Using 2k will save tonns of VRAM and you're still having beautiful textures. The only where you can install 4k textures are interior cells (cavesmines etc) as interior use much less VRAM and some underground creature retextures (DwemerFalmer) due to the same reasons, as well as personal standalone armorsweapons mods. If your PC is not the strongest, or you just want to save some VRAM for something else - for example, latest ENB effects or 3D LODs from DyndoLOD - simply don't waste your memory on that.
Graphics quality will be just fine.
Enviro-tec products for zone control air conditioning meet the highest standards for quiet, efficient performance, and they’ve just introduced their next generation series flow fan boxes, the CRB and Eti vav boxes – both with significant improvements in acoustic performance.
DMR is proud to represent products from Enviro-tec, and we look forward to assisting you with your next project.
CRB Series - Series Flow, Fan-Powered, VAV Terminal Units
CRQ Series - Ultra-Quiet Series Flow, Fan-Powered VAV Terminals
ETI CRQ Ultra-Quiet vs. Competition
eti vav boxes TABLE OF CONTENTS
TABLE OF CONTENTS.2
safety symbols.3
1.0 - DEFINITIONS AND DESCRIPTIONS.4
eti vav boxes 1.1 - Thermostat. .4
adalaj vav stepwell 1.2 - Controller and Modules shop vav qpl45a power switch 1.3 - M9104 Series Floating Point Actuator .6
2.0 - installation.7
2.1 - Inspection .7
2.2 - Coordination of Trades.7
2.3 - Thermostat Eti vav boxes .7
2.4 - Wiring Installation .9
2.5 - Controller Wiring .9
2.6 - Thermostat Wiring .9
2.7 - Actuator Installation and Removal (Service Only) .9
eti vav boxes 2.8 - Module Installation and Removal.10
3.0 - COMMISSIONING AND BALANCING. 11
eti vav boxes 3.1 - Commissioning Procedure .11
3.2 vav surat Air Balancing Procedures .11
3.3 - Most Terminal Units .12
3.4 - Constant Primary Volume .13
3.5 - Dual Duct .14
4.0 - TROUBLESHOOTING.16
4.1 - DAMPER MOTION .17
4.2 - FAN .18
4.3 - ELECTRIC OR HOT WATER HEAT .19
4.4 - NIGHT SETBACK.21
eti vav boxes 4.5 - NIGHT MODE, COMMON PROBLEMS.22
4.6 - MORNING WARM-UP / CHANGEOVER.23
4.7 - AUXILIARY MINIMUM.24
4.8 - AIRFLOW READINGS.25
4.9 - NO RESPONSE FROM THERMOSTAT.26
4.10 - CORRECTIVE ACTIONS.27
5.0 - TEMPERATURE CALIBRATION .28
5.1 - THERMOSTAT .28
5.2 - D UCT (SUPPLY AIR) TEMPERATURE SENSOR .28
6.0 - part numbers & sequence number cross reference .29
6.1 - THERMOSTAT PART NUMBERS .29
6.2 - 700 TO 7000 SEQUENCE NUMBER CROSS REFERENCE .29
6.3 - 700 TO 7000 CONTROLLER MODEL NUMBER CROSS REFERENCE. .31
AIRFLOW CALIBRATION CURVES.32
2 eti vav boxes eti vav boxes vav box cfm chart Johnson Controls
FORM ET130.13-NOM5 (209)
safety symbols
The following symbols are used in this document to alert the reader to areas of potential hazard:
Johnson Controls shop vav qpl45a power switch 3
eti vav boxes FORM ET130.13-NOM5 (209)
eti vav boxes LD13964
FIG. 1 - THERMOSTAT
4 vav boxes titus team vav surat Johnson Controls
eti vav boxes eti vav boxes eti vav boxes FORM ET130.13-NOM5 (209)
b shop vav qpl45a power switch LD13963
kacie off shoulder top vava by joy han c
d
FIG. 2A - MASTER CONTROLLER
a. Thermostat Connectors. One-piece, captive vava 8 in 1 Series of modules incorporating a variety of fan and
screw terminal type for reliable connections. heat control applications including series or parallel
eti vav boxes fan control and/or staged, floating or proportional heat
b. 24 VAC and Control Output Connectors. Male,
control. This series can be identified by red color of
", quick connect type.
eti vav boxes circuit board.
c. Labels. Computer printed with serial number,
inventory number and CO number. eti vav boxes vav members shes mine Thermostat Sensor
24 VAC Fan and and Valve Actuator
eti vav boxes Heat Outputs vav surat Inputs/Outputs
1.2.1 - Master Controller (Fig. 2a)
Incorporates flow transducer, damper control and power
supply for modules. Sockets on modules slide onto
pins on master controller. A screw inserted through the
solder side of the master controller screws into threads
of a modules mounting bracket.
a. Flow Transducer. Device mounted on controller
which produces electronic signal proportional
vav vlive 190324 to flow. Fittings for this device are connected to
the inlet of the VAV terminal at the factory with
tubing.
b. A.C. Actuator Drive. When replacing a 700
Series DC drive controller, an M9104 Series
eti vav boxes actuator must be installed.
c. Desired Flow (VSP) Test Loop
d. Actual Flow (VF) Test Loop (located underneath
flow transducer)
e. Common (Com) Test Loop.
shop vav qpl45a power switch vav surat Deadband
eti vav boxes shop vav qpl45a power switch Mounting Bracket Adjustment
Master Controller eti vav boxes (Optional)
eti vav boxes Mating Sockets LD13969
Johnson Controls 5
eti vav boxes eti vav boxes eti vav boxes FORM ET130.13-NOM5 (209)
1.2.3 - Setback/Warmup Modules (Fig. 2c) vava definition 1.3 - M9104 SERIES FLOATING POINT
Series of modules incorporating night setback and/or Actuator (Fig. 3)
morning eti vav boxes. Depending on model, warmup may Direct-coupled, AC drive actuator. Incorporates current
be accomplished through cooling/heating (summer/ eti vav boxes shop vav qpl45a power switch limit circuitry that removes power from motor when a
winter) changeover, or setting damper to maximum mechanical stop is met. See Installation Instructions
airflow setpoint. This series can be identified by green (Part No. 34-636-1433) at www.enviro-tec.com.
color of circuit board.
Thermostat and Sensor
eti vav boxes Supply Air Changeover
Inputs/Outputs
Temperature Adjustment
Night
shop vav qpl45a power switch Setback
Offset
Adjustment
eti vav boxesM9104 SERIES Is the vava baby monitor wifi POINT ACTUATOR
rani ki vav note Maximum Airflow
eti vav boxes vav surat vav surat Adjustment
Auxiliary Minimum
Airflow Adjustment
Minimum Airflow
13400 bee cave parkway bee vave tx Adjustment
6 eti vav boxes eti vav boxes eti vav boxes Johnson Controls
FORM ET130.13-NOM5 (209)
eti vav boxes 2.0 - installation
FRONT eti vav boxes eti vav boxes SIDE
VIEW VIEW
MODULAR CONTROLLER
eti vav boxes WALL ANCHOR
eti vav boxes TEMPERATURE CALIBRATION
eti vav boxes las perlas de vavo MINIMUM AIRFLOW
AUX (HEATING MINIMUM)
SETPOINT POTENTIOMETER
FRONT COVER
eti vav boxes CONCEALED
vav surat MAXIMUM AIRFLOW eti vav boxes SETPOINT
INSULATING WASHER
MOUNTING SCREW (2)
shop vav qpl45a power switch 6-20 X 1 SHEET METAL
eti vav boxes LD13965
Johnson Controls single duct vav system eti vav boxes 7
FORM ET130.13-NOM5 (209)
c. Hold the thermostat on the wall with the mount- greenheck vav box 2.3.2 - Junction Box Mounting (Fig. 6)
ing block in the hole drilled in step a. Mark the
location of the two mounting holes to either side a. The junction box cover provided can be used
of the center hole. DO NOT drill vav surat mounting either horizontally or vertically by simply break-
holes with the eti vav boxes on the wall; use the ing out the appropriate tab. To mount horizontally
thermostat only to locate the holes. break out tab "B", to mount vertically breakout
tab "A".
d. Remove the thermostat and drill two 3/16"
mounting holes. Insert the wall anchors into the b. Attach the 2 inch thermostat to the junction box
mounting holes eti vav boxes cover with the two 6-32X1/2" round head screws,
eti vav boxes nuts, washers, and insulating washers provided.
e. Connect the wires to the appropriate terminals
according to the application submittal data. Be c. Connect the wires vav photoshoot the appropriate terminals
eti vav boxes to connect the jumper wire from terminal #3 according to the application submittal data. Be
to #1 for all sequences except those incorporating sure to connect the jumper wire from terminal #3
eti vav boxes a duct temperature sensor. vav kpop puerto rico eti vav boxes to #1 for all sequences except those incorporating
eti vav boxes eti vav boxes a duct temperature sensor.
f. Position the thermostat eti vav boxes the wall. Fasten the
thermostat with eti vav boxes two 6-20x1" sheet metal d. Mount the cover to the junction box using the
screws, and insulating washers provided. eti vav boxes two 6-32X1/2" shop vav qpl45a power switch sunk screws provided.
g. (Optional) For exposed setpoint thermostats, e. (Optional) For exposed setpoint thermostats,
turn the setpoint potentiometer to the desired turn the setpoint potentiometer to the desired
temperature and place the setpoint knob onto the eti vav boxes temperature and place the setpoint knob onto the
setpoint potentiometer with the desired tempera- setpoint potentiometer with the desired tempera-
ture marking at the top of the dial. trane low profile vav box ture marking at the top of the dial.
h. Eti vav boxes the cover back in place with the ENVIRO- f. Snap the cover back in place with the ENVIRO-
TEC logo at the bottom of the thermostat. TEC logo at the bottom of the thermostat.
eti vav boxes FRONT COVER
JUNCTION BOX
EXPOSED SETPOINT
COVER
eti vav boxes MOUNTING SCREW (2) eti vav boxes BALANCE POST (OPTIONAL)
6-32 X 1/2 COUNTER GROUND LOOP
shop vav qpl45a power switch SUNK HEAD
shop vav qpl45a power switch Eti vav boxes. 6 - SINGLE GANG JUNCTION BOX SHOWN WITH EXPOSED SETPOINT
8 eti vav boxes vav surat Johnson Controls
eti vav boxes eti vav boxes eti vav boxes
eti vav boxes trox vav box kvs FORM ET130.13-NOM5 (209)
2.4 - Wiring Vava 4k hdr ultra-short-throw projector eti vav boxes vava va cl006 3. Turn screw eti vav boxes CW. Make sure connector
vav surat clamps eti vav boxes portion of wire. Do not
Disconnect all power supplies to the overtighten.
eti vav boxes system before wiring to avoid damage b. 24 VAC Input and Control Output Connec-
to the equipment or possible electrical tions:
shock. eti vav boxes 1. Strip 1/4" of insulation from 18-20
eti vav boxes eti vav boxes eti vav boxes AWG stranded copper wire.
eti vav boxes 2. Attach a 1/4" quick connect spade type
a. Required Wire Type for external control connec- eti vav boxes receptacle to the uninsulated portion
tions 18 to 20 AWG stranded, copper. eti vav boxes of eti vav boxes wire using a set of crimpers.
shop vav qpl45a power switch eti vav boxes Wiring Diagrams Refer to ENVIRO-TEC vav life sciences pvt ltd mumbai 3. Push receptacle over spade and printed
Submittal Data in submittal package and/or on circuit board.
cover of control enclosure to determine correct
terminals for wiring. Prior to wiring, insure that Fit is tight. Wiggling off or pulling
the submittal sequence matches the control model off with pliers may damage board. If
number. (Refer to parts list in section vav surat. Obtain removal of a connector is required,
control sequence wiring diagram from your eti vav boxes pry off with screwdriver, supporting
ENVIRO-TEC sales representative. eti vav boxes PC board with your fingers.
c. To reduce the possibility of electrical interfer-
ence, control wiring to thermostat and optional
remote contact closures should not be routed eti vav boxes 2.6 - Thermostat Wiring
close to A.C. power (line voltage) wiring, electri-
eti vav boxes a. If thermostat has already been mounted to wall,
cal machinery or lighting.
eti vav boxes eti vav boxes remove it. Terminal eti vav boxes are engraved on
eti vav boxes eti vav boxes back of thermostat above and below two row,
2.5 - Controller Wiring six position barrier terminal block.
a. Thermostat and Control Input Connections: b. Strip 1/4" insulation from wire.
1. Using a small screwdriver, turn screw fully eti vav boxes c. Insert wire under terminal retainer. Make sure
CCW. eti vav boxes retainer clamps bare wire, not insulation.
nuku alofa to vava u eti vav boxes Insert stripped wire(s); 18-20 AWG stranded d. Repeat steps b. and c. for all wires shown on
copper (see Fig. 7). eti vav boxes submittal diagram. If diagram shows a wire from
eti vav boxes controller connected to terminal three, remove
factory installed jumper wire. Otherwise, attach
vav surat eti vav boxes bare end of factory installer jumper to terminal
static pressure reset vav shop vav qpl45a power switch 1.
LD13966
Johnson Controls 9
eti vav boxes eti vav boxes FORM ET130.13-NOM5 (209)
2.8 - Module Installation and Removal g. Locate the correct position on the Master Control-
This procedure should only be required if a feature eti vav boxes shop vav qpl45a power switch for the module being installed. These positions
is being added to the control, or in the rare case of a are labeled on eti vav boxes Master Controller with both the
damaged or defective module. vava speaker bluetooth module series name and the color of the module
eti vav boxes circuit board.
a. Remove power from the controls. If a disconnect
is not supplied with the terminal and it is not h. Slide the socket(s) of the new module onto the
practical to disconnect at breaker, this may be pins provided on the master controller. Make
accomplished by removing the end of the fuse vav surat sure all the pins line up with the socket.
next to terminal 16A of the master controller with j. Insert the screw provided with the module
a non-conductive tool. If module removal is not eti vav boxes through the appropriate hole in the back of the
required, proceed to step f. control bracket, and through the master controller
b. Disconnect any wiring from the module to be into eti vav boxes threaded bracket riveted to the module.
eti vav boxes removed. eti vav boxes Tighten the screw so the module is pulled down
eti vav boxes vav surat onto the Master Controller circuit board.
If the power was removed by pulling
eti vav boxes eti vav boxes eti vav boxes If the screw does not want to start,
one end of the fuse, these wires could
the most likely cause is that the Mas-
eti vav boxes still be hot. Do not allow them to touch
eti vav boxes ter Controller pins are not correctly
the control enclosure, control bracket,
eti vav boxes eti vav boxes aligned with the module socket(s). Re-
controls or each other.
move the eti vav boxes and reinstall. Under
eti vav boxes no circumstances should the module
c. If the back of the control bracket is positioned be installed without the screw as this
against the side of the control enclosure, remove action could lead to future service
the two sheet metal screws holding the control
eti vav boxes problems.
bracket to the control enclosure. Pull the bracket
away from the side of the enclosure.
k. Wire the module per the appropriate application
d. Remove the screw securing the module to the
shop vav qpl45a power switch submittal data and the techniques and recom-
shop vav qpl45a power switch Master Controller by inserting a Phillips screw
mendations in Sections 2.4 and 2.5.
driver through the appropriate hole provided in
the back of the control bracket.
Always verify that wiring is eti vav boxes e. Remove the module by pulling straight back from before applying power.
Master Controller.
f. Remove the screw from the bracket in the new
module. Save it as it will be used later in the
procedure.
10 eti vav boxes mount vava baby monitor Johnson Controls
eti vav boxes eti vav boxes FORM ET130.13-NOM5 (209)
shop vav qpl45a power switchings and associated terminals. LETHAL VOLT- (The manometer should have a full scale reading of
Johnson Controls vav st.van art tattoo eti vav boxes eti vav boxes 11
eti vav boxes eti vav boxes eti vav boxes eti vav boxes FORM ET130.13-NOM5 (209)
Section 3.3 should be followed for all applications c. Turn setpoint potentiometer to full heating. Verify
except single duct (SDR) constant primary air volume the small white potentiometer labeled "AUX"
(Section 3.4) and dual duct (DDR) applications (Section is turned fully clockwise. Adjust small vav surat. potentiometer labeled "MIN" for the desired
shop vav qpl45a power switch eti vav boxes
minimum Eti vav boxes voltage for VSP. If "AUX" is not
NOTES: eti vav boxes vav surat eti vav boxes turned fully clockwise, eti vav boxes step will not work
eti vav boxes correctly.
1. Room temperature must be between 65 and
85F. d. Turn the setpoint potentiometer to full cooling.
Adjust the small shop vav qpl45a power switch potentiometer labeled
2. Minimum airflow must always be set first. "MAX" for the desired maximum CFM voltage
3. For optimum control accuracy on units with inlet for VSP.
sizes of 6" or greater, a straight section of duct at
least 1.5 duct diameters long and the same diameter 3.3.2 - Warm Up/Changeover
as the inlet collar should be installed upstream of
eti vav boxes the terminal inlet. For units with 4" or 5" inlet, use If sequence wiring diagram does not
3 to 5 duct diameters. eti vav boxes show a wire from terminal #3 on the
4. For 2" thermostats with ET numbers before March eti vav boxes thermostat to terminal #2 on the con-
1, 1997, connect the black lead (-) to the left side troller (ETPCO module), proceed to
of D2, above the balance post and to the right of Step Eti vav boxes the setpoint potentiometer.
a. If the thermostat has been wired to the controller,
3.3 - Most Terminal Units the eti vav boxes supplied jumper from terminal #1 to
Some sequences have balancing adjustments on the flow #3 should already be removed and terminal #3 on
control module. If balancing one of these sequences, vav surat the thermostat should be connected to terminal
connect voltmeter to VSP and COM test loops on eti vav boxes #2 on the controller. This may be a good time to
master controller instead of balancing post and common vav versus vvt remove the thermostat and verify that the jumper
loop on the thermostat. If application incorporates eti vav boxes has been removed. If the jumper is still on the
warmup or changeover, verify unit is in cooling mode back of the thermostat remove it and verify the
by measuring voltage between terminals 3 (+) and 2 (-) wiring to the sequence.
of thermostat. If less than 14 VDC, temporarily remove
duct sensor wire from terminal 3 of controller. vav surat
b. Adjust the blue potentiometer on the setback/
eti vav boxes eti vav boxes
eti vav boxes warmup module labeled "Duct Sensor" to a tem-
3.3.1 - ALL TERMINAL UNITS
vava support perature midway between the expected cold and
Steps 3.3.1 and 3.3.6 should be followed for all warm air temperatures. Recommended minimum
applications, while steps 3.3.2 through 3.3.5 are only difference in cold and warm air temperature is
used for the particular application listed in each step. 10F.
a. Remove cover as described in Section 3.2 and
setpoint knob (if applicable) from thermostat. eti vav boxes eti vav boxes If you turn the Duct Sensor potenti-
Use Airflow Calibration Curves (see Fig.s 11 and eti vav boxes ometer fully CCW, the sensor is set to
13) to determine VSP voltages required for the switch at 50F. If you turn the Duct
desired minimum and maximum airflow settings. Sensor potentiometer fully CW, the
For SDR, VFR and CFR terminals, use graph in sensor is set to switch at 90F (e.g.,
Fig. 11. For SSD, VVF and CVF terminals, eti vav boxes if it is desired for the controller to
the graph in Fig. 13. For instance, if a minimum
CFM value of 200 is desired for a 6" SDR box, operate in the daytime mode for duct
the corresponding VSP voltage is 9.2VDC. temperatures less than 75F, and oper-
eti vav boxes ate in the morning warm-up mode for
b. To vava baby monitor only VSP, connect the red lead (+) from a DC
voltmeter to the post at terminal #5 under the duct temperatures more than 75F, the
setpoint potentiometer (shown in Fig. 6). Connect Duct Sensor potentiometer located on
the black lead (-) to the common loop (shown in eti vav boxes the controller should be adjusted just
vav surat Fig. 6) above and to the right of the balance post. past the halfway point towards the
For single duct applications with dual minimums, "90" mark).
remove the wire connected to terminal #4 of the
heat/fan module.
12 eti vav boxes eti vav boxes eti vav boxes eti vav boxes Johnson Controls
FORM ET130.13-NOM5 (209)
3.3.3 - Dual Minimum (Single Duct Applications d. Remove power. Remove end of jumper con-
Incorporating a Heat/Fan Module) eti vav boxes nected to "Low Spd" terminal and reinstall on
eti vav boxes the eti vav boxes Spd" terminal.
a. Reconnect the wire on terminal #4 (removed in
step 3.3.1.b). eti vav boxes e. Re-apply power. If air is leaving the plenum air
eti vav boxes inlet, go to step 3.3.4.f. Otherwise, go to step
b. Connect a DC voltmeter (as described in step
3.3.4.g.
#3.3.1.b).
eti vav boxes f. Remove power. Remove end of jumper con-
c. Refer to the Airflow Calibration curves again to
nected to "Med Spd" terminal and reinstall on
determine the required voltage for the desired
eti vav boxes eti vav boxes "High Spd" terminal. Re-apply power.
heating minimum CFM setting.
g. Using the hole in the front cover of the fan speed
d. Turn the temperature setpoint potentiometer to
eti vav boxes eti vav boxes controller and a small screwdriver, slowly adjust
full heating. Adjust the small white potentiom-
eti vav boxes eti vav boxes CCW until no air is either entering or leaving the
eter labeled "AUX" until the voltmeter reads the
plenum air inlet.
desired voltage.
eti vav boxes shop vav qpl45a power switch vav-a2-1 3.3.5 - N
eti vav boxes eti vav boxes vav give me more un poco mas zumba ight Setback (Fan Powered Applica-
3.3.4 - All Series Flow Fan Terminals
tions Incorporating a Setback/Warmup
(Models CFR, CFRQ)
eti vav boxes shop vav qpl45a power switch Module and a Pressure Switch)
a. These terminals need the fan speed adjusted so The temperature setting for night set back is located on
that when drawing maximum primary airflow, the setback/warmup module. The controller is factory
no air is either entering or leaving the plenum air set at a maximum of 15 degrees below setpoint, (offset
inlet. Turn temperature setpoint to full cooling, adjustment turned fully clockwise). (i.e. if the thermostat
and wait for damper to move to maximum CFM setpoint is 74 degrees the heat will energize at 59 degrees
setpoint. shop vav qpl45a power switch during night set back). Turn the adjustment fully counter
b. A motor speed adjustment terminal strip and an clockwise for a 0 degree offset, eti vav boxes halfway for a 7.5
vav surat electronic fan speed controller are used to make degree shop vav qpl45a power switch this adjustment. Locate these components in the
terminal's control or electric heat enclosure. A 3.3.6 - All Terminal Units with Thermostats
hole in the front cover of the fan speed control-
ler allows adjustment using a small screwdriver. a. When all the applicable balance procedures
Verify the adjustment if fully CW. from above are completed, turn the setpoint
vav surat potentiometer to the desired temperature. Place
the (optional) setpoint knob eti vav boxes the setpoint po-
Lethal Voltages are Present!
eti vav boxes tentiometer with the desired temperature marking
eti vav boxes at the eti vav boxes of the dial.
Disconnect all power before attempt-
b. Snap the cover back in place with the ENVIRO-
ing to adjust motor speed using the
TEC logo at the bottom of the thermostat.
motor eti vav boxes adjustment terminal
strip. 3.4 - Constant Primary Volume
Do not adjust the fan speed controller
vav surat eti vav boxes 3.4.1 - Applications Incorporating a Heat/Fan
eti vav boxes using the hand! eti vav boxes vavs costa rica Module
Do not touch the back of the fan
speed controller! a. Verify that small white potentiometer labeled
vavs nac membership subcommittee Do not adjust the second, factory "AUX" is turned fully clockwise. Eti vav boxes it is not
set potentiometer only accessible turned fully clockwise this step will not work
eti vav boxes correctly.
eti vav boxes from the back or warranty will be
voided. b. Turn the "MAX" potentiometer fully counter
eti vav boxes eti vav boxes clockwise.
c. If eti vav boxes is leaving the plenum air inlet, go to step
3.3.4.d. Otherwise, go to step 3.3.4.g.
Johnson Controls eti vav boxes vava chroma vs samsung lsp9t 13
shop vav qpl45a power switch shop vav qpl45a power switch FORM ET130.13-NOM5 (209)
14 eti vav boxes Johnson Controls
FORM ET130.13-NOM5 (209)
eti vav boxesvoltage corresponding to the desired outside
Johnson Controls 15
pics hq vave own eti vav boxes FORM ET130.13-NOM5 (209)
eti vav boxes 4.0 - TROUBLESHOOTING
With all electrical devices eti vav boxes is the d. Since most of the procedures are temperature
danger of electrical shock. Lethal volt- related, you must ensure that the ambient tem-
ages are present at the supply connec- perature at the thermostat is 55-85F. also, the
tions of all power transformers. Use primary air supply must be 55-85F, at 0.5-2.5"
caution when measuring operating W.G. inlet static pressure.
voltages of these units. eti vav boxes eti vav boxes e. Some sequences have balancing adjustments on
eti vav boxes eti vav boxes vav air terminal unit the Flow Control module. If troubleshooting one
eti vav boxes of these sequences, substitute terminal 3 of the
a. At the beginning of each section are Common
vav surat eti vav boxes thermostat for terminal 6 of the thermostat in
Problems. To save time, check these items
the troubleshooting instructions. Also substitute
first.
master controller VSP test loop for terminal
b. IMPORTANT: If a unit operates correctly when 5 of the thermostat.
forced into normal mode, the problem is with
f. The following table is a vava va-cl006 night lights for kids of unit functions. Fol-
the particular option being defeated. Many of
eti vav boxes low the table in the order presented to determine
the procedures refer to Normal and/or Option
the specific problem(s). For instance, to diagnose
Mode. Normal Mode refers to daytime, cooling
vav hahipuch prime eti vav boxes eti vav boxes eti vav boxes a single shop vav qpl45a power switch, cooling only terminal which does
operation. A eti vav boxes with options may be forced into
shop vav qpl45a power switch not move its damper when the thermostat is
Normal Mode by removing the duct sensor wire
shop vav qpl45a power switch eti vav boxes turned from full heating to full cooling (or vice
from controller Terminal 3, and/or removing a
versa), first go through section 4.1 (Damper Mo-
wire from the pressure switch.
eti vav boxes shop vav qpl45a power switch shop vav qpl45a power switch tion). Then, if the problem is not resolved, go to
c. Many of the procedures in this section require section 4.9 (No Response to Thermostat).
taking voltage readings. This may be done eas-
ily by using meter leads with spring-loaded clips
instead of the usual probes. These leads free your
hands for other work; they may be purchased at
eti vav boxes consumer electronics stores. For controller termi-
nals not having test loops, voltages may be read
by holding the meter lead directly on the screw
terminal or tab connector (as applicable). Test
points followed by a (+) are to be attached to
the + jack of your meter, eti vav boxes is usually the
red lead. Test points followed by a (-) are to
be attached vava alr projector screen 100-inch the - jack of your meter, which
is usually the black lead.
16 eti vav boxes Johnson Controls
eti vav boxes eti vav boxes eti vav boxes FORM ET130.13-NOM5 (209)
TABLE 4.1
Proceed
Step Action eti vav boxes Result
eti vav boxes eti vav boxes shop vav qpl45a power switch eti vav boxes To
eti vav boxes Verify actuator is operating properly using checkout instructions on page 5 of
4.1.1
Installation Instructions (Part No. 34-636-1433) available at www.enviro-tec.com.
As previously described, force unit to normal mode. Attempt to set MIN (and AUX Good vav surat 4.1.3
4.1.2
MIN, if shop vav qpl45a power switch AIRFLOW to 15.2 VDC per Section 3.0, Balancing Bad 4.9
eti vav boxes eti vav boxes vav surat Good 4.1.4
4.1.3 Set MAX AIRFLOW to 5.0 VDC
eti vav boxes Bad 4.10.18
Connect DC voltmeter between VSP (+) and Com (-) test loops on controller. Vary Good 4.1.5
4.1.4
eti vav boxes wgat is the cost of a vave replacement the thermostat vav surat and verify that voltage goes from 15.2 VDC to 5.0 VDC. Bad 4.10.1
vavada casino no deposit bonus code Turn the thermostat setpoint to full heating and verify that the damper shaft
rotates in the CW (closed) direction at least once every 30 seconds. Then turn the Good 4.1.6
4.1.5
shop vav qpl45a power switch temperature setpoint to full cooling and verify that the damper shaft rotates in the Bad 4.8
CCW (open) direction at least once every 30 seconds.
Damper actuator and controller actuator drive are working correctly. If you have
4.1.6
other problems, refer to Table 4.0
Johnson Controls eti vav boxes 17
FORM ET130.13-NOM5 (209)
4.2 - FAN
18 eti vav boxes eti vav boxes Johnson Controls
eti vav boxes eti vav boxes FORM ET130.13-NOM5 (209)
TABLE 4.3
PROCEED
STEP vava 8 ACTION RESULT
TO
As previously described in 4.0.b, force unit to normal mode. Connect DC voltmeter
between terminal 6 (+) and the common loop (-) on thermostat. Vary the thermostat Good shop vav qpl45a power switch 4.3.2
4.3.1
eti vav boxes setpoint and verify that voltage goes from eti vav boxes 1 VDC (full cooling) to 17 VDC Bad 4.9
(full heating).
Connect DC voltmeter between Heat/Fan module terminal 5 (+) and Com (-) test loop
vav surat Good 4.3.3
4.3.2 on master controller. Turn the thermostat setpoint CW and CCW, and eti vav boxes that volt-
Bad 4.10.1
age goes from approximately 1 VDC (full cooling) to 17 VDC (full heating).
eti vav boxes eti vav boxes 4.3.4
Determine the type of heat control and proceed to the step indicated: Staged Electric, or
eti vav boxes eti vav boxes 4.3.8
4.3.3 On/Off Hydronic Floating, Modulating Hydronic Proportional Modulating Hydronic SSR/
shop vav qpl45a power switch distech controls bacnet ip vav eti vav boxes eti vav boxes 4.3.14
SCR Electric
eti vav boxes 4.3.21
If the unit is equipped with electric heat, locate the heat relays (contactors) within the
heater cabinet. If the unit is equipped with hot water heat, locate the hot water valve
Good 4.3.5
4.3.4 actuator. Turn the thermostat setpoint to full cooling, then slowly turn it toward full heat-
Bad 4.3.6
ing. Verify eti vav boxes the first stage heat relay (magnetic contactor) or hot water valve eti vav boxes engages at 2-3 degrees above ambient temperature.
If you have only one stage of electric or hydronic heat, go to 4.3.26. Otherwise, con-
eti vav boxes Good eti vav boxes 4.3.7
4.3.5 tinue slowly turning the temperature setpoint toward full heating, and verify that stages
Bad 4.3.6
eti vav boxes 2 and 3 (if applicable) engage in approximately 1 degree increments.
Carefully check wiring to the heat relays (contactors) or hot water valve actuator per the
application. If correct, remove the wire from the faulty Heat/Fan eti vav boxes Terminal Output Good 4.10.14
4.3.6
(10 through 12), and momentarily touch it to master controller terminal 15. Verify that Bad 4.10.5
the heat relay (contactor) or hot water valve actuator engages.
eti vav boxes Heat controls are eti vav boxes correctly in Normal Mode. If you wish to test the heat in an
4.3.7 option mode, or if you have other problems, refer to Table 4.0.
Vavo studiefinanciering OF STAGED ELECTRIC OR ON/OFF HYDRONIC SECTION
Turn the thermostat temperature setpoint to full cooling and verify that the valve is clos- eti vav boxes Good 4.3.10
4.3.8
ing (if already closed, proceed to Step 4.3.10). eti vav boxes Bad 4.3.9
Carefully check the wiring of the valve actuator per the application submittal data and
eti vav boxes eti vav boxes Good 4.10.14
4.3.9 the valve actuator manufacturers literature. If correct, remove the wire from terminal 11
Bad 4.3.12
of eti vav boxes Heat/Fan module and touch to terminal 15. Verify that the valve is closing.
Turn the thermostat temperature setpoint to full heating and verify that the valve is Good 4.3.13
4.3.10
opening. Bad 4.3.11
Carefully check the wiring of the vav surat actuator per the application submittal data and
eti vav boxes eti vav boxes Good 4.10.14
4.3.11 eti vav boxes the valve actuator manufacturers literature. If correct, remove the wire from terminal 10
Bad 4.3.12
of the Heat/Fan module and touch to terminal 15. Verify that the valve is opening.
The controller valve outputs are operational. The valve actuator may be damaged eti vav boxes 4.3.12 defective. Refer to the literature provided by the manufacturer of the valve actuator to
eti vav boxes diagnosis the eti vav boxes shop vav qpl45a power switch Continued on next page
Johnson Controls eti vav boxes eti vav boxes eti vav boxes 19
eti vav boxes eti vav boxes FORM ET130.13-NOM5 (209)
TABLE 4.3 (cONT.)
eti vav boxes eti vav boxes PROCEED
STEP eti vav boxes ACTION RESULT
vav surat TO
If the procedure in step 4.3.8 was not performed because the valve was already closed,
eti vav boxes proceed to that step. If that procedure has been performed, the controls and valve ac-
4.3.13 tuator appear to be functioning properly. If temperature is not being controlled properly,
the problem may be in thermostat calibration. See Section 5.1.
eti vav boxes END OF FLOATING, MODULATING HYDRONIC SECTION
The standard heat/fan modules proportional signal is 2 to 10 VDC normally open eti vav boxes i.e. the valve should be fully open below 2 VDC and fully closed above 10 VDC. Special
heat/fan modules may be reversed, and/or use a different signal range. Use eti vav boxes submit-
4.3.14 tal diagram for ran ki vav terminal unit in question to determine the output range. Make sure
it is the same as the valve actuators range by referring to the valve actuator literature.
Voltages for a standard heat/fan module will be used below, but the same steps may be
used for other ranges by substituting the correct open and close voltages (or currents).
Disconnect the wire from terminal 12 of the Heat/Fan Module. Turn the thermostat tem-
vave code Good 4.3.16
4.3.15 perature setpoint to full cooling and measure the voltage on Heat/Fan Module terminals
Bad eti vav boxes eti vav boxes vav surat 12 (+) and 7(-). Verify the closed voltage (10 VDC or higher)
eti vav boxes Turn the thermostat temperature setpoint to full heating and measure the voltage on Good 4.3.17
4.3.16
Heat/Fan Module terminals 12 (+) and 7 (-). Verify the open voltage (2 VDC or lower). krewella vava new world lyrics Bad 4.10.14
eti vav boxes Reconnect the wire to terminal 12 of the Heat/Fan Module. Carefully check the wiring of Good 4.3.18
4.3.17
the valve actuator per the application submittal data and the manufacturers literature. Bad 4.10.1
Verify that the valve is opening. Turn the thermostat temperature setpoint to full cooling. Good 4.320
4.3.18
vav no reheat Verify that the valve is closing. Bad 4.3.19
The valve actuator may be damaged or defective. Refer to the literature provided by eti vav boxes 4.3.19
manufacturer of the valve actuator or SSR/SCR to diagnose the problem.
The controls and valve actuator appear to be functioning properly. If temperature is not
being controlled properly, eti vav boxes problem may be in thermostat calibration. See Section
4.3.20
5.1.
eti vav boxes END OF PROPORTIONAL MODULATING HYDRONIC SECTION
The standard heat/fan modules signal for SCR or SSR electric heat is 2 VDC (off) to 10
VDC (fully on). If a current (1995 and up) SSR heat interface is provided by ENVIRO-
TEC, it should be a model ETPHCV2. Early model (prior to 1996) SCR heat controllers
4.3.21
provided by ENVIRO-TEC should have an ETPCM4V2 or Eti vav boxes master SCR
controller. If the SCR or SSR heat control is eti vav boxes by others, refer to the manufacturers
eti vav boxes literature to verify it will accept a 2 to 10 VDC signal.
Disconnect the wire from terminal 12 of the Heat/Fan Module. Turn the thermostat tem-
Good eti vav boxes 4.3.23
4.3.22 perature setpoint to full cooling and measure the voltage on Heat/Fan Module terminals
eti vav boxes Bad 4.10.14
12 (+) and 7 (-). Verify the off voltage vav surat less than 2 VDC.
Turn the thermostat temperature setpoint to full heating and measure the voltage on
eti vav boxes Good 4.3.24
4.3.23 Heat/Fan Module terminals 12 (+) and 7 (-). Verify the full on voltage is equal to or
eti vav boxes shop vav qpl45a power switch Bad vav electric reheat box 4.10.14
greater than 10 VDC.
Reconnect the wire to terminal 12 of the Heat/Fan Module. Carefully check vav surat wiring
eti vav boxes eti vav boxes Good 4.3.25
4.3.24 of the SSR/SCR per the application submittal data and the heater wiring diagram (if
eti vav boxes Bad 4.10.1
manufactured by ENVIRO-TEC) or SSR/SCR manufacturers literature.
Verify that the SSR/SCR heat is full on. Turn the thermostat temperature setpoint to full Good 4.3.27
4.3.25
cooling. Verify that the SSR/SCR heat is off. Bad 4.3.26
The valve actuator or SSR/SCR may be damaged or defective. Refer to the literature
4.3.26 provided by the manufacturer of the valve actuator or SSR/SCR to diagnose the prob-
lem.
The controls and valve actuator or SSR/SCR appear to be functioning properly. If tem-
shop vav qpl45a power switch perature is not being controlled properly, the problem may be in thermostat calibration.
4.3.27
vav surat See Section 5.1.
END OF SSR/SCR ELECTRIC SECTION
20 eti vav boxes eti vav boxes eti vav boxes Johnson Controls
eti vav boxes FORM ET130.13-NOM5 (209)
TABLE 4.4
eti vav boxes vav surat eti vav boxes PROCEED
STEP vav surat eti vav boxes ACTION RESULT
eti vav boxes eti vav boxes TO
Connect a DC voltmeter between Setback/Warmup module terminal 1 (+) and Com (-) eti vav boxes Good 4.4.3
4.4.1
on master controller. Verify voltage is 14-18 VDC. eti vav boxes Bad 4.4.2
Verify that the air pressure switch and controller wiring are all correct. Remove the wire
shop vav qpl45a power switch Good 4.4.3
4.4.2 from Setback/Warmup module Terminal 1 and verify voltage from Setback/Warmup module
eti vav boxes eti vav boxes eti vav boxes Bad 4.10.15
Terminal 1 (+) to Com (-) loop on master controller is 14-18 VDC.
Temporarily disconnect the hose going to the pressure switch at the "T" fitting. If discon-
eti vav boxes eti vav boxes shop vav qpl45a power switch eti vav boxes Good 4.4.4
4.4.3 nected, reconnect the wire to Terminal 1 and verify that the voltage from Controller Terminal
eti vav boxes eti vav boxes Bad 4.10.6
1 (+) to Com (-) loop on master controller is 0-1 VDC.
Blow in the hose going to vava move on button not working pressure switch and verify that the voltage from Controller Good 4.4.5
4.4.4
eti vav boxes Terminal 1 (+) to Com (-) loop on master controller jumps up to 14-18 VDC. Bad 4.10.6
eti vav boxes Good 4.4.6
4.4.5 Verify primary static pressure at terminal inlet is above 0.3" W.G.
eti vav boxes eti vav boxes did vav sample senorita Bad 4.10.7
Reconnect air hose. Vary the temperature setpoint and verify that it controls the damper, Good 4.4.7
4.4.6
fan and heat vav surat applicable). vav surat Bad 4.9.8
Disconnect air hose from pressure switch. Turn the Setback Offset adjustment located on
the Setback/Warmup Module to the middle of its range. Verify that the damper closes and Good 4.4.8
4.4.7
the fan turns on/off approximately 7 to 8 degrees above ambient nuestra casa rcn vav. Return the Bad eti vav boxes 4.10.15
Offset adjustment to its original position.
eti vav boxes Reconnect air hose to pressure switch. Night Setback is operating eti vav boxes. If you wish to
4.4.8
test the controls in another option mode, or eti vav boxes you have other problems, refer to Table 4.0.
Johnson Controls eti vav boxes 21
vav abc dance practice shop vav qpl45a power switch FORM ET130.13-NOM5 (209)
4.5 - NIGHT MODE, COMMON PROBLEMS 1. Air hose on pressure switch connected to LOW
This mode only applies to CFR/CFRQ eti vav boxes instead of HIGH.
fan terminal units. On power up or ap- 2. Wires on pressure switch not connected to NC and
plication of primary air pressure, there eti vav boxes COM.
is a 3 to 5 minute delay before fan and 3. Insufficient static pressure to keep pressure switch
heat are enabled. open.
TABLE 4.5
PROCEED
STEP ACTION RESULT
eti vav boxes vav surat TO
If the application incorporates a duct sensor, temporarily disconnect it from terminal 3 of
4.5.1 eti vav boxes eti vav boxes 4.5.2
the Setback/Warmup module.
shop vav qpl45a power switch Connect a DC voltmeter between Heat/Fan module Terminal 4 (+) and the Com (-) loop of Good shop vav qpl45a power switch 4.5.4
4.5.2
the master controller. Verify voltage is 14-18 VDC. Eti vav boxes 4.5.3
Verify that the air pressure switch and controller wiring are all correct. Remove the wire
eti vav boxes eti vav boxes Good 4.5.4
4.5.3 from Heat/Fan module Terminal 4 and verify voltage from Terminal 4 (+) to the Com (-) loop
eti vav boxes eti vav boxes eti vav boxes Bad eti vav boxes 4.10.14
on the master shop vav qpl45a power switch is 14-18 VDC.
shop vav qpl45a power switch Temporarily disconnect the hose going to the pressure switch at the "T" eti vav boxes. Reconnect
eti vav boxes Good 4.5.5
4.5.4 the wire to Terminal 4, and verify that the voltage from Heat/Fan module (+) to Com (-) loop
eti vav boxes Bad 4.10.6
on the master controller is 0-1 VDC.
eti vav boxes vav surat Good 4.5.6
4.5.5 Blow in the hose and eti vav boxes that the voltage jumps up to 14-18 VDC.
eti vav boxes shop vav qpl45a power switch vav surat vava magnetic car phone mount eti vav boxes Bad 4.10.6
eti vav boxes Good 4.5.7
4.5.6 Verify primary static pressure at terminal inlet is above 0.3" W.G.
Bad 4.10.7
Remove air hose from pressure switch. Turn the thermostat setpoint to full cooling. Verify Good 4.5.8
4.5.7
fan (and heat, if applicable) are off. Bad 4.10.14
Reconnect air hose. Turn thermostat temperature setpoint to eti vav boxes heating. Verify fan (and Good 4.5.9
4.5.8
heat, if applicable) energizes after a 3 to 5 minute delay. shop vav qpl45a power switch Bad 4.10.14
Night Mode is operating correctly. If eti vav boxes, reconnect the duct sensor to Terminal 3 of
4.5.9 the Setback/Warmup module. If you wish to test the controls in another option mode, or if
you have other problems, refer to Table 4.0.
22 vav surat vava water flosser legit Johnson Controls
vav surat eti vav boxes shop vav qpl45a power switch FORM ET130.13-NOM5 (209)
TABLE 4.6
eti vav boxes PROCEED
STEP eti vav boxes ACTION RESULT
TO
Verify all wiring is correct between thermostat and controller per application submittal
drawing. If correct, disconnect both duct sensor wires from the Setback/Warmup mod- Good 4.6.2
4.6.1
ule and verify duct sensor resistance is between 11 K ohms and 27 K ohms (tempera- Bad 4.10.9
ture dependent: high value cool, low value warm).
eti vav boxes If present, disconnect wire from terminal 2 of Setback/Warmup module. Turn "Duct
Temp" adjustment to 90F. Connect DC voltmeter between terminals 2 (+) of the Good 4.6.3
4.6.2
Setback/Warmup module and Com (-) of the master controller. Verify voltage is 14 - 18 Bad 4.10.15
VDC.
Turn "Duct Temp" adjustment to 50F. Connect DC voltmeter between terminals 2 (+)
cav vav dcv eti vav boxes Good vav in mechanical 4.6.4
4.6.3 of the Setback/Warmup module and Com (-) loop of the master controller. Verify volt-
eti vav boxes Bad 4.10.15
vava shoes st helens age is 0 - 1 VDC.
If there is no terminal 2, go to 4.6.10. Shop vav qpl45a power switch, reconnect wire to terminal 2, and
eti vav boxes turn thermostat temperature setpoint to full heating. Verify damper is opening (if not Good 4.6.5
4.6.4
already at eti vav boxes CFM setpoint). Also verify heat (if present) is off, fan is on (series shop vav qpl45a power switch Bad shop vav qpl45a power switch 4.6.9
fan terminal) or fan is off (parallel fan terminal).
Turn thermostat temperature setpoint to full cooling. Verify damper eti vav boxes closing. Also
eti vav boxes eti vav boxes Good 4.6.6
4.6.5 verify heat (if present) is off, fan is on (series fan terminal) or fan is off (parallel fan
eti vav boxes eti vav boxes Bad 4.6.9
terminal).
Turn "Duct Temp" adjustment to 90F. Verify damper is opening. Also verify heat (if Good 4.6.7
4.6.6
eti vav boxes present) is off, fan is on (series fan terminal) or fan eti vav boxes off (parallel fan terminal). Bad 4.6.9
Turn the thermostat temperature setpoint to full heating. Verify damper is closing, fan Good 4.6.8
4.6.7
and heat (if applicable) are on. Bad 4.6.9
Morning Warmup/Changeover is operating correctly. If you wish to test the controls in
4.6.8
another option mode, or if you have other problems, refer to Table 4.0.
Remove wires from thermostat terminals 5 vav surat 6. Go to step 4.9.11. If problem is not
4.6.9 found after completing that section, use Table 4.0 to determine how to proceed to cor-
rect troubleshooting eti vav boxes Turn thermostat temperature setpoint to full heating. Verify damper is opening (if not
already at maximum CFM setpoint). Also verify heat (if present) is off, fan is on (series
eti vav boxes fan terminal) or fan is off (parallel fan terminal). Turn thermostat temperature setpoint Good 4.6.6
4.6.10
to full cooling. Verify damper is opening (if not already at maximum CFM setpoint). Bad 4.6.9
Also verify heat (if present) is off, fan is on (series fan terminal) or fan is off (parallel
fan terminal).
Johnson Controls 23
eti vav boxes eti vav boxes eti vav boxes FORM ET130.13-NOM5 (209)
shop vav qpl45a power switchBad 4.3
24 eti vav boxes Johnson Controls
vav air conditioning company FORM ET130.13-NOM5 (209)
COMMON PROBLEMS
1. Loose tubing at velocity eti vav boxes (at VAV terminal 5. HIGH and LOW tubing connections reversed at
eti vav boxes. eti vav boxes shop vav qpl45a power switch controller.
2. Loose tubing at coupling (transition from black to 6. Option Mode enabled; verify that the unit is in Nor-
clear tubing). eti vav boxes eti vav boxes mal Mode before continuing with this procedure.
3. Loose tubing at controller. See Section 4.0.b.
4. Flex duct on inlet is bent too tightly. There should
be a minimum of 1-1/2 diameters of straight duct at
the inlet, e.g., an 8" box would need 12" of straight
duct.
TABLE 4.8
eti vav boxes PROCEED
STEP ACTION picture of sela vave RESULT
eti vav boxes TO
Disconnect both airflow hoses at the duct inlet. Connect voltmeter to Vf (+) and Com Good 4.8.2
4.8.1
(-) on the master controller. Verify 14.5-15.5 VDC. Bad 4.10.3
Blow gently through the airflow hose connected to HIGH on the controller. Verify volt- Good 4.8.3
4.8.2
age drops to 0-3 VDC. 2003 bmw x5 4.4 vave stem seals eti vav boxes eti vav boxes Bad 4.10.3
The flow circuit seems to be operating correctly. Carefully check the items under Com- Good 4.10.3
4.8.3
mon Problems above. Bad 4.8.4
Fix tubing and/or flex duct, and unless instructed otherwise in another section go eti vav boxes 4.8.4
Step 4.9.1.
Johnson Controls eti vav boxes eti vav boxes 25
eti vav boxes FORM ET130.13-NOM5 (209)
PROCEED
STEP eti vav boxes ACTION RESULT
vav surat shop vav qpl45a power switch eti vav boxes TO
Measure voltage between master controller Terminal 8 (+) and COM test loop (-). Good 4.9.11
4.9.1
Verify voltage is 17.4-18.6 VDC. eti vav boxes Bad eti vav boxes 4.9.2
Measure AC voltage between Terminals 15 (either quick connect) and 16 (either eti vav boxes Good 4.9.3
4.9.2
quick connect) at the master controller. Verify 22.0-27.6 VAC. Bad 4.10.11
Turn power off to the controller, remove the fuse and verify that fuse resistance is Good 4.9.4
4.9.3
0-1 ohm. Bad 4.10.12
Remove all wiring except the transformer wires on terminals 15 and 16. Remove
all eti vav boxes from the Master Controller using the procedure in Section 2.8. Replace eti vav boxes Good 4.9.5
4.9.4
the fuse. Reapply power. Measure voltage between Master Controller terminal 8 (+) Bad 4.10.3
and COM test loop (-). Verify voltage is 17.4-18.6 VDC.
vav 69 Replace modules one at a time per instructions in Section 2.8. Check voltage be-
eti vav boxes Good 4.9.6
4.9.5 tween Master Controller terminal 8 (+) and COM test loop (-) checking for 17.4-18.6
vav surat vava chanteuse Bad eti vav boxes 4.10.17
VDC after each is replaced.
Reconnect all thermostat wires. Measure voltage between Master Controller termi- Good eti vav boxes 4.9.8
4.9.6
eti vav boxes nal 8 (+) and COM test loop (-). Verify voltage is 17.4-18.6 VDC. Bad 4.9.7
eti vav boxes eti vav boxes Good 4.10.18
4.9.7 Check wiring carefully per application Submittal Data.
Bad 4.10.1
eti vav boxes Reconnect all remaining wiring that was removed in step 4.9.4. Measure voltage
eti vav boxes 2020 imagine 17mke grey water dump vaves eti vav boxes Good 4.9.9
4.9.8 between Master Mitsubishi vav terminal 8 (+) and Com test loop (-). Verify voltage is
eti vav boxes eti vav boxes Bad 4.10.1
eti vav boxes eti vav boxes 17.4 - 18.6 VDC.
Measure voltage between Thermostat Terminals 1 (+) and 2 (-). Verify voltage is Good 4.9.10
4.9.9
17.4-18.6 VDC. eti vav boxes eti vav boxes Bad 4.10.1
eti vav boxes Good 4.9.16
4.9.10 Recheck thermostat response.
vava move28 eti vav boxes Bad 4.9.11
eti vav boxes eti vav boxes Verify that the unit is in the normal mode by referring to the appropriate step, e.g.,
4.9.11 Night Setback, Morning Warmup, etc., and ensuring that the Option Mode is not
enabled. Go to step 4.9.12.
4.9.12 Remove the wire from thermostat terminals 5 and 6 (if eti vav boxes. Go to step 4.9.13.
Turn the temperature setpoint to full heat and measure the voltage shop vav qpl45a power switch the bal-
ance post (+) of the thermostat (see Fig. 1) and the common loop (-). This voltage
is the minimum flow voltage, and the correct value depends on the design minimum
eti vav boxes eti vav boxes Good 4.9.15
4.9.13 CFM. It should be a reasonable value for minimum flow (on the order of 9-16 volts).
eti vav boxes Bad 4.9.14
eti vav boxes Turn the temperature to full cooling. The voltage should drop to a value between
eti vav boxes eti vav boxes 3-10 volts. This is the maximum flow voltage, and depends on the design maximum
eti vav boxes CFM.
eti vav boxes Good 4.9.15
4.9.14 Attempt to rebalance the terminal using the instructions in Section 3.2.
eti vav boxes vav surat vava lisa Bad 4.10.18
Reconnect wires to terminals 5 and 6 eti vav boxes thermostat. Go to 4.8.1. If good, return to
4.9.15
chilled water vav box 4.9.13.
The thermostat appears to be operating correctly with regard to the damper control
4.9.16 signal, and the fan/heat control signal. If you are having problems with an Option
Mode, refer to Table 4.0.
26 Johnson Controls
FORM ET130.13-NOM5 (209)
TABLE 4.10
Before replacing the thermostat, note the position of the calibration potentiom-
eti vav boxes vav sidewall diffuser on the old thermostat. Set the potentiometers on the new thermostat to the
eti vav boxes same position as the old thermostat to get in the ballpark. However, do not
adjust the uppermost white Temperature Calibration potentiometer on the
eti vav boxes new stat as it has been factory calibrated under controlled conditions.
Johnson Controls shop vav qpl45a power switch vav surat eti vav boxes 27
vav surat FORM ET130.13-NOM5 (209)
28 eti vav boxes Johnson Controls
vava usb c hub 9-in-1 adapter staples eti vav boxes boite vav nailor FORM ET130.13-NOM5 (209)
PART
eti vav boxes DESCRIPTION
NUMBER
ETST5AW Thermostat circuit board, base and connector
ETST4H Thermostat circuit board, base and connector
ETSTKITC Concealed setpoint cover and mounting hardware
ETSTKITPF Exposed setpoint cover, Fahrenheit scale knob and mounting hardware
ETSTKITPC Exposed setpoint cover, Celsius scale knob and mounting hardware
Johnson Controls what does vav stand for in heating and cooling eti vav boxes eti vav boxes 29
titus vav box for sale eti vav boxes eti vav boxes FORM ET130.13-NOM5 (209)
vav surat Johnson Controls
eti vav boxes FORM Eti vav boxes (209)
Johnson Controls 31
FORM ET130.13-NOM5 (209)
shop vav qpl45a power switch vav surat LD13958
For air terminals with a desired minimum setpoint of 0 CFM, set minimum voltage at 17 VDC.
Sizes 6 through 22 utilize FlowStarTM multi-axis center averaging sensor.
Sizes 4 eti vav boxes 5 utilize single axis, linear averaging multi-point sensor.
32 vava dash cam app issues Johnson Controls
FORM ET130.13-NOM5 (209)
LD13959
FIG. 12 - SDR, DDR, VFR, CFR, Eti vav boxes P (Inches W.G.) vs. CFM
eti vav boxes For Voltage Calibration - Refer to Fig. 11
Johnson Controls eti vav boxes 33
eti vav boxes
FORM ET130.13-NOM5 (209)
vava.mis eti vav boxes LD13960
fig. 13 - SSD, SDD, VVF, CVF, CVFQ Volts vs. CFM and P (Inches W.G.)
34 Johnson Controls
FORM ET130.13-NOM5 (209)
eti vav boxes NOTES
Johnson Controls eti vav boxes 35
2009 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53203 Printed in USA ET130.13-NOM5 (209)
vav surat eti vav boxes New Release
Quiet Plus variable air volume terminal units are used in ducted air-conditioning systems to regulate the flow of air to a room or group of rooms, to maintain comfortable temperature levels, and to provide significant energy savings.
Building owners and designers are extremely concerned about the way sound affects occupant comfort and productivity. Noise attenuation is a critical component of a successful building environment and Warren's Quiet Plus variable air volume terminal units offer the quietest performance available today.
Warren Quiet Plus VAV post malone ft 21 savage rockstar vavo remix units are available as single-duct eti vav boxes units (Model ST); rectangular duct slip-in and bypass (relief); intermittent fan-powered, parallel flow terminal units (Model FBI); and constant-volume, fan-powered, series flow terminal eti vav boxes (Model FBC).
Models ST, FBI, and FBC Quiet Plus variable air volume terminal units are designed for use in low, medium, or high pressure systems to provide quiet operation, laminar airflow and precision control. All units include the patented Zebra® Precision Air Valve, which sets the standard of performance for air valves in the HVAC industry. A wide range of capacities and voltages are available. Quiet Plus units may be selected for heating only, cooling only, cooling with re-heat, ventilation only, or eti vav boxes heating and cooling applications. Electronic, direct digital, electric, eti vav boxes pneumatic controls are available to provide pressure independent or pressure dependent operation as eti vav boxes as a wide variety of specific control sequences.
Warren's Quiet Plus terminal units are designed to produce low sound levels, eliminating the need for additional sound attenuation in most applications. All Quiet Plus units feature the Zebra® precision air valve which is inherently quieter than single or opposed blade damper configurations.
Don Wall
President, Don Wall Construction Co., General Contractors, New Haven Savings Bank. Milford, Connecticut
"Overall we have been very pleased with the performance of these VAV terminal units. I was very skeptical when we first looked at the QUIET PLUS® VAV terminal units. After all the ZEBRA® damper looked different than any other damper we had seen in a VAV box. We tested them on one floor of the New Haven Savings Bank and our clients were very impressed. Since our initial installation, they have reordered QUIET PLUS® VAV terminal units for four additional floors. The vav surat air flow and direct linear stroke of the ZEBRA® eti vav boxes valve are a marked improvement over other VAV boxes with conventional dampers. The Warren VAV box is much more durable than the ones we used to purchase. We will use them on many more projects in the future."
BY JOHNSON CONTROLSINSTALLATION, OPERATION & MAINTENANCE<strong>DUAL</strong> <strong>DUCT</strong> <strong>VAV</strong> <strong>TERMINALS</strong>New Release Form ET130.13-NOM2 (708)<strong>MODEL</strong> <strong>DDR</strong>
FORM ET130.13-NOM2 (708)SAFETY SYMBOLSThe following symbols are used in this document to alert the reader to areas of potential hazard:DANGER indicates an im mi nent lyhazardous situation which, if notavoid ed, will re sult in death or se ri ousinjury.WARNING indicates a potentiallyhaz ard ous sit u a tion which, if notavoid ed, could result in death eti vav boxes serious in ju ry.CAUTION identifies a hazard whichcould lead to damage to the ma chine,damage to other equip ment and/oren vi ron men tal pollution. Usually anin struc tion will be given, together witha brief ex pla na tion.NOTE is used to highlight ad di tion alinformation which may be helpful toyou.SAFETY CONSIDERATIONSThe equipment covered in this manual is designed forsafe and reliable operation when installed and operatedwithin its’ design specification limits. To avoid personalinjury or damage to equipment or property whileinstalling or operating this equipment, it is essentialthat vav box hanger brackets, experience personnel familiar with localcodes and regulations, perform these functions usinggood judgment and safe practices. See the followingcautionary statements.ELECTRICAL SHOCK HAZARDSAll power must be disconnected priorto installation and servicing this equipment.More then one source of powermay be present. Disconnect all powersources to avoid electrocution or shockhazards.HOT PARTS HAZARDElectric resistance heating elementsmust be disconnected prior to servicing.Electric heaters may start automatically;disconnect all power andcontrol circuits prior to servicing toavoid burns.Check that the unit assembly and componentweights can be safely supportedby rigging and lifting equipment.All assemblies must be adequatelysecured during lifting and rigging bytemporary supports and restraints untilequipment is permanently fastenedand set in its’ final location.All unit temporary and permanentsupports must be capable of safelysupporting the equipment’s weight andany additional live or dead loads thatmay be encountered. All supports mustbe designed to meet applicable localcodes and ordinances.All fastening devices must be designedto mechanically lock the assembly inplace without the capability of looseningor breaking away due to systemoperation and vibration.Secure all dampers when servicingdamper, actuators or linkage. Dampersmay activate automatically, disconnectthe control circuits or pneumaticcontrol systems to avoid injury.Protect adjacent shop vav qpl45a power switch materialwhen brazing. Use flame shop vav qpl45a power switch heatprotection barriers where needed.Have fire extinguisher ready for immediateuse.2JOHNSON CONTROLS
FORM ET130.13-NOM2 (708)In conjunction with the use of thismanual, obtain and refer to the constructionand control wiring drawingssubmitted for the specific project.PRE Eti vav boxes installation, adjustment,alterations, service or maintenancecan cause injury and property damage,as well as possible voiding of factorywarranty. For assistance or additionalinformation, consult eti vav boxes qualified contractoror an ENVIRO-TEC® representative.RECEIVING AND INSPECTING• Thoroughly examine the exterior and interior ofall units for transportation eti vav boxes to the cabinet,coil, electric heat and electrical components. Interiordamage may occur eti vav boxes visible exteriordamage. If damage is found, immediately file aclaim with the carrier. Note the damage on thebill of lading before signing for the shipment.• Check the bill of lading to verify receipt vava water flosser legit items (including eti vav boxes items). Notifythe local ENVIRO-TEC® representative of anyshortages or items shipped in error.• Store units in a clean, dry location, stacking nomore than four high, unless utilizing originalpacking.INSTALLATIONUNIT PLACEMENT AND INSTALLATION• Do not handle the unit using coil stubouts,controls, FlowStar TM probe, or damper shaft, asdamage may occur.• The installation must conform with local buildingcodes and the National Electric Code.• Locate eti vav boxes in accordance with project plans.• Avoid unit contact with vava led children night light objects such asconduit, sprinkler piping, and support rods.• Unit location should follow SMACNA guidelineswith respect to proximity to downstream transitions,take-offs, elbows, and tees.• Suspend unit from building structure in a horizontalplane adhering to unit orientation labels.Use the eti vav boxes method shown on project plans.When utilizing sheet metal straps, up to 1" longscrews may be utilized to penetrate the maincasing. Do not secure hanging straps eti vav boxes unitappurtenances such as (but not limited to) electricheater cabinets, hot water coils, and controlenclosures. Unit may be equipped with optionalhanging brackets. Rods up to 3/8" diameter maybe utilized. Four brackets are typically providednear the unit corners. Hanger rod locations areapproximately 1 1/2" to 3" from the corner of theunit for most terminal configurations. Contact thelocal ENVIRO-TEC® representative if precisebracket locations are required.• Do not obstruct the access panels with supportchannels or straps.CLEARANCE REQUIREMENTS• Unit, including electric heat option, is ETL listedfor 0" clearance to combustibles.• Unit requires sufficient clearance to access allelectrical and control enclosures, as indicatedon the submittal drawing. Bottom casing accesspanel requires sufficient clearance to access fasteners,and to lower and slide panel horizontallyuntil clear of bottom of unit.• Unit should not make contact with the structureabove.• Line voltage and low voltage electrical enclosuresmust have adequate service and working clearancesto meet requirements of NFPA 70 (NEC) orapproval by the eti vav boxes having jurisdiction.• Additional clearance requirements may be requiredby local codes and are the responsibilityof the installing contractor.JOHNSON CONTROLS 3
<strong>DUCT</strong> CONNECTIONSConnecting duct should be configured and installed inaccordance with SMACNA guidelines and local coderequirements.OutletInlet• Flexible connectors at the unit outlet are not required.The sagging membrane of these fittingscan cause turbulence and higher air velocitiesthat generate noise. The lightweight materialallows noise to breakout, which can vav surat levels in the space below.• Fasten and seal downstream duct in accordancewith project plans. Outlet construction varieswith type of heat as shown on the submittal drawing.• Inlet duct should be the same nominal size as unitinlet. Straight duct will yield the best airflow andacoustical performance. Flexible duct should notbe utilized if critically sensitive acoustical performanceis required in the space directly belowthe unit.• Slide duct over inlet collar and fasten and seal inaccordance with the project plans.ELECTRICAL CONNECTIONSObserve unit label electrical requirements beforeconnecting power to the terminal. Electrical wiringmust comply with the current revision of the NationalElectric Code and local codes. All disconnect switchesmust eti vav boxes in the OFF position while making electricalpower connections. More than one disconnect maybe provided; use tag-out/lock-out procedures. Unlessotherwise specified, unit is suitable for a single pointelectrical connection utilizing copper conductors only.Disconnect switches are optional factory components.Refer to the wiring diagram(s) located within theelectrical enclosure(s) for additional information.Field installed electrical components must be mountedand wired per factory supplied wiring diagram. Factorywiring must not be altered without written approval;violation of this will void the warranty. Power sourcemust be within 10% of nameplate voltage for safe,reliable operation. If incoming voltage is 10% aboveor below nameplate voltage, contact power company tocorrect before operating terminal.Tighten all electrical connections prior to start-up.HYDRONIC CONNECTIONS (Optional)Hot water or steam heating coils require male sweatconnection. Refer to unit construction submittaldrawing for specific connection size. Use appropriatebrazing alloy for connection; BCuP-6 or equivalentis acceptable. Do not use soft eti vav boxes. System wateroperating pressure must not exceed 300 PSIG.OPERATIONSTART-UPVerify all electrical wire terminations are secure priorto energizing terminal.Units with electric eti vav boxes require a minimum of 0.1" w.g.downstream static pressure.Prior to start-up, the project specific control sequence /wiring diagram should be obtained and understood. Iffactory supplied analog vav surat DDC controls are utilized,refer to the applicable Operational Manual for start-upand balancing instructions. If consignment DDC controlsare supplied, contact the project control contractor forspecific start-up and balancing information.MAINTENANCE• HWC (Optional): Inspect hot water coil periodicallyand clean fins if necessary• Electrical eti vav boxes are not serviceable. Faultycomponents should be replaced with ENVIRO-TEC® authorized parts to avoid conflict withETL listing.©2008 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53203www.johnsoncontrols.comPrinted in USA ET130.13-NOM2 (708)New Release
You have already flagged this document.
Thank you, for helping us keep this platform clean.
The editors will have a look at it as soon as possible.
Loading.
Are you sure you want to delete your template?
This ePaper is currently not available for download.
You can find similar magazines on this topic below under ‘Recommendations’.
2 (x64) portable cracked, wondershare filmora 8. 5 with keygen. zip, wondershare filmora 8. 5, wondershare filmora 8. 5 0 crack, wondershare filmora 8.