to the fan relay (magnetic contactor) per the sequence.
eti vav boxes eti vav boxes eti vav boxes Bad 4.10.1
Remove the wire from Heat/Fan Eti vav boxes Terminal 9 and momentarily touch it to mas- Good 4.10.14
4.2.7
ter controller Terminal 15. Verify that the fan relay (or magnetic contactor) engages. Bad 4.10.4
shop vav qpl45a power switch Fan controls are operating correctly in Normal Mode. If you wish to test the fan in an
4.2.8
option mode, or if you have other problems, refer to Table 4.0.

18 eti vav boxes eti vav boxes Johnson Controls
eti vav boxes eti vav boxes FORM ET130.13-NOM5 (209)

4.3 - ELECTRIC OR HOT WATER HEAT


COMMON PROBLEMS

1. Blown fan motor fuse.


2. Option Mode enabled; verify that the unit is in Normal Mode before continuing with this procedure.
See Section 4.0.b.
3. Blue and yellow wires swapped from transformer to controller.

TABLE 4.3

PROCEED
STEP vava 8 ACTION RESULT
TO
As previously described in 4.0.b, force unit to normal mode. Connect DC voltmeter
between terminal 6 (+) and the common loop (-) on thermostat. Vary the thermostat Good shop vav qpl45a power switch 4.3.2
4.3.1
eti vav boxes setpoint and verify that voltage goes from eti vav boxes 1 VDC (full cooling) to 17 VDC Bad 4.9
(full heating).
Connect DC voltmeter between Heat/Fan module terminal 5 (+) and Com (-) test loop
vav surat Good 4.3.3
4.3.2 on master controller. Turn the thermostat setpoint CW and CCW, and eti vav boxes that volt-
Bad 4.10.1
age goes from approximately 1 VDC (full cooling) to 17 VDC (full heating).
eti vav boxes eti vav boxes 4.3.4
Determine the type of heat control and proceed to the step indicated: Staged Electric, or
eti vav boxes eti vav boxes 4.3.8
4.3.3 On/Off Hydronic Floating, Modulating Hydronic Proportional Modulating Hydronic SSR/
shop vav qpl45a power switch distech controls bacnet ip vav eti vav boxes eti vav boxes 4.3.14
SCR Electric
eti vav boxes 4.3.21
If the unit is equipped with electric heat, locate the heat relays (contactors) within the
heater cabinet. If the unit is equipped with hot water heat, locate the hot water valve
Good 4.3.5
4.3.4 actuator. Turn the thermostat setpoint to full cooling, then slowly turn it toward full heat-
Bad 4.3.6
ing. Verify eti vav boxes the first stage heat relay (magnetic contactor) or hot water valve eti vav boxes engages at 2-3 degrees above ambient temperature.
If you have only one stage of electric or hydronic heat, go to 4.3.26. Otherwise, con-
eti vav boxes Good eti vav boxes 4.3.7
4.3.5 tinue slowly turning the temperature setpoint toward full heating, and verify that stages
Bad 4.3.6
eti vav boxes 2 and 3 (if applicable) engage in approximately 1 degree increments.
Carefully check wiring to the heat relays (contactors) or hot water valve actuator per the
application. If correct, remove the wire from the faulty Heat/Fan eti vav boxes Terminal Output Good 4.10.14
4.3.6
(10 through 12), and momentarily touch it to master controller terminal 15. Verify that Bad 4.10.5
the heat relay (contactor) or hot water valve actuator engages.
eti vav boxes Heat controls are eti vav boxes correctly in Normal Mode. If you wish to test the heat in an
4.3.7 option mode, or if you have other problems, refer to Table 4.0.
Vavo studiefinanciering OF STAGED ELECTRIC OR ON/OFF HYDRONIC SECTION
Turn the thermostat temperature setpoint to full cooling and verify that the valve is clos- eti vav boxes Good 4.3.10
4.3.8
ing (if already closed, proceed to Step 4.3.10). eti vav boxes Bad 4.3.9
Carefully check the wiring of the valve actuator per the application submittal data and
eti vav boxes eti vav boxes Good 4.10.14
4.3.9 the valve actuator manufacturers literature. If correct, remove the wire from terminal 11
Bad 4.3.12
of eti vav boxes Heat/Fan module and touch to terminal 15. Verify that the valve is closing.
Turn the thermostat temperature setpoint to full heating and verify that the valve is Good 4.3.13
4.3.10
opening. Bad 4.3.11
Carefully check the wiring of the vav surat actuator per the application submittal data and
eti vav boxes eti vav boxes Good 4.10.14
4.3.11 eti vav boxes the valve actuator manufacturers literature. If correct, remove the wire from terminal 10
Bad 4.3.12
of the Heat/Fan module and touch to terminal 15. Verify that the valve is opening.
The controller valve outputs are operational. The valve actuator may be damaged eti vav boxes 4.3.12 defective. Refer to the literature provided by the manufacturer of the valve actuator to
eti vav boxes diagnosis the eti vav boxes shop vav qpl45a power switch Continued on next page
Johnson Controls eti vav boxes eti vav boxes eti vav boxes 19
eti vav boxes eti vav boxes FORM ET130.13-NOM5 (209)
TABLE 4.3 (cONT.)

eti vav boxes eti vav boxes PROCEED
STEP eti vav boxes ACTION RESULT
vav surat TO
If the procedure in step 4.3.8 was not performed because the valve was already closed,
eti vav boxes proceed to that step. If that procedure has been performed, the controls and valve ac-
4.3.13 tuator appear to be functioning properly. If temperature is not being controlled properly,
the problem may be in thermostat calibration. See Section 5.1.
eti vav boxes END OF FLOATING, MODULATING HYDRONIC SECTION
The standard heat/fan modules proportional signal is 2 to 10 VDC normally open eti vav boxes i.e. the valve should be fully open below 2 VDC and fully closed above 10 VDC. Special
heat/fan modules may be reversed, and/or use a different signal range. Use eti vav boxes submit-
4.3.14 tal diagram for ran ki vav terminal unit in question to determine the output range. Make sure
it is the same as the valve actuators range by referring to the valve actuator literature.
Voltages for a standard heat/fan module will be used below, but the same steps may be
used for other ranges by substituting the correct open and close voltages (or currents).
Disconnect the wire from terminal 12 of the Heat/Fan Module. Turn the thermostat tem-
vave code Good 4.3.16
4.3.15 perature setpoint to full cooling and measure the voltage on Heat/Fan Module terminals
Bad eti vav boxes eti vav boxes vav surat 12 (+) and 7(-). Verify the closed voltage (10 VDC or higher)
eti vav boxes Turn the thermostat temperature setpoint to full heating and measure the voltage on Good 4.3.17
4.3.16
Heat/Fan Module terminals 12 (+) and 7 (-). Verify the open voltage (2 VDC or lower). krewella vava new world lyrics Bad 4.10.14
eti vav boxes Reconnect the wire to terminal 12 of the Heat/Fan Module. Carefully check the wiring of Good 4.3.18
4.3.17
the valve actuator per the application submittal data and the manufacturers literature. Bad 4.10.1
Verify that the valve is opening. Turn the thermostat temperature setpoint to full cooling. Good 4.320
4.3.18
vav no reheat Verify that the valve is closing. Bad 4.3.19
The valve actuator may be damaged or defective. Refer to the literature provided by eti vav boxes 4.3.19
manufacturer of the valve actuator or SSR/SCR to diagnose the problem.
The controls and valve actuator appear to be functioning properly. If temperature is not
being controlled properly, eti vav boxes problem may be in thermostat calibration. See Section
4.3.20
5.1.
eti vav boxes END OF PROPORTIONAL MODULATING HYDRONIC SECTION
The standard heat/fan modules signal for SCR or SSR electric heat is 2 VDC (off) to 10
VDC (fully on). If a current (1995 and up) SSR heat interface is provided by ENVIRO-
TEC, it should be a model ETPHCV2. Early model (prior to 1996) SCR heat controllers
4.3.21
provided by ENVIRO-TEC should have an ETPCM4V2 or Eti vav boxes master SCR
controller. If the SCR or SSR heat control is eti vav boxes by others, refer to the manufacturers
eti vav boxes literature to verify it will accept a 2 to 10 VDC signal.
Disconnect the wire from terminal 12 of the Heat/Fan Module. Turn the thermostat tem-
Good eti vav boxes 4.3.23
4.3.22 perature setpoint to full cooling and measure the voltage on Heat/Fan Module terminals
eti vav boxes Bad 4.10.14
12 (+) and 7 (-). Verify the off voltage vav surat less than 2 VDC.
Turn the thermostat temperature setpoint to full heating and measure the voltage on
eti vav boxes Good 4.3.24
4.3.23 Heat/Fan Module terminals 12 (+) and 7 (-). Verify the full on voltage is equal to or
eti vav boxes shop vav qpl45a power switch Bad vav electric reheat box 4.10.14
greater than 10 VDC.
Reconnect the wire to terminal 12 of the Heat/Fan Module. Carefully check vav surat wiring
eti vav boxes eti vav boxes Good 4.3.25
4.3.24 of the SSR/SCR per the application submittal data and the heater wiring diagram (if
eti vav boxes Bad 4.10.1
manufactured by ENVIRO-TEC) or SSR/SCR manufacturers literature.
Verify that the SSR/SCR heat is full on. Turn the thermostat temperature setpoint to full Good 4.3.27
4.3.25
cooling. Verify that the SSR/SCR heat is off. Bad 4.3.26
The valve actuator or SSR/SCR may be damaged or defective. Refer to the literature
4.3.26 provided by the manufacturer of the valve actuator or SSR/SCR to diagnose the prob-
lem.
The controls and valve actuator or SSR/SCR appear to be functioning properly. If tem-
shop vav qpl45a power switch perature is not being controlled properly, the problem may be in thermostat calibration.
4.3.27
vav surat See Section 5.1.
END OF SSR/SCR ELECTRIC SECTION
20 eti vav boxes eti vav boxes eti vav boxes Johnson Controls
eti vav boxes FORM ET130.13-NOM5 (209)

4.4 - NIGHT SETBACK


COMMON PROBLEMS

1. Air hose on pressure switch connected to LOW fitting instead of HIGH.


2. Wires on pressure switch not connected to NC and COM.
3. Insufficient static pressure to keep pressure switch open.

TABLE 4.4

eti vav boxes vav surat eti vav boxes PROCEED
STEP vav surat eti vav boxes ACTION RESULT
eti vav boxes eti vav boxes TO
Connect a DC voltmeter between Setback/Warmup module terminal 1 (+) and Com (-) eti vav boxes Good 4.4.3
4.4.1
on master controller. Verify voltage is 14-18 VDC. eti vav boxes Bad 4.4.2
Verify that the air pressure switch and controller wiring are all correct. Remove the wire
shop vav qpl45a power switch Good 4.4.3
4.4.2 from Setback/Warmup module Terminal 1 and verify voltage from Setback/Warmup module
eti vav boxes eti vav boxes eti vav boxes Bad 4.10.15
Terminal 1 (+) to Com (-) loop on master controller is 14-18 VDC.
Temporarily disconnect the hose going to the pressure switch at the "T" fitting. If discon-
eti vav boxes eti vav boxes shop vav qpl45a power switch eti vav boxes Good 4.4.4
4.4.3 nected, reconnect the wire to Terminal 1 and verify that the voltage from Controller Terminal
eti vav boxes eti vav boxes Bad 4.10.6
1 (+) to Com (-) loop on master controller is 0-1 VDC.
Blow in the hose going to vava move on button not working pressure switch and verify that the voltage from Controller Good 4.4.5
4.4.4
eti vav boxes Terminal 1 (+) to Com (-) loop on master controller jumps up to 14-18 VDC. Bad 4.10.6
eti vav boxes Good 4.4.6
4.4.5 Verify primary static pressure at terminal inlet is above 0.3" W.G.
eti vav boxes eti vav boxes did vav sample senorita Bad 4.10.7
Reconnect air hose. Vary the temperature setpoint and verify that it controls the damper, Good 4.4.7
4.4.6
fan and heat vav surat applicable). vav surat Bad 4.9.8
Disconnect air hose from pressure switch. Turn the Setback Offset adjustment located on
the Setback/Warmup Module to the middle of its range. Verify that the damper closes and Good 4.4.8
4.4.7
the fan turns on/off approximately 7 to 8 degrees above ambient nuestra casa rcn vav. Return the Bad eti vav boxes 4.10.15
Offset adjustment to its original position.
eti vav boxes Reconnect air hose to pressure switch. Night Setback is operating eti vav boxes. If you wish to
4.4.8
test the controls in another option mode, or eti vav boxes you have other problems, refer to Table 4.0.

Johnson Controls eti vav boxes 21
vav abc dance practice shop vav qpl45a power switch FORM ET130.13-NOM5 (209)

4.5 - NIGHT MODE, COMMON PROBLEMS 1. Air hose on pressure switch connected to LOW
This mode only applies to CFR/CFRQ eti vav boxes instead of HIGH.
fan terminal units. On power up or ap- 2. Wires on pressure switch not connected to NC and
plication of primary air pressure, there eti vav boxes COM.
is a 3 to 5 minute delay before fan and 3. Insufficient static pressure to keep pressure switch
heat are enabled. open.

TABLE 4.5

PROCEED
STEP ACTION RESULT
eti vav boxes vav surat TO
If the application incorporates a duct sensor, temporarily disconnect it from terminal 3 of
4.5.1 eti vav boxes eti vav boxes 4.5.2
the Setback/Warmup module.
shop vav qpl45a power switch Connect a DC voltmeter between Heat/Fan module Terminal 4 (+) and the Com (-) loop of Good shop vav qpl45a power switch 4.5.4
4.5.2
the master controller. Verify voltage is 14-18 VDC. Eti vav boxes 4.5.3
Verify that the air pressure switch and controller wiring are all correct. Remove the wire
eti vav boxes eti vav boxes Good 4.5.4
4.5.3 from Heat/Fan module Terminal 4 and verify voltage from Terminal 4 (+) to the Com (-) loop
eti vav boxes eti vav boxes eti vav boxes Bad eti vav boxes 4.10.14
on the master shop vav qpl45a power switch is 14-18 VDC.
shop vav qpl45a power switch Temporarily disconnect the hose going to the pressure switch at the "T" eti vav boxes. Reconnect
eti vav boxes Good 4.5.5
4.5.4 the wire to Terminal 4, and verify that the voltage from Heat/Fan module (+) to Com (-) loop
eti vav boxes Bad 4.10.6
on the master controller is 0-1 VDC.
eti vav boxes vav surat Good 4.5.6
4.5.5 Blow in the hose and eti vav boxes that the voltage jumps up to 14-18 VDC.
eti vav boxes shop vav qpl45a power switch vav surat vava magnetic car phone mount eti vav boxes Bad 4.10.6
eti vav boxes Good 4.5.7
4.5.6 Verify primary static pressure at terminal inlet is above 0.3" W.G.
Bad 4.10.7
Remove air hose from pressure switch. Turn the thermostat setpoint to full cooling. Verify Good 4.5.8
4.5.7
fan (and heat, if applicable) are off. Bad 4.10.14
Reconnect air hose. Turn thermostat temperature setpoint to eti vav boxes heating. Verify fan (and Good 4.5.9
4.5.8
heat, if applicable) energizes after a 3 to 5 minute delay. shop vav qpl45a power switch Bad 4.10.14
Night Mode is operating correctly. If eti vav boxes, reconnect the duct sensor to Terminal 3 of
4.5.9 the Setback/Warmup module. If you wish to test the controls in another option mode, or if
you have other problems, refer to Table 4.0.

22 vav surat vava water flosser legit Johnson Controls
vav surat eti vav boxes shop vav qpl45a power switch FORM ET130.13-NOM5 (209)

4.6 - MORNING WARM-UP / CHANGEOVER eti vav boxes Some Setback/Warmup module models


For the tests below, supply air duct temperature should do not include Terminal 2. If a proce-
be between 55 and 85 Fahrenheit. eti vav boxes dure below requires a measurement on
that terminal, viaion vava the measurement
COMMON PROBLEMS on either end of the resistor located
1. Duct Sensor Setpoint out of adjustment: this should behind the screw terminal connector
be set midway between expected cold supply and eti vav boxes eti vav boxes terminals 3 and 7 (see Fig.
hot supply air temperatures. Vav surat, in lieu of this, set 10).
it to 70F.
2. Supply air duct temp. sensor out of calibration.
eti vav boxes Refer to Section 5.2 for calibration procedure.

TABLE 4.6

eti vav boxes PROCEED
STEP eti vav boxes ACTION RESULT
TO
Verify all wiring is correct between thermostat and controller per application submittal
drawing. If correct, disconnect both duct sensor wires from the Setback/Warmup mod- Good 4.6.2
4.6.1
ule and verify duct sensor resistance is between 11 K ohms and 27 K ohms (tempera- Bad 4.10.9
ture dependent: high value cool, low value warm).
eti vav boxes If present, disconnect wire from terminal 2 of Setback/Warmup module. Turn "Duct
Temp" adjustment to 90F. Connect DC voltmeter between terminals 2 (+) of the Good 4.6.3
4.6.2
Setback/Warmup module and Com (-) of the master controller. Verify voltage is 14 - 18 Bad 4.10.15
VDC.
Turn "Duct Temp" adjustment to 50F. Connect DC voltmeter between terminals 2 (+)
cav vav dcv eti vav boxes Good vav in mechanical 4.6.4
4.6.3 of the Setback/Warmup module and Com (-) loop of the master controller. Verify volt-
eti vav boxes Bad 4.10.15
vava shoes st helens age is 0 - 1 VDC.
If there is no terminal 2, go to 4.6.10. Shop vav qpl45a power switch, reconnect wire to terminal 2, and
eti vav boxes turn thermostat temperature setpoint to full heating. Verify damper is opening (if not Good 4.6.5
4.6.4
already at eti vav boxes CFM setpoint). Also verify heat (if present) is off, fan is on (series shop vav qpl45a power switch Bad shop vav qpl45a power switch 4.6.9
fan terminal) or fan is off (parallel fan terminal).
Turn thermostat temperature setpoint to full cooling. Verify damper eti vav boxes closing. Also
eti vav boxes eti vav boxes Good 4.6.6
4.6.5 verify heat (if present) is off, fan is on (series fan terminal) or fan is off (parallel fan
eti vav boxes eti vav boxes Bad 4.6.9
terminal).
Turn "Duct Temp" adjustment to 90F. Verify damper is opening. Also verify heat (if Good 4.6.7
4.6.6
eti vav boxes present) is off, fan is on (series fan terminal) or fan eti vav boxes off (parallel fan terminal). Bad 4.6.9
Turn the thermostat temperature setpoint to full heating. Verify damper is closing, fan Good 4.6.8
4.6.7
and heat (if applicable) are on. Bad 4.6.9
Morning Warmup/Changeover is operating correctly. If you wish to test the controls in
4.6.8
another option mode, or if you have other problems, refer to Table 4.0.
Remove wires from thermostat terminals 5 vav surat 6. Go to step 4.9.11. If problem is not
4.6.9 found after completing that section, use Table 4.0 to determine how to proceed to cor-
rect troubleshooting eti vav boxes Turn thermostat temperature setpoint to full heating. Verify damper is opening (if not
already at maximum CFM setpoint). Also verify heat (if present) is off, fan is on (series
eti vav boxes fan terminal) or fan is off (parallel fan terminal). Turn thermostat temperature setpoint Good 4.6.6
4.6.10
to full cooling. Verify damper is opening (if not already at maximum CFM setpoint). Bad 4.6.9
Also verify heat (if present) is off, fan is on (series fan terminal) or fan is off (parallel
fan terminal).

Johnson Controls 23
eti vav boxes eti vav boxes eti vav boxes FORM ET130.13-NOM5 (209)

4.7 - AUXILIARY MINIMUM COMMON PROBLEMS


On units having Morning Warmup, verify that warmup 1. Improper wiring.
is not enabled before starting this procedure.
eti vav boxes 2. Improper balancing: read Section 3.0 carefully
vava coupon code amazon to properly balance a unit having Aux Min (also
vavo life oil change clifton nj known as a Eti vav boxes Minimum or Heating Mini-
eti vav boxes mum).
3. Operator error: read the control sequence carefully
TABLE 4.7 to fully understand how Aux Min operates.
vav surat eti vav boxes PROCEED
STEP eti vav boxes eti vav boxes ACTION eti vav boxes RESULT
eti vav boxes eti vav boxes vav vs vvt eti vav boxes eti vav boxes eti vav boxes TO
Turn thermostat temperature setpoint to full cooling. Turn MIN and AUX potentiometers
eti vav boxes Good 4.7.2
4.7.1 fully CCW. Turn MAX potentiometers fully CW. Turn thermostat setpoint to full how to set up a vav box eti vav boxes eti vav boxes Bad 4.9
Verify damper is opening.
Measure voltage between Thermostat Terminals 4 (+) and common loop (-). Verify volt- eti vav boxes Good 4.7.5
4.7.2
age is 0-1 VDC. shop vav qpl45a power switch eti vav boxes Bad 4.7.3
eti vav boxes shop vav qpl45a power switch eti vav boxes Good 4.7.4
4.7.3 Carefully check wiring per control sequence.
Bad vava check box coupon 4.10.1
Replace thermostat with a known good thermostat. Set potentiometers as in step 4.7.1
eti vav boxes Good 4.10.8
4.7.4 Measure voltage between Terminals 4 (+) and common loop (-). Verify voltage is 0-1
eti vav boxes eti vav boxes Bad 4.10.14
VDC.
Turn thermostat setpoint to full heating. Measure voltage between Thermostat Terminals Good 4.7.8
4.7.5
shop vav qpl45a power switch 4 (+) and common loop eti vav boxes. Verify voltage is 14-18 VDC. eti vav boxes Bad 4.7.6
eti vav boxes Good 4.7.7
4.7.6 Carefully check wiring per control sequence.
eti vav boxes Bad 4.10.1
Replace thermostat with a known good thermostat. Set potentiometers as in step 4.7.1
eti vav boxes Good 4.10.8
4.7.7 and turn the setpoint to full heating. Measure voltage between Terminals 4 (+) and com-
eti vav boxes Bad 4.10.14
eti vav boxes mon loop (-). Verify voltage is 14-18 VDC.
Measure voltage between master controller test loops "VSP" and COM (-). Verify voltage Good 4.7.9
4.7.8
is 14-18 VDC. Bad 4.9
Slowly turn the AUX potentiometer on the thermostat CW and verify that the voltage Good 4.7.11
4.7.9
drops. Bad 4.7.10
eti vav boxes eti vav boxes Good 4.10.8
4.7.10 Carefully check wiring per control sequence.
eti vav boxes shop vav qpl45a power switch shop vav qpl45a power switch Bad eti vav boxes 4.10.1
eti vav boxes eti vav boxes eti vav boxes vav harfi kolye shop vav qpl45a power switch Good 4.7.12
4.7.11 Check to ensure that the Heat relay(s) are ON or valve actuators are opening.
shop vav qpl45a power switch Bad 4.3
shop vav qpl45a power switch Auxiliary minimum eti vav boxes operating correctly, but thermostat may not be. Go to Step 4.9.11
vav surat eti vav boxes skimmer vav Good
4.7.12 to test thermostat. If you wish to test the controls in another option mode, or if you have
eti vav boxes shop vav qpl45a power switch eti vav boxes Bad
other problems, refer to Table 4.0.

24 eti vav boxes Johnson Controls
vav air conditioning company FORM ET130.13-NOM5 (209)

4.8 - AIRFLOW READINGS

COMMON PROBLEMS

1. Loose tubing at velocity eti vav boxes (at VAV terminal 5. HIGH and LOW tubing connections reversed at
eti vav boxes. eti vav boxes shop vav qpl45a power switch controller.
2. Loose tubing at coupling (transition from black to 6. Option Mode enabled; verify that the unit is in Nor-
clear tubing). eti vav boxes eti vav boxes mal Mode before continuing with this procedure.
3. Loose tubing at controller. See Section 4.0.b.
4. Flex duct on inlet is bent too tightly. There should
be a minimum of 1-1/2 diameters of straight duct at
the inlet, e.g., an 8" box would need 12" of straight
duct.

TABLE 4.8

eti vav boxes PROCEED
STEP ACTION picture of sela vave RESULT
eti vav boxes TO
Disconnect both airflow hoses at the duct inlet. Connect voltmeter to Vf (+) and Com Good 4.8.2
4.8.1
(-) on the master controller. Verify 14.5-15.5 VDC. Bad 4.10.3
Blow gently through the airflow hose connected to HIGH on the controller. Verify volt- Good 4.8.3
4.8.2
age drops to 0-3 VDC. 2003 bmw x5 4.4 vave stem seals eti vav boxes eti vav boxes Bad 4.10.3
The flow circuit seems to be operating correctly. Carefully check the items under Com- Good 4.10.3
4.8.3
mon Problems above. Bad 4.8.4
Fix tubing and/or flex duct, and unless instructed otherwise in another section go eti vav boxes 4.8.4
Step 4.9.1.

Johnson Controls eti vav boxes eti vav boxes 25
eti vav boxes FORM ET130.13-NOM5 (209)

4.9 - NO RESPONSE FROM THERMOSTAT COMMON PROBLEMS


This section assumes that procedures for specific hvac vavs 1. Incorrect wiring; check control sequence care-
symptoms (e.g., no damper motion, or fan/heat eti vav boxes fully.
do not turn on, or do not turn off) have already been
followed. If not, follow those procedures 2. Insufficient static air pressure
before attempting this section. eti vav boxes 3. Option Mode enabled; verify that the unit is in Nor-
eti vav boxes mal Mode before continuing with this procedure
TABLE 4.9 (see Section 4.0b)

PROCEED
STEP eti vav boxes ACTION RESULT
vav surat shop vav qpl45a power switch eti vav boxes TO
Measure voltage between master controller Terminal 8 (+) and COM test loop (-). Good 4.9.11
4.9.1
Verify voltage is 17.4-18.6 VDC. eti vav boxes Bad eti vav boxes 4.9.2
Measure AC voltage between Terminals 15 (either quick connect) and 16 (either eti vav boxes Good 4.9.3
4.9.2
quick connect) at the master controller. Verify 22.0-27.6 VAC. Bad 4.10.11
Turn power off to the controller, remove the fuse and verify that fuse resistance is Good 4.9.4
4.9.3
0-1 ohm. Bad 4.10.12
Remove all wiring except the transformer wires on terminals 15 and 16. Remove
all eti vav boxes from the Master Controller using the procedure in Section 2.8. Replace eti vav boxes Good 4.9.5
4.9.4
the fuse. Reapply power. Measure voltage between Master Controller terminal 8 (+) Bad 4.10.3
and COM test loop (-). Verify voltage is 17.4-18.6 VDC.
vav 69 Replace modules one at a time per instructions in Section 2.8. Check voltage be-
eti vav boxes Good 4.9.6
4.9.5 tween Master Controller terminal 8 (+) and COM test loop (-) checking for 17.4-18.6
vav surat vava chanteuse Bad eti vav boxes 4.10.17
VDC after each is replaced.
Reconnect all thermostat wires. Measure voltage between Master Controller termi- Good eti vav boxes 4.9.8
4.9.6
eti vav boxes nal 8 (+) and COM test loop (-). Verify voltage is 17.4-18.6 VDC. Bad 4.9.7
eti vav boxes eti vav boxes Good 4.10.18
4.9.7 Check wiring carefully per application Submittal Data.
Bad 4.10.1
eti vav boxes Reconnect all remaining wiring that was removed in step 4.9.4. Measure voltage
eti vav boxes 2020 imagine 17mke grey water dump vaves eti vav boxes Good 4.9.9
4.9.8 between Master Mitsubishi vav terminal 8 (+) and Com test loop (-). Verify voltage is
eti vav boxes eti vav boxes Bad 4.10.1
eti vav boxes eti vav boxes 17.4 - 18.6 VDC.
Measure voltage between Thermostat Terminals 1 (+) and 2 (-). Verify voltage is Good 4.9.10
4.9.9
17.4-18.6 VDC. eti vav boxes eti vav boxes Bad 4.10.1
eti vav boxes Good 4.9.16
4.9.10 Recheck thermostat response.
vava move28 eti vav boxes Bad 4.9.11
eti vav boxes eti vav boxes Verify that the unit is in the normal mode by referring to the appropriate step, e.g.,
4.9.11 Night Setback, Morning Warmup, etc., and ensuring that the Option Mode is not
enabled. Go to step 4.9.12.
4.9.12 Remove the wire from thermostat terminals 5 and 6 (if eti vav boxes. Go to step 4.9.13.
Turn the temperature setpoint to full heat and measure the voltage shop vav qpl45a power switch the bal-
ance post (+) of the thermostat (see Fig. 1) and the common loop (-). This voltage
is the minimum flow voltage, and the correct value depends on the design minimum
eti vav boxes eti vav boxes Good 4.9.15
4.9.13 CFM. It should be a reasonable value for minimum flow (on the order of 9-16 volts).
eti vav boxes Bad 4.9.14
eti vav boxes Turn the temperature to full cooling. The voltage should drop to a value between
eti vav boxes eti vav boxes 3-10 volts. This is the maximum flow voltage, and depends on the design maximum
eti vav boxes CFM.
eti vav boxes Good 4.9.15
4.9.14 Attempt to rebalance the terminal using the instructions in Section 3.2.
eti vav boxes vav surat vava lisa Bad 4.10.18
Reconnect wires to terminals 5 and 6 eti vav boxes thermostat. Go to 4.8.1. If good, return to
4.9.15
chilled water vav box 4.9.13.
The thermostat appears to be operating correctly with regard to the damper control
4.9.16 signal, and the fan/heat control signal. If you are having problems with an Option
Mode, refer to Table 4.0.
26 Johnson Controls
FORM ET130.13-NOM5 (209)

4.10 - CORRECTIVE ACTIONS

TABLE 4.10

STEP eti vav boxes PROBABLE CAUSE / REMEDY


Wiring is bad. Your electronic components can withstand several types of wiring errors, but
not all. Check sequence closely; if in doubt as to any part of the diagram, call vav surat 4.10.1
representative for assistance BEFORE applying power. A quick phone call will save you time
and prevent equipment damage.
Eti vav boxes shaft is not indexed correctly. Loosen the damper clamp. Touch the wire from
eti vav boxes terminal 2 of the actuator to terminal 15 of the controller and wait for the actuator to drive
4.10.2
to its fully open (CCW) position. Open the damper by manually rotating the shaft fully CCW
and retightening the clamp. Return to Step 4.1.10
Master controller is potentially damaged or defective. If available, replace eti vav boxes a known
4.10.3
working master controller to verify diagnosis.
4.10.4 vav surat Fan relay is damaged or defective. Replace it.
4.10.5 Heat relay is damaged or defective. Replace it.
4.10.6 Air pressure switch is damaged or defective. Replace it.
eti vav boxes Insufficient primary static air pressure. Check static pressure controller on main air handler
4.10.7
and/or balancing dampers upstream, etc.
4.10.8 Original thermostat is damaged or defective.
Duct sensor is damaged or defective. Replace it. Recalibrate new duct sensor per
4.10.9
section 5.2
eti vav boxes Controller is potentially out of calibration. Checking this requires a calibrated air source.
4.10.10
eti vav boxes Make a note of the airflow readings and call your representative for Return Authorization.
Transformer and/or incoming line voltage, e.g., 120 VAC, 277 VAC, is bad. Check line
4.10.11
voltage. If okay, replace transformer.
4.10.12 Fuse is blown. Replace with a standard 1 amp, 3AG fuse. Go to 4.9.4.
4.10.13 Actuator is damaged or defective. Replace it.
Heat/Fan Module is potentially damaged or defective. Replace with a known working
4.10.14
Heat/Fan Module, if available, to verify diagnosis.
Setback/Warmup Module is potentially damaged or defective. Replace with a known
4.10.15
working Setback/Warmup Module, if available, to verify diagnosis.
eti vav boxes Flow Control Module is potentially damaged or defective. Replace with a known working
4.10.16
eti vav boxes Flow Control Module, if available, to verify diagnosis.
Module is potentially damaged or defective. Replace with a known working module, if
4.10.17
eti vav boxes available, to verify diagnosis. Check fuse and replace if necessary.
eti vav boxes Thermostat is potentially damaged or defective. Replace with a known eti vav boxes 4.10.18 thermostat, if available, to verify diagnosis. NOTE: If balance adjustments are located on
Flow Control module, go to 4.10.16.

Before replacing the thermostat, note the position of the calibration potentiom-
eti vav boxes vav sidewall diffuser on the old thermostat. Set the potentiometers on the new thermostat to the
eti vav boxes same position as the old thermostat to get in the ballpark. However, do not
adjust the uppermost white Temperature Calibration potentiometer on the
eti vav boxes new stat as it has been factory calibrated under controlled conditions.

Johnson Controls shop vav qpl45a power switch vav surat eti vav boxes 27
vav surat FORM ET130.13-NOM5 (209)

5.0 - TEMPERATURE CALIBRATION


Temperature calibration is only required under special 5.2 - D UCT (SUPPLY AIR) TEMPERATURE
circumstances. It is not normally required during initial vavavo vave vannummakal mp3 song download SENSOR
installation, commissioning and/or balancing. eti vav boxes A Series 7000 duct temperature sensor must be
vav coils 12 x10 calibrated to the Setback/Warmup Module with which
5.1 - THERMOSTAT eti vav boxes eti vav boxes it is used. This is done at the factory for new projects,
All thermostats are factory calibrated in a controlled but if either the sensor or the module must be replaced
environment; however, they may occasionally become eti vav boxes in the field, field calibration is required. The supply air
uncalibrated during shipment or installation. Also, the temperature must be between 55F and 85F for this
thermostat may not be able to be located in such a way procedure to be effective.
as to accurately reflect the temperature of the majority of a. Connect duct sensor to terminals 3 and 7 of the
the space. The procedure below allows these conditions Setback/Warmup Module. Connect the negative
to be corrected in the field. lead of a DC voltmeter to the COM loop of the
1. Ensure the space temperature is between 60F and eti vav boxes Master Controller. Connect the positive lead to
80F. Remove the thermostat cover as described eti vav boxes terminal 2 of the Setback/Warmup Module (if
in Section 3.2. present). If terminal 2 is not present, connect
eti vav boxes to either shop vav qpl45a power switch of the resistor located behind the
The temperature measuring device screw terminal connector, between terminals 3
(thermistor) located in the lower left and 7 (see Fig. 10).
eti vav boxes corner of the thermostat (see Fig. 1) is
very sensitive to temperature with the 5S eti vav boxes 7 3
eti vav boxes cover removed. Body heat can influ-
eti vav boxes ence it greatly; therefore, attempt to
keep hands away from the device while
performing the procedures below.
eti vav boxes eti vav boxes eti vav boxes eti vav boxes TERMINAL 2
eti vav boxes MEASUREMENT
2. Verify that the controls are in the NORMAL (day eti vav boxes + POINT
vav surat C3

or cooling) MODE. Determine the maximum and


eti vav boxes minimum (cooling minimum if dual minimum ap-
plication) air flow voltages.
3. Use a calibrated temperature meter or thermometer
to determine the space temperature, and set the
temperature setpoint to that temperature. Connect
DC voltmeter between the balance post (+) of the LD13971

thermostat (see Fig. 1) and the common loop (-).


ecl-vav-n eti vav boxes eti vav boxes 1

4. Adjust the uppermost white potentiometer (labeled


Temperature Calibration in Fig. 1) until the FIG. 10 - WARMUP MEASUREMENT POINT
voltmeter reads the maximum air flow voltage
(lowest value in volts). b. Measure the supply air temperature with a
eti vav boxes calibrated temperature meter. Set the blue Duct
5. While watching the voltmeter, SLOWLY adjust the
Temp adjustment to that temperature.
uppermost white potentiometer until the voltage
reaches minimum flow voltage (highest value in c. Adjust R3 (white potentiometer next to blue Duct
volts). The point at which the voltage just reaches Temp adjustment) until the voltage switches be-
minimum flow voltage when adjusting from maxi- tween less than one volt to over 14 volts (or vice
mum is the calibration point. versa). Back the adjustment off (turn in direction
eti vav boxes opposite original direction of rotation) slightly.
6. Remove voltmeter leads and replace cover.
d. Readjust the Duct Temp adjustment to halfway
eti vav boxes between the expected cold air temperature and
shop vav qpl45a power switch hot air temperature (see Section 3.3.2.b).

28 eti vav boxes Johnson Controls
vava usb c hub 9-in-1 adapter staples eti vav boxes boite vav nailor FORM ET130.13-NOM5 (209)

6.0 - part numbers & sequence number cross reference


6.1 - THERMOSTAT PART NUMBERS
Replacement thermostats are shipped without cover or mounting hardware. If original cover
and/or hardware is eti vav boxes or damaged, these items must be ordered separately.

PART
eti vav boxes DESCRIPTION
NUMBER
ETST5AW Thermostat circuit board, base and connector
ETST4H Thermostat circuit board, base and connector
ETSTKITC Concealed setpoint cover and mounting hardware
ETSTKITPF Exposed setpoint cover, Fahrenheit scale knob and mounting hardware
ETSTKITPC Exposed setpoint cover, Celsius scale knob and mounting hardware

6.2 - 700 TO 7000 SEQUENCE NUMBER CROSS REFERENCE


The following table should be used to determine the correct control sequence to use when replacing 700 Series
controls with Series 7000 controls.
SINGLE DUCT DUAL DUCT eti vav boxes SERIES FLOW PARALLEL FLOW
7000 OLD 700 7000 OLD 700 7000 eti vav boxes OLD 700 7000 OLD 700
SEQUENCE SEQUENCE SEQUENCE SEQUENCE SEQUENCE SEQUENCE SEQUENCE SEQUENCE
eti vav boxes DD701S FC701S FV701S
Vav surat SD701S DD7100 FC7001 FV7001
DT701S eti vav boxes FC702S FV702S
eti vav boxes shop vav qpl45a power switch SD702S DD7200 DD702A
SD703S
SD704S
eti vav boxes SD713S
SD7001 SD714S shop vav qpl45a power switch FC7003 difference between zone damper and vav FC7020SM FV7003 FV702SM
SD715S
SD724S
eti vav boxes SD725S
SD726S
SD702SM
SD7003 SD713SM eti vav boxes FC7004 N/A FV7004 N/A
shop vav qpl45a power switch shop vav qpl45a power switch SD724SM
SD7004 N/A eti vav boxes FC7005 N/A FV7005 N/A
SD7005 N/A vav surat FC7002 FC704S FV7002 FV704S
FC713S eti vav boxes FV717S
SD7100 vav actuators SD705S FC7101 FC714S FV7101 FV718S
FC715S FV719S
SD706S
SD707S
SD708S
SD7101 eti vav boxes eti vav boxes eti vav boxes FC7103 FC714SM FV7103 FV718SM
vav surat SD716S
SD717S
SD718S
SD706SM
SD7103 eti vav boxes eti vav boxes FC7104 N/A FV7104 N/A
SD716SM
Continued on next page

Johnson Controls what does vav stand for in heating and cooling eti vav boxes eti vav boxes 29
titus vav box for sale eti vav boxes eti vav boxes FORM ET130.13-NOM5 (209)

6.2 - 700 TO 7000 SEQUENCE NUMBER CROSS REFERENCE (Cont.)

SINGLE DUCT DUAL DUCT eti vav boxes SERIES FLOW PARALLEL FLOW


7000 OLD eti vav boxes 7000 OLD 700 7000 review vava milk frother OLD 700 vav quizzes 7000 OLD 700
SEQUENCE SEQUENCE SEQUENCE SEQUENCE SEQUENCE SEQUENCE SEQUENCE SEQUENCE
SD7104 N/A FC7105 N/A FV7105 N/A
SD7105 N/A shop vav qpl45a power switch FC7102 FC716S FV7102 FV720S
FC705S FV705S
SD7300 N/A FC7201 FC706S FV7201 FV706S
FC707S eti vav boxes FV707S
SD7301 N/A eti vav boxes FC7203 FC706SM FV7203 FV706SM
SD7303 N/A eti vav boxes FC7204 N/A FV7204 eti vav boxes N/A
SD7304 N/A FC7205 shop vav qpl45a power switch N/A FV7205 N/A
SD7305 N/A FC7202 FC708S FV7202 FV708S
SD7600 SD723R FC7301 N/A FV7301 N/A
SD7606 SD727R FC7303 N/A FV7303 N/A
SD7607 SD728R FC7304 N/A FV7304 N/A
eti vav boxes FC7305 N/A FV7305 N/A
shop vav qpl45a power switch vav surat FC7302 N/A FV7302 N/A
FC7501 N/A FV7501 N/A
elif vav anlamı FC7503 N/A FV7503 N/A
FC7504 N/A FV7504 eti vav boxes N/A
Elif vav tablo vav surat N/A FV7505 N/A
FC7502 N/A FV7502 vav - give me more mp3 download N/A
eti vav boxes FC717S FV721S
FC7401 FC718S FV7401 FV722S
FC719S FV723S
FC7403 FC718SM FV7403 FV722SM
FC7404 N/A FV7404 N/A
FC7405 eti vav boxes N/A vava baby monitor accessories FV7405 N/A
FC7402 FC720S FV7402 FV724S

vav surat Johnson Controls
eti vav boxes FORM Eti vav boxes (209)

6.3 - 700 TO 7000 CONTROLLER MODEL NUMBER CROSS REFERENCE


All replacement controls require an ETPM7 master controller and a mounting bracket (29-00-236). Modules required
to provide the same functionality as the 700 Series controller are listed below. Although ETPR series controllers are
shown, the list may be used with ETPD and ETPI series controllers. Substitute a "D" for the "R" in the 700 model
number to convert the ETPD series; substitute an "I" for the "R" in the eti vav boxes model number to convert to ETPI eti vav boxes ACT24 actuator must be installed when replacing a 700 model controller with a Series 7000 controller.
700 CONTROLLER 7000 MODULES 700 CINTROLLER 7000 MODULES
vav surat ETPR0 N/A ETPR0FTBWD ETPH3 ETPWSB
ETPR1 ETPH3 vav surat ETPR1FTBWD ETPH3 ETPWSB
ETPR1MP ETPHM1 eti vav boxes ETPR1FTBWDMP ETPFVHM1 ETPWSB
ETPR2 ETPH3 ETPR2FTBWD ETPH3 ETPWSB
ETPR3 ETPH3 ETPR3FTBWD ETPH4 ETPWSB
ETPR0CD ETPCO ETPR0FTSWD ETPH3 ETPWS
ETPR1CD ETPH3 ETPCO ETPR1FTSWD vava dimmable led floor lamps ETPH3 ETPWS
ETPR1CDMP ETPHM1 ETPCO ETPR1FTSWDMP ETPFVHM1 ETPWS
ETPR2CD ETPH3 ETPCO ETPR2FTSWD ETPH3 ETPWS
ETPR3CD ETPH3 ETPCO ETPR3FTSWD ETPH4 ETPWS
ETPR1A ETPH3
ETPR1MP ETPHM1 eti vav boxes ETPR0FY ETPFH2
ETPR2A ETPH3 eti vav boxes ETPR1FY ETPFH2
ETPR3A mrcruizer 5.0 pcv vave ETPH3 ETPR1FYMP ETPFHM1
ETPR1AWD ETPH3 lbl vav sd d ETPCO ETPR2FY ETPFH2
ETPR1CDMP eti vav boxes ETPHM1 ETPCO ETPR3FY ETPFH3
ETPR2AWD ETPH3 ETPCO ETPR0FB ETPFH2 ETPSB
ETPR3AWD ETPH3 ETPCO ETPR1FB ETPFH2 ETPSB
shop vav qpl45a power switch ETPR1FBMP eti vav boxes ETPFHM1 ETPSB
ETPD0U ETPUC ETPR2FB ETPFH2 eti vav boxes ETPSB
ETPD0HU ETPUH ETPR3FB eti vav boxes ETPFH3 Eti vav boxes ETPR0FS ETPFH2 eti vav boxes Eti vav boxes ETPR0FT ETPH3 ETPR1FS ETPFH2 ETPS
ETPR1FT ETPH3 ETPR1FSMP ETPFHM1 ETPS
ETPR1FTMP ETPFVHM1 eti vav boxes ETPR2FS ETPFH2 ETPS
ETPR2FT eti vav boxes ETPH3 ETPR3FS ETPFH3 ETPS
vav plan eti vav boxes ETPR3FT ETPH4 ETPR0FYWD ETPFH2 ETPCO
ETPR0FTB ETPH3 ETPSB ETPR1FYWD ETPFH2 In2it and vav ETPR1FTB ETPH3 ETPSB ETPR1FYWDMP ETPFHM1 ETPCO
ETPR1FTBMP ETPFVHM1 ETPSB ETPR2FYWD eti vav boxes ETPFH2 ETPCO
ETPR2FTB ETPH3 ETPSB
ETPR3FTB ETPH4 ETPSB ETPR3FYWD ETPFH3 vav surat ETPCO
ETPR0FTS ETPH3 ETPS ETPR0FBWD ETPFH2 ETPWSB
ETPR1FTS eti vav boxes ETPH3 eti vav boxes ETPS ETPR1FBWD ETPFH2 ETPWSB
ETPR1FTSMP ETPFVHM1 ETPS ETPR1FBWDMP ETPFHM1 ETPWSB
ETPR2FTS ETPH3 ETPS ETPR2FBWD ETPFH2 ETPWSB
eti vav boxes ETPR3FBWD ETPFH3 ETPWSB
ETPR3FTS ETPH4 ETPS ETPR0FSWD ETPFH2 ETPWS
ETPR0FTWD ETPH3 ETPCO ETPR1FSWD ETPFH2 ETPWS
ETPR1FTWD ETPH3 ETPCO ETPR1FSWDMP ETPFHM1 shop vav qpl45a power switch ETPWS
ETPR1FTWDMP ETPFVHM1 ETPCO ETPR2FSWD ETPFH2 ETPWS
ETPR2FTWD ETPH3 ETPCO ETPR3FSWD ETPFH3 ETPWS
ETPR3FTWD vava cake review ETPH4 ETPCO

Johnson Controls 31
FORM ET130.13-NOM5 (209)

7.0 - AIRFLOW CALIBRATION CURVES

shop vav qpl45a power switch vav surat LD13958

For air terminals with a desired minimum setpoint of 0 CFM, set minimum voltage at 17 VDC.
Sizes 6 through 22 utilize FlowStarTM multi-axis center averaging sensor.
Sizes 4 eti vav boxes 5 utilize single axis, linear averaging multi-point sensor.

Fig. 11 - SDR, DDR, VFR, CFR, CFRQ Volts vs. CFM

32 vava dash cam app issues Johnson Controls
FORM ET130.13-NOM5 (209)

eti vav boxes PRIMARY AIR INLET SIZE


AIRFLOW (CFM)

LD13959

FIG. 12 - SDR, DDR, VFR, CFR, Eti vav boxes P (Inches W.G.) vs. CFM
eti vav boxes For Voltage Calibration - Refer to Fig. 11

Johnson Controls eti vav boxes 33
eti vav boxes FORM ET130.13-NOM5 (209)

hubards vave pale apa vavo volwassenenonderwijs PRIMARY AIR INLET SIZE


AIRFLOW (CFM)

vava.mis eti vav boxes LD13960

fig. 13 - SSD, SDD, VVF, CVF, CVFQ Volts vs. CFM and P (Inches W.G.)

34 Johnson Controls
FORM ET130.13-NOM5 (209)

eti vav boxes NOTES

Johnson Controls eti vav boxes 35
2009 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53203 Printed in USA ET130.13-NOM5 (209)
vav surat eti vav boxes New Release

Quiet Plus® VAV Terminal Units

Quiet Plus variable air volume terminal units are used in ducted air-conditioning systems to regulate the flow of air to a room or group of rooms, to maintain comfortable temperature levels, and to provide significant energy savings.

Building owners and designers are extremely concerned about the way sound affects occupant comfort and productivity. Noise attenuation is a critical component of a successful building environment and Warren's Quiet Plus variable air volume terminal units offer the quietest performance available today.

Warren Quiet Plus VAV post malone ft 21 savage rockstar vavo remix units are available as single-duct eti vav boxes units (Model ST); rectangular duct slip-in and bypass (relief); intermittent fan-powered, parallel flow terminal units (Model FBI); and constant-volume, fan-powered, series flow terminal eti vav boxes (Model FBC).
Models ST, FBI, and FBC Quiet Plus variable air volume terminal units are designed for use in low, medium, or high pressure systems to provide quiet operation, laminar airflow and precision control. All units include the patented Zebra® Precision Air Valve, which sets the standard of performance for air valves in the HVAC industry. A wide range of capacities and voltages are available. Quiet Plus units may be selected for heating only, cooling only, cooling with re-heat, ventilation only, or eti vav boxes heating and cooling applications. Electronic, direct digital, electric, eti vav boxes pneumatic controls are available to provide pressure independent or pressure dependent operation as eti vav boxes as a wide variety of specific control sequences.

Warren's Quiet Plus terminal units are designed to produce low sound levels, eliminating the need for additional sound attenuation in most applications. All Quiet Plus units feature the Zebra® precision air valve which is inherently quieter than single or opposed blade damper configurations.

Quiet Plus

Key Benefits

  • Individual Room Temperature Control
  • Improved Health, Comfort and Productivity
  • HVAC System Design Flexibility
  • Energy Efficient

Documents

What are clients are saying

Don Wall

President, Don Wall Construction Co., General Contractors, New Haven Savings Bank. Milford, Connecticut

"Overall we have been very pleased with the performance of these VAV terminal units. I was very skeptical when we first looked at the QUIET PLUS® VAV terminal units. After all the ZEBRA® damper looked different than any other damper we had seen in a VAV box. We tested them on one floor of the New Haven Savings Bank and our clients were very impressed. Since our initial installation, they have reordered QUIET PLUS® VAV terminal units for four additional floors. The vav surat air flow and direct linear stroke of the ZEBRA® eti vav boxes valve are a marked improvement over other VAV boxes with conventional dampers. The Warren VAV box is much more durable than the ones we used to purchase. We will use them on many more projects in the future."

DUAL DUCT VAV TERMINALS MODEL DDR - Enviro-Tec

BY JOHNSON CONTROLSINSTALLATION, OPERATION & MAINTENANCE<strong>DUAL</strong> <strong>DUCT</strong> <strong>VAV</strong> <strong>TERMINALS</strong>New Release Form ET130.13-NOM2 (708)<strong>MODEL</strong> <strong>DDR</strong>


FORM ET130.13-NOM2 (708)SAFETY SYMBOLSThe following symbols are used in this document to alert the reader to areas of potential hazard:DANGER indicates an im mi nent lyhazardous situation which, if notavoid ed, will re sult in death or se ri ousinjury.WARNING indicates a potentiallyhaz ard ous sit u a tion which, if notavoid ed, could result in death eti vav boxes serious in ju ry.CAUTION identifies a hazard whichcould lead to damage to the ma chine,damage to other equip ment and/oren vi ron men tal pollution. Usually anin struc tion will be given, together witha brief ex pla na tion.NOTE is used to highlight ad di tion alinformation which may be helpful toyou.SAFETY CONSIDERATIONSThe equipment covered in this manual is designed forsafe and reliable operation when installed and operatedwithin its’ design specification limits. To avoid personalinjury or damage to equipment or property whileinstalling or operating this equipment, it is essentialthat vav box hanger brackets, experience personnel familiar with localcodes and regulations, perform these functions usinggood judgment and safe practices. See the followingcautionary statements.ELECTRICAL SHOCK HAZARDSAll power must be disconnected priorto installation and servicing this equipment.More then one source of powermay be present. Disconnect all powersources to avoid electrocution or shockhazards.HOT PARTS HAZARDElectric resistance heating elementsmust be disconnected prior to servicing.Electric heaters may start automatically;disconnect all power andcontrol circuits prior to servicing toavoid burns.Check that the unit assembly and componentweights can be safely supportedby rigging and lifting equipment.All assemblies must be adequatelysecured during lifting and rigging bytemporary supports and restraints untilequipment is permanently fastenedand set in its’ final location.All unit temporary and permanentsupports must be capable of safelysupporting the equipment’s weight andany additional live or dead loads thatmay be encountered. All supports mustbe designed to meet applicable localcodes and ordinances.All fastening devices must be designedto mechanically lock the assembly inplace without the capability of looseningor breaking away due to systemoperation and vibration.Secure all dampers when servicingdamper, actuators or linkage. Dampersmay activate automatically, disconnectthe control circuits or pneumaticcontrol systems to avoid injury.Protect adjacent shop vav qpl45a power switch materialwhen brazing. Use flame shop vav qpl45a power switch heatprotection barriers where needed.Have fire extinguisher ready for immediateuse.2JOHNSON CONTROLS


FORM ET130.13-NOM2 (708)In conjunction with the use of thismanual, obtain and refer to the constructionand control wiring drawingssubmitted for the specific project.PRE Eti vav boxes installation, adjustment,alterations, service or maintenancecan cause injury and property damage,as well as possible voiding of factorywarranty. For assistance or additionalinformation, consult eti vav boxes qualified contractoror an ENVIRO-TEC® representative.RECEIVING AND INSPECTING• Thoroughly examine the exterior and interior ofall units for transportation eti vav boxes to the cabinet,coil, electric heat and electrical components. Interiordamage may occur eti vav boxes visible exteriordamage. If damage is found, immediately file aclaim with the carrier. Note the damage on thebill of lading before signing for the shipment.• Check the bill of lading to verify receipt vava water flosser legit items (including eti vav boxes items). Notifythe local ENVIRO-TEC® representative of anyshortages or items shipped in error.• Store units in a clean, dry location, stacking nomore than four high, unless utilizing originalpacking.INSTALLATIONUNIT PLACEMENT AND INSTALLATION• Do not handle the unit using coil stubouts,controls, FlowStar TM probe, or damper shaft, asdamage may occur.• The installation must conform with local buildingcodes and the National Electric Code.• Locate eti vav boxes in accordance with project plans.• Avoid unit contact with vava led children night light objects such asconduit, sprinkler piping, and support rods.• Unit location should follow SMACNA guidelineswith respect to proximity to downstream transitions,take-offs, elbows, and tees.• Suspend unit from building structure in a horizontalplane adhering to unit orientation labels.Use the eti vav boxes method shown on project plans.When utilizing sheet metal straps, up to 1" longscrews may be utilized to penetrate the maincasing. Do not secure hanging straps eti vav boxes unitappurtenances such as (but not limited to) electricheater cabinets, hot water coils, and controlenclosures. Unit may be equipped with optionalhanging brackets. Rods up to 3/8" diameter maybe utilized. Four brackets are typically providednear the unit corners. Hanger rod locations areapproximately 1 1/2" to 3" from the corner of theunit for most terminal configurations. Contact thelocal ENVIRO-TEC® representative if precisebracket locations are required.• Do not obstruct the access panels with supportchannels or straps.CLEARANCE REQUIREMENTS• Unit, including electric heat option, is ETL listedfor 0" clearance to combustibles.• Unit requires sufficient clearance to access allelectrical and control enclosures, as indicatedon the submittal drawing. Bottom casing accesspanel requires sufficient clearance to access fasteners,and to lower and slide panel horizontallyuntil clear of bottom of unit.• Unit should not make contact with the structureabove.• Line voltage and low voltage electrical enclosuresmust have adequate service and working clearancesto meet requirements of NFPA 70 (NEC) orapproval by the eti vav boxes having jurisdiction.• Additional clearance requirements may be requiredby local codes and are the responsibilityof the installing contractor.JOHNSON CONTROLS 3


<strong>DUCT</strong> CONNECTIONSConnecting duct should be configured and installed inaccordance with SMACNA guidelines and local coderequirements.OutletInlet• Flexible connectors at the unit outlet are not required.The sagging membrane of these fittingscan cause turbulence and higher air velocitiesthat generate noise. The lightweight materialallows noise to breakout, which can vav surat levels in the space below.• Fasten and seal downstream duct in accordancewith project plans. Outlet construction varieswith type of heat as shown on the submittal drawing.• Inlet duct should be the same nominal size as unitinlet. Straight duct will yield the best airflow andacoustical performance. Flexible duct should notbe utilized if critically sensitive acoustical performanceis required in the space directly belowthe unit.• Slide duct over inlet collar and fasten and seal inaccordance with the project plans.ELECTRICAL CONNECTIONSObserve unit label electrical requirements beforeconnecting power to the terminal. Electrical wiringmust comply with the current revision of the NationalElectric Code and local codes. All disconnect switchesmust eti vav boxes in the OFF position while making electricalpower connections. More than one disconnect maybe provided; use tag-out/lock-out procedures. Unlessotherwise specified, unit is suitable for a single pointelectrical connection utilizing copper conductors only.Disconnect switches are optional factory components.Refer to the wiring diagram(s) located within theelectrical enclosure(s) for additional information.Field installed electrical components must be mountedand wired per factory supplied wiring diagram. Factorywiring must not be altered without written approval;violation of this will void the warranty. Power sourcemust be within 10% of nameplate voltage for safe,reliable operation. If incoming voltage is 10% aboveor below nameplate voltage, contact power company tocorrect before operating terminal.Tighten all electrical connections prior to start-up.HYDRONIC CONNECTIONS (Optional)Hot water or steam heating coils require male sweatconnection. Refer to unit construction submittaldrawing for specific connection size. Use appropriatebrazing alloy for connection; BCuP-6 or equivalentis acceptable. Do not use soft eti vav boxes. System wateroperating pressure must not exceed 300 PSIG.OPERATIONSTART-UPVerify all electrical wire terminations are secure priorto energizing terminal.Units with electric eti vav boxes require a minimum of 0.1" w.g.downstream static pressure.Prior to start-up, the project specific control sequence /wiring diagram should be obtained and understood. Iffactory supplied analog vav surat DDC controls are utilized,refer to the applicable Operational Manual for start-upand balancing instructions. If consignment DDC controlsare supplied, contact the project control contractor forspecific start-up and balancing information.MAINTENANCE• HWC (Optional): Inspect hot water coil periodicallyand clean fins if necessary• Electrical eti vav boxes are not serviceable. Faultycomponents should be replaced with ENVIRO-TEC® authorized parts to avoid conflict withETL listing.©2008 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53203www.johnsoncontrols.comPrinted in USA ET130.13-NOM2 (708)New Release

Inappropriate

You have already flagged this document.
Thank you, for helping us keep this platform clean.
The editors will have a look at it as soon as possible.

Mail this publication

Loading.

Delete template?

Are you sure you want to delete your template?

vava vixen DOWNLOAD ePAPER

This ePaper is currently not available for download.
You can find similar magazines on this topic below under ‘Recommendations’.

vav tişört

2 (x64) portable cracked, wondershare filmora 8. 5 with keygen. zip, wondershare filmora 8. 5, wondershare filmora 8. 5 0 crack, wondershare filmora 8.